Technical guideFree to read2022

E6 Series Online UPS 10-15-20 kVA: technical sheet

Original title E6 Serisi Online UPS 10–15–20 kVA: teknik görsel

Enel

A 2022 single-page technical sheet from Enel for its three-phase E6 series double-conversion online UPS in 10, 15 and 20 kVA, giving power, input, bypass, output, efficiency, battery and environmental data.

On this page

Overview

The sheet presents the E6 series with 3-level (3L) rectifier and inverter technology. Highlighted features are high short-circuit withstand, regenerative loading, input THDi below 5 percent, output THDv below 2 percent and an input power factor of 0.99 across 25-100 percent load. Control is dual DSP with SPWM, and the IEC 62040-3 class is given as VFI-SS-111.

The power row gives 8, 12 and 16 kW for 10, 15 and 20 kVA; output power factor is 0.8 (0.9 optional). Input is 380/400/415 V 3 phase + N, range +20 and -15 percent (at full load) down to -36 percent (load dependent), 50/60 Hz and ±10 percent. Bypass voltage range is up to ±20 percent and frequency range ±4 percent (adjustable up to ±10 percent), with a manual maintenance bypass as standard.

Output voltage tolerance is ±1 percent on static load and ±5 percent on dynamic load; frequency is ±0.1 percent free-running and ±1 percent when synchronised to the mains. Overload capability is 60 minutes up to 110 percent, 10 minutes up to 125 percent and 1 minute up to 150 percent. Efficiency is 94 percent at 50 percent load and at most 94 percent at full load in online mode, and up to 98 percent in eco mode; these are not a part-load curve.

The internal battery is 30 VRLA AGM, gel or Ni-Cd blocks of 7-9 Ah, and an external battery cabinet connection is standard. Cold start from battery is standard, and parallel operation of up to 6 units is optional. Operating temperature is 0-40 C (20-25 C for longest battery life), altitude up to 2000 m, noise below 55 dB(A). Service life is stated as 10 years.

Key points

  1. The 10, 15 and 20 kVA models give 8, 12 and 16 kW; output power factor is 0.8 (0.9 optional).
  2. Input: 380/400/415 V 3 phase + N, +20 / -15 percent (full load), -36 percent (load dependent); power factor at least 0.99, THDi below 5 percent.
  3. Output: THDv below 2 percent (linear load) and 5 percent or less (non-linear load), crest factor 3:1.
  4. Efficiency: 94 percent at 50 percent load and at most 94 percent at full load online; up to 98 percent in eco mode.
  5. Overload: 60 min up to 110 percent, 10 min up to 125 percent, 1 min up to 150 percent.
  6. IEC 62040-3 class VFI-SS-111; parallel operation up to 6 units (optional).
  7. Internal battery 30 blocks, 7-9 Ah, VRLA AGM, gel or Ni-Cd; cold start from battery is standard.
  8. Cabinet 255 x 770 x 870 mm (W x D x H), 49 kg and 51 kg (two weight values are given), IP20, noise below 55 dB(A).
  9. Operation 0-40 C, humidity 0-95 percent non-condensing, up to 2000 m; service life 10 years.

Using it in design

  • Calculate real output power in kW (8, 12, 16 kW), not kVA; power factor is 0.8 by default and 0.9 optional.
  • Do not use the efficiency figures as a part-load curve: the sheet gives only the 50 percent and full-load points and the eco mode ceiling.
  • Use input THDi and power factor in generator sizing.
  • Assess the overload curve together with bypass transfer and protection selectivity.
  • Choose battery type and the external cabinet option by required runtime; 20-25 C is preferred for battery life.

Who should read it

Designers selecting 10-20 kVA UPS units for small and medium data rooms and technical rooms.

Document contents

  1. Features
  2. Power
  3. Input
  4. Bypass
  5. Output
  6. Overload capacity
  7. Efficiency
  8. General
  9. Operating environment
  10. UPS cabinet
  11. Battery
  12. Standards
  13. Service life

Publication details

Authors
Enel
Publisher
Enel
Year
2022
Document language
Turkish
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Enel (2022). E6 Serisi Online UPS 10–15–20 kVA: teknik görsel. Enel. https://enel.com.tr/wp-content/uploads/2022/10/E-Serisi-3.jpg

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.