UNIBLOCK UBTD+ Diesel Rotary UPS (Technical Brochure)
Original title UNIBLOCK UBTD+ Diesel Rotary UPS (technical brochure / whitepaper)
Piller Group GmbH
A 2019 Piller brochure: the UNIBLOCK UBTD+ combines motor-generator, coupling choke and diesel engine in one unit, offers 500-2700 kW single machines and parallel systems up to 40 MW, contains no power capacitors and lasts over 20 years.
On this page
Overview
The brochure describes Piller's diesel rotary UPS: the UNIBLOCK motor-generator (MG) is connected through a free-wheel clutch to a diesel engine on one short base frame. The load is normally fed through an isolating and coupling choke connected to the utility; a second tapped connection of the choke goes to the MG. On a short interruption or loss of mains the load is first carried by a ride-through source (a battery system or the POWERBRIDGE electrically coupled kinetic energy store); the diesel then starts, and once at speed the clutch engages to hand the load to the engine.
The reliability argument rests on no power capacitors, no brushes or slip rings, no bypass needed for the UPS function, and, in most cases, electric cooling fans replaced by the machine's own impeller. On power quality, the MG and choke counter low voltages and brownouts down to -30% without using the ride-through store, carry 100% non-linear load and 100% step load, present near-unity power factor to the utility and isolate about 99% of harmonics between load and source.
The energy-storage options are compared: POWERBRIDGE is a vertical flywheel-generator on magnetic bearings that avoids batteries and air-conditioned battery rooms and is claimed to give typically 3 times longer bridging time than other UPS; the battery option is electrically more efficient than the kinetic equivalent but trades off space and other factors. Other sections cover air or chilled-water cooling, containerised delivery and unit configurations (single system, parallel).
This is a manufacturer brochure describing its own product; comparisons are against other UPS technologies in general and rest on no independent measurement. It is useful for a designer who wants the rotary UPS concept, the mains-failure duration statistics and the cooling and container options in one place.
Key points
- A single machine is 500-2700 kW; paralleling reaches 40 MW; low and medium voltage options exist.
- The design has no power capacitors, unit life easily exceeds 20 years, and bypass is not needed for the UPS function.
- Most mains disturbances last over 10 ms; on overhead networks over 60% of failures last more than 100 ms and only about 2% last more than a few seconds.
- With POWERBRIDGE, false generator starts fall practically to none, against about 5 starts a week with other diesel UPS solutions.
- It counters voltage sags down to -30% without using the ride-through store, and carries 100% non-linear load and a 100% load step.
- Input power factor seen by the utility is near unity; about 99% harmonic isolation between load and source.
- With POWERBRIDGE there is no battery room or disposal issue; the store can absorb and release power at the same rate indefinitely.
- Cooling can be by air or chilled water (closed air circuit connected to the building's chilled-water loop); a containerised installation is available.
- The design also offers multi-system parallel expansion and delayed or instant diesel starting options.
Using it in design
- When comparing diesel rotary UPS with static UPS, put capacitor and fan replacement maintenance, life expectancy (over 20 years) and floor footprint into total cost of ownership.
- In choosing the ride-through source, weigh the kinetic-store versus battery trade-off (space, battery room air conditioning, disposal, autonomy time) explicitly.
- Derive the mains-outage duration distribution from local data; set the number of unnecessary generator starts as a design target.
- Assess the cooling option (air, building water, container) with the electrical room and cooling plan; the closed water-cooled option makes a room airflow study unnecessary.
- Ask the supplier for measured data on 100% non-linear load, load step and leading and lagging power factor performance.
Who should read it
Electrical designers choosing between diesel rotary and static UPS in large critical facilities, colocation operators and operations engineers.
Document contents
- About Piller
- Principle of operation
- The UNIBLOCK motor-generator
- System reliability and power quality improvement
- Power factor correction and fault handling
- Energy storage solutions (POWERBRIDGE, battery)
- Other design solutions (water-cooled, containerised)
- Optimised protection and enhanced diesel engine starting
- Unit configurations
Related standards
- ISO 8528-11
- IEC 62040-3
Publication details
- Authors
- Piller Group GmbH
- Publisher
- Piller Group GmbH
- Year
- 2019
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Manufacturer brochure distributed as 'whitepaper' via Datacenter Forum; no open licence. Year from PDF metadata (Mar 2019).
Citation
Piller Group GmbH (2019). UNIBLOCK UBTD+ Diesel Rotary UPS (technical brochure / whitepaper). Piller Group GmbH. https://www.datacenter-forum.com/piller-germany-gmbh-co-kg/uniblock-ubtd-diesel-rotary-ups/download
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
