Enel D1 Series UPS technical specifications
Original title D1 Serisi UPS Teknik Özellikleri
Enel
One-page technical table for Enel's D1 three-phase double-conversion UPS: nine ratings from 160 to 800 kVA, 0.8 output power factor, 92% on-line and 98% eco-mode efficiency.
On this page
Overview
The document is a graphic data sheet that gathers input, bypass, output, efficiency, general features, environment, cabinet and battery data for Enel's D1 UPS family in one table. The nine models are rated 160, 200, 250, 300, 400, 500, 600, 700 and 800 kVA, equal to 128 to 640 kW at a fixed 0.8 output power factor.
On the input side it lists 380/400/415 V three-phase plus neutral, a +/-15% voltage window at full load, 50/60 Hz with +/-10% frequency tolerance, input power factor of 0.99 or higher and input current distortion (THDi) below 4%. The bypass operates within +/-10% voltage and +/-4% frequency; a manual maintenance bypass is standard and an external bypass is optional.
At the output the table gives +/-1% voltage for static load and +/-5% for dynamic load, THDv below 2% on linear and below 5% on non-linear load, and a 3:1 crest factor. Overload capability is 60 minutes at 110%, 10 minutes at 125% and 1 minute at 150%. The technology is true online double conversion with an IGBT rectifier, classified VFI-SS-111 under 62040-3.
Cabinet size and weight vary widely with rating: 490 kg to 2300 kg, and width from 635 mm to 3430 mm. The battery is 60 or 64 VRLA AGM or gel blocks with a 10-year design life. The sheet is a product summary; autonomy, load-dependent efficiency curves and installation details must be obtained separately from the manufacturer.
Key points
- Nine ratings: 160, 200, 250, 300, 400, 500, 600, 700, 800 kVA (128 to 640 kW).
- Output power factor 0.8 (0.9 optional); input power factor 0.99 or higher, THDi below 4%.
- Efficiency: 92% in on-line mode, 98% in eco mode.
- Overload: 60 min at 110%, 10 min at 125%, 1 min at 150%.
- Classification VFI-SS-111 (62040-3); up to 8 units in parallel.
- Operating temperature 0-40 C (20-25 C for longest battery life); to 2000 m without derating, then 0.6% per 100 m.
- Noise below 65, 70 and 75 dB(A) depending on rating; protection class IP20.
- Cabinet weight 490 kg to 2300 kg; 60 or 64 VRLA battery blocks.
Using it in design
- Size the critical load in kW rather than kVA: for D1 the kW rating is 80% of kVA, with a 0.9 power factor as an option.
- If the design relies on eco mode (98%), compare the protection level in that mode with the load's sensitivity.
- Carry cabinet weight and footprint into UPS-room floor loading and layout; cabinets above 600 kVA are wider than 2 m.
- Check the overload curve against transformer energisation and inrush scenarios.
- Calculate derating for site altitude above 2000 m and ambient above 40 C.
Who should read it
Electrical designers selecting UPSs and engineers writing specifications in the large-power class.
Document contents
- Power
- Input
- Bypass
- Output
- Overload capacity
- Efficiency
- General
- Operating environment
- UPS cabinet
- Battery
- Standards
- Service life
Publication details
- Authors
- Enel
- Publisher
- Enel
- Year
- Year not stated
- Document language
- Turkish
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Enel D1 Serisi UPS Teknik Özellikleri. Enel. https://enel.com.tr/wp-content/uploads/2019/10/ENEL-D1-SER%C4%B0S%C4%B0-2.jpg
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
