White Paper: Digital Twins for Data Centers, Revision 1.0, Version 1.2
Open Compute Project · Stephen Clement, Matthew Kaufeler et al.
OCP guidance defining data-centre digital twins, maturity levels, interoperability and lifecycle use cases. Virtual commissioning is described as an opportunity to expose errors before physical tests, not as evidence that physical acceptance has been achieved.
CC BY-SA 4.0: share with attribution under the same licence
On this page
Overview
The document states that scale, complexity and workload change demand an evolution from static management to intelligent, adaptive design and operations. Developed under the OCP Digital Twin Initiative, it gives a definition agreed by stakeholders and a maturity model to remove confusion in the industry over definitions, capabilities and implementation standards. The revision history shows the initial submission in December 2025, version 1.1 in June 2026 after OCP review comments, and version 1.2 in July 2026 after Steering Committee feedback.
By its definition, a digital twin is a dynamic, behavioural virtual replica of a physical system or object, existing or intended for future creation, dynamically synchronised with its physical counterpart through continuous data exchange; it captures not just physical attributes but behaviour, interactions and operational context. A twin created before the physical counterpart is a Digital Twin Prototype (design twin), and one in operation is a Digital Twin Instance; a digital thread runs through both and decommissioning. The twin is distinguished from BIM and similar technologies by its emphasis on real-time operational optimisation, energy efficiency and behaviour simulation.
Use cases are grouped across the lifecycle: planning and design (rack layout, power distribution and cooling modelling, capacity and space planning), construction and commissioning, operations (monitoring with DCIM, visualising airflow and cooling demand, simulating the impact of hardware changes before implementation) and sustainability. For commissioning, because the twin includes functional behaviour, some tests due during physical commissioning can be anticipated by simulation, avoiding late discovery of malfunctions or design errors.
The maturity model defines levels from 0 to 5: level 0 is legacy manual operation with no DT capability and level 5 is autonomous, self-optimising systems, with dashboards and real-time analysis, simulation and hardware-change impact prediction, and advisory and autonomous adjustment in between. An example table makes the levels concrete for cooling, electrical and other subsystems (for cooling, level 1 shows temperature and airflow dashboards, level 3 simulates the thermal and airflow impact of new hardware, and level 5 autonomously adjusts cooling and fan output). The model is additive and incremental; operators are not required to implement every level. Interoperability is discussed together with the fact that no single standard has emerged and toolchains are fragmented.
Key points
- Definition: a digital twin is a behavioural virtual replica of a physical system, synchronised through continuous data exchange; it captures physical attributes, behaviour and operational context.
- A twin built before its physical counterpart is a Digital Twin Prototype (design twin); the in-operation twin is a Digital Twin Instance; a digital thread links them.
- The maturity model runs from 0 to 5: 0 is legacy manual operation with no DT capability and 5 is autonomous, self-optimising systems.
- The model is additive and incremental; operators do not need to reach every level.
- In commissioning, functional simulation can anticipate some physical commissioning tests and expose design errors earlier.
- Version 1.2 is dated July 2026; the initial submission was December 2025 and version 1.1 June 2026.
- Data-centre digital twins are distinguished from BIM by real-time operational optimisation, energy efficiency and behaviour simulation.
- No single standard has yet emerged as the definitive framework for digital twins; toolchains are fragmented and interoperability remains a challenge.
- Use cases include rack layout, power distribution and cooling modelling, capacity and space planning, and DCIM-integrated operational optimisation.
Using it in design
- At project start, write into the specification which maturity level (0-5) is targeted for the digital twin and for which subsystems (cooling, electrical, capacity).
- Use the design twin (digital twin prototype) for rack layout, power distribution and cooling modelling, and plan a digital thread to hand the same data model over to the operational twin (digital twin instance).
- Put virtual commissioning ahead of physical tests, not in place of them: use simulation to expose design errors, but carry out the physical acceptance tests all the same.
- When choosing tools and vendors, require open and industry-standard interfaces and data models; record the fact that no single standard has settled and toolchains are fragmented as a risk.
- Design the monitoring points list that links DCIM and BMS data to the twin so that airflow and cooling demand can be visualised.
Who should read it
Data-centre designers and commissioning engineers, operations and DCIM teams, digital twin and simulation software vendors and decision makers.
Document contents
- Introduction (definition, digital twins in the data center, problems solved)
- Digital Twin Capability and Maturity
- Use Cases in the Data Center Lifecycle (planning and design, construction, commissioning: detect defects before the physical commissioning, operational optimization, sustainability)
- Standards and interfaces
- Digital Twin Maturity (maturity level examples)
- Data Integration and Interoperability, and challenges
Read the document
ocp-digital-twins-data-centers-v12-2026.pdf
CC BY-SA 4.0: share with attribution under the same licence
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Stephen Clement; Matthew Kaufeler; Jean Marc Gaufrés; Kourosh Nemati; Sherman Ikemoto
- Publisher
- Open Compute Project
- Year
- 2026
- Document number
- Revision1.0, Version1.2
- Document language
- English
- Source type
- Industry body
- Access
- Open licence (downloadable)
- Licence
- CC BY-SA 4.0: share with attribution under the same licence
- Licence evidence
- opencompute.org
Original licence note
Creative Commons Attribution-ShareAlike 4.0 International; licence verified from the licence statement in the document itself. Attribution to the authors and publisher is kept; adaptations must keep the same licence.
Citation
Stephen Clement; Matthew Kaufeler; Jean Marc Gaufrés; Kourosh Nemati; Sherman Ikemoto (2026). White Paper: Digital Twins for Data Centers, Revision 1.0, Version 1.2. Open Compute Project. Revision1.0, Version1.2. https://www.opencompute.org/documents/ocp-digital-twin-whitepaper-v1-2-final-pdf/
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.