White Paper: Cold Plate Development and Qualification (OCP Cooling Environments - Cold Plate)

Open Compute Project Foundation · Samantha Yates, David Zhou, Edward Kung (Intel), Huang Jiaming, Zhao Shuai, Li Rengang (Inspur)

A multi-vendor OCP guide to the mechanical design, thermal performance, quality and reliability requirements for single-phase cold plates and the test methods used to qualify them: flatness, hydrostatic and leak testing, corrosion and salt spray, and thermal cycling. It is older than most OCP cold-plate documents but remains the main open reference on cold-plate qualification.

CC BY-SA 4.0: share with attribution under the same licence

On this page

Overview

The document defines development and test methods for single-phase cold plate technology. Its rationale is that high-TDP processors cannot always be met by air cooling and that in some regions new data centres must have a PUE below 1.3. A cold plate is a liquid-channelled heat sink placed on the processor; it consists of a heat exchanger (base and top cover), fluid connectors and a retention bracket.

The design section separates 1-piece and 2-piece cold plates: in the 2-piece type the exchanger and bracket are separate, so the bracket can be redesigned for a new processor family and the exchanger reused as a cost saving. The processes joining base and cover (brazing, friction stir welding, soldering, O-ring sealing) are compared in a table; for example brazing supports high pressure but is costly and anneals the copper, reducing stiffness, while O-ring sealing is cheap but has lower pressure, leak-life and temperature capability. Because process marginalities introduce defects, the qualification plan should include samples from a representative production line.

Requirements fall under three headings. For mechanics: meeting the processor supplier's mass, flatness and loading limits, plus surface roughness and height. For integration: electrochemical potential difference between wetted metals of at most 0.15 V, and flow impedance lower than pump pressure. For thermal performance: defined processor temperature limit, fluid temperature and flow rate, and fluid velocity into the plate below 1.5 m/s to prevent erosion. In the hydrostatic test the plate is held at maximum operating pressure for 5 minutes and at 3 times that pressure for 2 minutes.

Test methods follow in order: ISO 12781-2:2011 for flatness, ISO 21920-2:2021 for roughness, X-ray for internal defects, thermal resistance at several flow rates, pressure-drop measurement, ASTM D2570 and ICP for corrosion and metal-ion analysis, ASTM B117 salt spray, hydrostatic verification after shock and vibration, and temperature cycling with a cycle count aimed at the processor's expected lifetime power cycles. Hydrostatic verification is repeated after each stress test. The document also includes a glossary of cooling-loop components.

Key points

  1. Fluid velocity into the cold plate should stay below 1.5 m/s to prevent erosion.
  2. Leak test: hold at maximum operating pressure for 5 minutes, then at 3x maximum operating pressure for 2 minutes (IEC 62368-1 framework).
  3. Any metal-to-metal interface in the cold plate should have an electrochemical potential difference of at most 0.15 V to avoid galvanic corrosion.
  4. Exterior corrosion resistance is assessed by ASTM B117 salt spray; base flatness is measured per ISO 12781-2:2011 and roughness per ISO 21920-2:2021.
  5. Suspended particulate in the flushing fluid should be below 50 um.
  6. A 2-piece cold plate allows the bracket to be redesigned for new processors while the exchanger is reused.
  7. Joining methods: brazing handles high pressure but anneals copper; friction stir welding does not anneal copper but is costly and slow; soldering is cheaper but can be voided and brittle; O-ring sealing is cheap but limited in pressure and life.
  8. Temperature-cycling counts should match the processor's expected lifetime power cycles; thermal performance and hydrostatic verification are repeated afterwards.
  9. ASTM D2570 and ICP metal-ion measurement (ASTM D6130, D5185) are recommended as early corrosion indicators.

Using it in design

  • In the cold-plate procurement specification, require a 1.5 m/s maximum inlet velocity, the 5-minute and 3x pressure leak test, and ASTM B117 salt-spray results.
  • List the wetted metals and check the electrochemical potential difference between them against the 0.15 V limit; where different metals are present, plan an integrated corrosion qualification.
  • In TCS design, compare the cold-plate pressure drop with CDU pump pressure and check how seasonal fluid-temperature change affects flow.
  • If several processor generations are planned, evaluate the 2-piece cold plate for cost and reuse.
  • Confirm the supplier's qualification plan includes samples from a representative production line and covers hydrostatic verification after shock, vibration and temperature cycling.

Who should read it

Engineers designing cold plates and liquid-cooled servers, procurement and quality teams, qualification laboratories and TCS designers.

Document contents

  1. Introduction and scope
  2. Cold plate technology (design variations, manufacturing processes, assembly, technology cooling system)
  3. Requirements (mechanical, thermal performance, reliability)
  4. Test methods: mechanical testing (dimensions, structural, cold plate integration, cosmetic)
  5. Test methods: performance testing (thermal performance, fluid pressure drop)
  6. Test methods: reliability testing (hydrostatic pressure, corrosion, dynamics, temperature cycling)
  7. Conclusion
  8. Glossary and references
  9. Appendix A: 2-piece cold plate assembly

Related standards

  • IEC 62368-1
  • ASTM B117
  • ISO 12781-2:2011

Read the document

ocp-cold-plate-development-qualification-2022.pdf

PDF · 0.8 MB · English

CC BY-SA 4.0: share with attribution under the same licence

The document is provided unaltered because its licence permits redistribution.

Publication details

Authors
Samantha Yates, David Zhou, Edward Kung (Intel); Huang Jiaming, Zhao Shuai, Li Rengang (Inspur)
Publisher
Open Compute Project Foundation
Year
2022
Document language
English
Source type
Industry body
Access
Open licence (downloadable)
Licence
CC BY-SA 4.0: share with attribution under the same licence
Licence evidence
www.opencompute.org
Original licence note

Creative Commons Attribution-ShareAlike 4.0 International; licence verified from the licence statement in the document itself. Attribution to the authors and publisher is kept; adaptations must keep the same licence.

Citation

Samantha Yates, David Zhou, Edward Kung (Intel); Huang Jiaming, Zhao Shuai, Li Rengang (Inspur) (2022). White Paper: Cold Plate Development and Qualification (OCP Cooling Environments - Cold Plate). Open Compute Project Foundation. https://www.opencompute.org/documents/ocp-cold-plate-development-and-qualification-with-integrated-comments-pdf/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.