White Paper: Cold Plate Development and Qualification (OCP Cooling Environments - Cold Plate)
Open Compute Project Foundation · Samantha Yates, David Zhou, Edward Kung (Intel), Huang Jiaming, Zhao Shuai, Li Rengang (Inspur)
A multi-vendor OCP guide to the mechanical design, thermal performance, quality and reliability requirements for single-phase cold plates and the test methods used to qualify them: flatness, hydrostatic and leak testing, corrosion and salt spray, and thermal cycling. It is older than most OCP cold-plate documents but remains the main open reference on cold-plate qualification.
CC BY-SA 4.0: share with attribution under the same licence
On this page
Overview
The document defines development and test methods for single-phase cold plate technology. Its rationale is that high-TDP processors cannot always be met by air cooling and that in some regions new data centres must have a PUE below 1.3. A cold plate is a liquid-channelled heat sink placed on the processor; it consists of a heat exchanger (base and top cover), fluid connectors and a retention bracket.
The design section separates 1-piece and 2-piece cold plates: in the 2-piece type the exchanger and bracket are separate, so the bracket can be redesigned for a new processor family and the exchanger reused as a cost saving. The processes joining base and cover (brazing, friction stir welding, soldering, O-ring sealing) are compared in a table; for example brazing supports high pressure but is costly and anneals the copper, reducing stiffness, while O-ring sealing is cheap but has lower pressure, leak-life and temperature capability. Because process marginalities introduce defects, the qualification plan should include samples from a representative production line.
Requirements fall under three headings. For mechanics: meeting the processor supplier's mass, flatness and loading limits, plus surface roughness and height. For integration: electrochemical potential difference between wetted metals of at most 0.15 V, and flow impedance lower than pump pressure. For thermal performance: defined processor temperature limit, fluid temperature and flow rate, and fluid velocity into the plate below 1.5 m/s to prevent erosion. In the hydrostatic test the plate is held at maximum operating pressure for 5 minutes and at 3 times that pressure for 2 minutes.
Test methods follow in order: ISO 12781-2:2011 for flatness, ISO 21920-2:2021 for roughness, X-ray for internal defects, thermal resistance at several flow rates, pressure-drop measurement, ASTM D2570 and ICP for corrosion and metal-ion analysis, ASTM B117 salt spray, hydrostatic verification after shock and vibration, and temperature cycling with a cycle count aimed at the processor's expected lifetime power cycles. Hydrostatic verification is repeated after each stress test. The document also includes a glossary of cooling-loop components.
Key points
- Fluid velocity into the cold plate should stay below 1.5 m/s to prevent erosion.
- Leak test: hold at maximum operating pressure for 5 minutes, then at 3x maximum operating pressure for 2 minutes (IEC 62368-1 framework).
- Any metal-to-metal interface in the cold plate should have an electrochemical potential difference of at most 0.15 V to avoid galvanic corrosion.
- Exterior corrosion resistance is assessed by ASTM B117 salt spray; base flatness is measured per ISO 12781-2:2011 and roughness per ISO 21920-2:2021.
- Suspended particulate in the flushing fluid should be below 50 um.
- A 2-piece cold plate allows the bracket to be redesigned for new processors while the exchanger is reused.
- Joining methods: brazing handles high pressure but anneals copper; friction stir welding does not anneal copper but is costly and slow; soldering is cheaper but can be voided and brittle; O-ring sealing is cheap but limited in pressure and life.
- Temperature-cycling counts should match the processor's expected lifetime power cycles; thermal performance and hydrostatic verification are repeated afterwards.
- ASTM D2570 and ICP metal-ion measurement (ASTM D6130, D5185) are recommended as early corrosion indicators.
Using it in design
- In the cold-plate procurement specification, require a 1.5 m/s maximum inlet velocity, the 5-minute and 3x pressure leak test, and ASTM B117 salt-spray results.
- List the wetted metals and check the electrochemical potential difference between them against the 0.15 V limit; where different metals are present, plan an integrated corrosion qualification.
- In TCS design, compare the cold-plate pressure drop with CDU pump pressure and check how seasonal fluid-temperature change affects flow.
- If several processor generations are planned, evaluate the 2-piece cold plate for cost and reuse.
- Confirm the supplier's qualification plan includes samples from a representative production line and covers hydrostatic verification after shock, vibration and temperature cycling.
Who should read it
Engineers designing cold plates and liquid-cooled servers, procurement and quality teams, qualification laboratories and TCS designers.
Document contents
- Introduction and scope
- Cold plate technology (design variations, manufacturing processes, assembly, technology cooling system)
- Requirements (mechanical, thermal performance, reliability)
- Test methods: mechanical testing (dimensions, structural, cold plate integration, cosmetic)
- Test methods: performance testing (thermal performance, fluid pressure drop)
- Test methods: reliability testing (hydrostatic pressure, corrosion, dynamics, temperature cycling)
- Conclusion
- Glossary and references
- Appendix A: 2-piece cold plate assembly
Related standards
- IEC 62368-1
- ASTM B117
- ISO 12781-2:2011
Read the document
ocp-cold-plate-development-qualification-2022.pdf
CC BY-SA 4.0: share with attribution under the same licence
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Samantha Yates, David Zhou, Edward Kung (Intel); Huang Jiaming, Zhao Shuai, Li Rengang (Inspur)
- Publisher
- Open Compute Project Foundation
- Year
- 2022
- Document language
- English
- Source type
- Industry body
- Access
- Open licence (downloadable)
- Licence
- CC BY-SA 4.0: share with attribution under the same licence
- Licence evidence
- www.opencompute.org
Original licence note
Creative Commons Attribution-ShareAlike 4.0 International; licence verified from the licence statement in the document itself. Attribution to the authors and publisher is kept; adaptations must keep the same licence.
Citation
Samantha Yates, David Zhou, Edward Kung (Intel); Huang Jiaming, Zhao Shuai, Li Rengang (Inspur) (2022). White Paper: Cold Plate Development and Qualification (OCP Cooling Environments - Cold Plate). Open Compute Project Foundation. https://www.opencompute.org/documents/ocp-cold-plate-development-and-qualification-with-integrated-comments-pdf/
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.