Technical guidePDF2023

Practices and Insights into Liquid Cooling on Meta's AI Training Platforms (OCP contribution, August 2023)

Open Compute Project Foundation (Meta contribution) · Cheng Chen, Yin Hang et al.

Case studies from Meta's Zion and Grand Teton AI training platforms comparing the cooling limits of air, air-assisted liquid cooling and facility water cooling, with lessons from three generations of cold-plate design. It is a grounded source on real cold-plate behaviour behind OCP's 30 degC coolant roadmap.

CC BY-SA 4.0: share with attribution under the same licence

On this page

Overview

The document is based on single-phase cold-plate solutions with 25 vol.% propylene glycol (PG25) coolant. AI training module power has risen steadily since 2016; a simplified trendline presented at an OCP regional summit panel forecast 1 kW in 2025 and 1.5 kW before 2030, and multi-chip modules could go well above that. In its 2021 roadmap Meta derived roofline limits for air cooling, air-assisted liquid cooling (AALC) and facility water cooling (FWC).

The rooflines rest on these boundary conditions: for air, dry air at 30 degC supply and 0.145 CFM/W; for AALC, PG25 at 40 degC supply and 1.5 LPM/kW; for FWC, PG25 at 30 degC supply and 1.5 LPM/kW; plus a 0.2 degC.cm2/W thermal interface and margins for uncertainty. The analysis shows module and HBM power trends breaching the air-cooling roofline and even liquid cooling with warmer coolant, which is why the move from air to liquid was adopted, with AALC as a transitional solution.

The 30 degC technical fluid supply setpoint rests on three factors: facility PUE and WUE goals, condensation limits on the air supply loop, and the ability to support or stretch to the foreseeable roadmap. The document notes the final setpoint may change, but facilities with that capability keep their flexibility. Three cold-plate generations are described: Tide 1.0 (assembly and reliability oriented), Tide 1.5 (performance and simplicity oriented, at least 60% lower case-to-inlet thermal resistance than air, lowest 0.02 degC/W) and Tide 2.0 (parallel GPU cold-plate loop, leak detection and an assembly kit).

The most instructive part is the field issues: 1-3 degC case-temperature rise in a 90-day accelerated reliability test with one outlier at 5 degC; about +/-10% cold-plate flow variation across 4 Zion systems in a hypothetical rack flow network, with quick-disconnect variation the largest contributor; and junction-to-inlet resistance of 0.05-0.06 degC/W across 6 Zion systems with an outlier at 0.047 degC/W. The document states plainly that results may not represent today's best solutions.

Key points

  1. Assumed boundary conditions: air at 30 degC and 0.145 CFM/W; AALC with PG25 at 40 degC and 1.5 LPM/kW; facility water cooling with PG25 at 30 degC and 1.5 LPM/kW.
  2. 30 degC supply was chosen for facility PUE and WUE goals, condensation limits on the air loop and roadmap headroom.
  3. Training module power forecast: 1 kW in 2025 and 1.5 kW before 2030; multi-chip modules can exceed that.
  4. Tide 1.5: at least 60% lower case-to-inlet resistance than air and lowest 0.02 degC/W; TIM contact resistance estimated at 0.1 degC.cm2/W.
  5. In a 90-day accelerated reliability test, TTV case temperature rose 1-3 degC, with one outlier reaching 5 degC.
  6. A hypothetical flow network showed about +/-10% cold-plate flow variation across 4 Zion systems; quick-disconnect variation was the most impactful factor.
  7. Across 6 Zion systems (48 OAM modules, average 1.4 LPM per cold plate), junction-to-inlet resistance was 0.05-0.06 degC/W with an outlier at 0.047 degC/W.
  8. For the ASIC, lid and TIM1 contribute about half of total resistance; for HBM, heat crosstalk from the ASIC and internal stack resistance make up most of it.
  9. Leak detection and flow halt should exist at module, board, system or rack level, with minimal latency and software dependency.

Using it in design

  • When fixing the facility water supply temperature (for example 30 degC), use the separate rooflines for AALC and direct facility water cooling and the flow target of 1.5 LPM/kW as design inputs.
  • Reserve temperature margin on cold-plate performance for lifetime degradation, and make long-term reliability validation a standard commissioning step.
  • In rack manifold design, account for quick-disconnect impedance variation and flow-distribution uncertainty of the order of +/-10%; do not assume equal flow.
  • Define leak detection and flow-halt tiers (module, board, system, rack) in the BMS and rack design.
  • Write into the requirements that coolant supply must work with coarse flow and temperature control and that the cooling loop integrates with the IT monitoring and control system.

Who should read it

Mechanical engineers designing liquid-cooled AI racks, cold-plate and CDU manufacturers, hyperscale operators and commissioning teams.

Document contents

  1. Introduction
  2. AI Power Trend and Cooling Limits (a glimpse of the trend, analysis for practical demands, importance of community alignment)
  3. Platform Practices (Tide 1.0, Tide 1.5, Tide 2.0)
  4. Impact of Packaging
  5. Other Challenges (performance degradation, flow variation, part to part variation, communication and control)
  6. Call to Action
  7. Terminology and references

Related standards

  • OCP 30 C Coolant Roadmap
  • OCP Reservoir and Pumping Unit Specification

Read the document

ocp-meta-liquid-cooling-ai-training-practices-2023.pdf

PDF · 1.2 MB · English

CC BY-SA 4.0: share with attribution under the same licence

The document is provided unaltered because its licence permits redistribution.

Publication details

Authors
Cheng Chen; Yin Hang; Noman Mithani; Chris Malone; Yueming Li; Wenying Zhang; John Fernandes; Kalpak Dhake; Jaret Wyatt; Jarrod Clow; Darron Young
Publisher
Open Compute Project Foundation (Meta contribution)
Year
2023
Document language
English
Source type
Industry body
Access
Open licence (downloadable)
Licence
CC BY-SA 4.0: share with attribution under the same licence
Licence evidence
www.opencompute.org
Original licence note

Creative Commons Attribution-ShareAlike 4.0 International; licence verified from the licence statement in the document itself. Attribution to the authors and publisher is kept; adaptations must keep the same licence.

Citation

Cheng Chen; Yin Hang; Noman Mithani; Chris Malone; Yueming Li; Wenying Zhang; John Fernandes; Kalpak Dhake; Jaret Wyatt; Jarrod Clow; Darron Young (2023). Practices and Insights into Liquid Cooling on Meta's AI Training Platforms (OCP contribution, August 2023). Open Compute Project Foundation (Meta contribution). https://www.opencompute.org/documents/practices-and-insights-into-liquid-cooling-on-metas-ai-training-platforms-ocp-format-august-14-2023-pdf/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.