Technical guideFree to read2024

Energy Optimized and Scalable Breakout Architecture for your Data Centers

Panduit / Cisco / Keysight · Cisco, Panduit et al.

A 2024 white paper by Panduit, Cisco and Keysight reporting measured energy savings (7.2 kW, 54.5%) from replacing per-cabinet 100G ToR switches with a 400G middle-of-row (MoR) breakout architecture in a 16-cabinet row.

On this page

Overview

The paper explains that switch-port throughput is surpassing server NIC speeds, which makes breakout architectures (one high-speed port split into several lower-speed ports) attractive. ASIC capability doubles every two years while electrical lane standards double every four, and switch ASICs can run far more ports than the servers and devices that fit in one cabinet. This supports end-of-row (EoR) or middle-of-row (MoR) breakout layouts over conventional top-of-rack (ToR). Concerns are operational complexity and a single failure affecting several devices.

The theoretical scenario covers a 16-cabinet row with 32 servers per cabinet on 100G NICs and one Cisco Nexus 9364C-GX ToR switch per cabinet (48 of 64 ports used: 32 down, 16 up, 2:1 oversubscription). The switch and 48 100G transceivers draw 1017.4 W per switch, 16.28 kW per row with 16 switches. The alternative places four Nexus 9364D-GX2A 400G switches in the middle of the row (same 48 ports and 2:1 ratio), drawing 1900 W per switch and 7.6 kW per row. Theoretical savings are 8.68 kW or 53.3%. The scenario has no redundancy; for a redundant setup the savings double.

Actual testing used the Cisco switches, a Keysight AresONE-S 400GE traffic generator, Panduit PDUs and a third-party power meter. Tests cover transceivers unterminated and terminated, and traffic at 0, 20, 40, 70 and 100% on 64 and 48 ports with RFC 2544 throughput and latency tests (1024-byte fixed frames). At 70% traffic, measured power is 826.5 W for the 100G switch and 1511.8 W for the 400G switch, giving 13.2 kW and 6.0 kW per row, a saving of 7.2 kW or 54.5% (against 53.3% theoretical).

An additional consideration notes that a typical 100G ToR design would likely use DACs rather than optics, DAC power is usually below 0.5 W, and moving to MoR with optical breakouts still saves about 40% of network power. Physical-infrastructure best practices are: breakout cassettes instead of harnesses, RapidID for patch-cord identification, a standardised cabinet layout (32 servers in sets of 4 on the same transceiver) and the Panduit-Cisco breakout guide. Integrating Panduit iPDUs with Cisco Nexus Dashboard gives real-time energy, cost and greenhouse-gas tracking. The paper is a vendor publication with measurements for this specific product combination.

Key points

  1. Theoretical scenario: 16 cabinets, 32 servers each, 100G NICs; each ToR switch uses 48 of 64 ports (32 down, 16 up, 2:1 oversubscription); no redundancy.
  2. 100G ToR: switch plus 48 transceivers draw 1017.4 W each (811 W switch, 206.4 W transceivers), 16.28 kW per row with 16 switches.
  3. 400G MoR: four switches at 1900 W each (1324 W switch, 576 W transceivers), 7.6 kW per row; theoretical saving 8.68 kW or 53.3%.
  4. Measured power at 70% traffic: 826.5 W for the 100G switch, 1511.8 W for the 400G switch; 13.2 kW and 6.0 kW per row.
  5. Measured saving is 7.2 kW or 54.5%, consistent with the 53.3% theoretical value.
  6. If the 100G ToR design uses DACs (power usually below 0.5 W), optical-breakout MoR still saves about 40% of network power.
  7. ASIC capability doubles every two years and electrical lane standards every four years.
  8. Best practices: cassettes over harnesses, RapidID patch-cord identification, standard cabinet layout (32 servers in sets of 4), breakout ordering guide.

Using it in design

  • When choosing row-level switch architecture, calculate energy for MoR or EoR 400G breakout against ToR, including used port count and transceiver power.
  • In a breakout design, account in redundancy planning (dual attachment) for the fact that one 400G port failure affects four servers.
  • Separate DAC from optical connections in energy comparisons and compare like with like; the savings figures are specific to the vendors' products.
  • Use cassettes instead of harnesses, set patch-panel and polarity standards, and standardise cabinet layout so groups of servers (for example four) share one transceiver.
  • Add energy and emissions reporting to the design, measuring switch power with intelligent PDUs and tracking it in DCIM or Nexus Dashboard.

Who should read it

Data-centre network and structured-cabling designers and operations engineers pursuing energy efficiency.

Document contents

  1. Introduction: breakout architectures
  2. How Cisco, Panduit and Keysight came together for this testing
  3. Theoretical scenario and power savings
  4. Testing results
  5. Additional considerations: Nexus Dashboard and Panduit iPDU integration
  6. Breakout architecture physical infrastructure best practices
  7. Conclusion

Publication details

Authors
Cisco; Panduit; Keysight Technologies
Publisher
Panduit / Cisco / Keysight
Year
2024
Document number
C11-4434966-00; 08/24
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Public manufacturer document or page inspected. No document-specific redistribution permission established; retain metadata and original short summaries only.

Citation

Cisco; Panduit; Keysight Technologies (2024). Energy Optimized and Scalable Breakout Architecture for your Data Centers. Panduit / Cisco / Keysight. C11-4434966-00; 08/24. https://panduit.com/content/dam/panduit/en/website/documents/energy-savings-scale-dc-breakout-arch-wp.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cost studies in SoSo CAD

Calculate equipment cost, energy cost and total cost of ownership (TCO) from the design’s quantities and your own price assumptions.

CAPEX and TCO estimates in the SoSo CAD cost workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.