Data Center Standards and Guidelines for Public Institutions, Version 2.0
Tanzania e-Government Authority
A February 2026 Tanzania e-Government Authority standard that classes public hosting as Tier II, III and IV: N+1 to 2N+1 redundancy, generator autonomy of 12, 72 and 96 hours, and availability of 99.741%, 99.982% and 99.995%.
On this page
Overview
The document (eGA/EXT/IRA/003, version 2.0, approved 18 February 2026) guides public institutions, under the e-Government Act of 2019 and its 2020 Regulations, in deciding in which approved hosting environment to place ICT applications; its aim is not to set up new data centres but to assess whether existing data centres meet the minimum requirements to be an approved hosting environment. Three classes are defined: Server Room (Tier II), Critical Data Center (Tier III) and Mission-Critical Data Center (Tier IV).
The standards cover site selection (hazards, access, utilities), space planning, architecture, mechanical, electrical (transformers, UPS, batteries, generators, grounding, surge protection), cabling, fire protection, security, monitoring, maintenance and operations. Site selection asks to avoid seismically active areas and flood risk, with a single point of entry and adequate setback. For cooling, indoor temperature is held between 18 and 23 degrees and relative humidity between 45 and 50 percent, with multiple HVAC systems instead of one central chiller.
Redundancy rises with class: Tier II has N+1 in some components including power, cooling, network equipment and ISP; Tier III has at least N+1 in all components including UPS, ICT infrastructure, auxiliary generator, cooling and ISP; Tier IV has at least 2N+1 in all components. The generator must carry the IT load and HVAC for at least 12 hours in Tier II, 72 in Tier III and 96 in Tier IV; generators are run at least one hour each month and a full load test and switching test is done at least yearly.
The operations section gives minimum service availability with annual downtime: Tier II 99.741% (22 hours a year), Tier III 99.982% (1.6 hours), Tier IV 99.995% (26.3 minutes). Appendix I has tables showing which classes each requirement is mandatory for; annual full-load and switching tests are marked for critical and mission-critical classes, and periodic reliability and performance tests of fibre and copper cabling for all three classes. The document is a national public-sector regulation; it does not replace Uptime Institute Tier certification.
Key points
- Three classes: Server Room (Tier II), Critical Data Center (Tier III), Mission-Critical Data Center (Tier IV).
- Redundancy: Tier II N+1 in some components, Tier III at least N+1 in all, Tier IV at least 2N+1 in all.
- Generator autonomy (IT load and HVAC): Tier II at least 12 hours, Tier III 72 hours, Tier IV 96 hours.
- Generators are run at least one hour monthly; a full load test and switching test is done at least yearly.
- Minimum availability: Tier II 99.741% (22 hours a year), Tier III 99.982% (1.6 hours), Tier IV 99.995% (26.3 minutes).
- Indoor temperature 18-23 degrees Celsius and relative humidity 45-50%; manufacturer ranges are also considered.
- Multiple HVAC systems instead of one central chiller; raised floor plenum static pressure held 5 percent higher.
- Site selection avoids seismically active areas and flood risk; a single entry point and setback distance are sought.
- Tier IV requires two physically diverse meet-me rooms and redundant automatic transfer switches.
- The document is the 2026 version, setting minimum conditions for assessing public institutions' approved hosting environments.
Using it in design
- In a public project, fix the target class (Tier II, III or IV) first and write the redundancy (N+1 or 2N+1) and generator autonomy (12, 72, 96 hours) requirements into the design basis.
- Size fuel storage to the class autonomy requirement and add monthly generator runs and the annual full-load and switching test to the operations plan.
- In cooling design, compare the 18-23 degree and 45-50% humidity targets with manufacturer ranges and avoid dependence on a single chiller.
- Align availability targets (annual downtime of 22 hours, 1.6 hours, 26.3 minutes) with the SLA and redundancy design.
- Use the standard as a national minimum requirement, not as a substitute for Uptime Tier certification.
Who should read it
Engineers and public ICT managers designing, assessing or preparing approved hosting environment applications for data centres in Tanzania or similar public regulatory settings.
Document contents
- Introduction (overview, purpose, rationale, scope)
- Site Selection Standards
- Space Planning Standards
- Architectural Standards
- Mechanical Systems Standards
- Electrical Systems Standards
- Cabling Infrastructure Standards
- Fire Protection Standards
- Security Standards
- Monitoring Standards
- Maintenance Standards
- Operation Standards
- Implementation, Review and Enforcement
- Appendix I: Standards Requirements for Different Government Data Centers
Publication details
- Authors
- Tanzania e-Government Authority
- Publisher
- Tanzania e-Government Authority
- Year
- 2026
- Document number
- eGA/EXT/IRA/003, v2.0
- Document language
- English
- Source type
- Government / public
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Public official source inspected. No document-specific commercial redistribution permission established. Metadata and original brief summaries only; local evidence is not a redistribution package.
Citation
Tanzania e-Government Authority (2026). Data Center Standards and Guidelines for Public Institutions, Version 2.0. Tanzania e-Government Authority. eGA/EXT/IRA/003, v2.0. https://www.ega.go.tz/uploads/standarddocuments/sw-1773257204-FINAL%20Reviewed_Data%20Center%20Standards%20and%20Guidelines%20for%20Public%20Institutions-18.2.2026.pdf