Technical guideFree to readYear not stated

INVT HT33 Series Tower Online UPS 60-600 kVA

Original title HT33 Series Tower Online UPS 60–600 kVA

INVT

The INVT HT33 series is a 60-600 kVA, 380/400/415 V three-phase tower online UPS with system efficiency up to 96%, 99% in ECO mode, input PF above 0.99 and scaling to 1500 kVA in parallel.

On this page

Overview

The page is the product introduction and specification table for the INVT HT33 three-phase-in, three-phase-out tower online UPS series. The series offers three high-speed DSPs with fully digital control, high input power factor and low input current distortion; full front access for service is a highlighted design feature. Target uses are IDCs, ISPs, IT rooms, service centres and precision instruments. Protections include over-temperature (8 sensors), overload, battery under-voltage, fan failure and short circuit, and battery cold start is supported.

The specification table covers 12 models (HT33060X to HT33600X; 60, 80, 90, 100, 120, 150, 200, 250, 300, 400, 500 and 600 kVA). Input is 3PH+N+PE, 380/400/415 V, 304-478 Vac at full load (load decreasing linearly between 228 and 304 Vac), 40-70 Hz, input PF above 0.99 and THDi below 3%. Output power factor is 1, voltage regulation is 1% on balanced and 1.5% on unbalanced load, THDu is below 1% on linear and below 5% on non-linear load, and inverter overload is 110% for 1 hour, 125% for 10 min and 150% for 1 min. Battery is ±240 Vdc, 40 units as standard (even number 32-44 settable), charge power up to 20% of output active power.

Efficiency is 95-96% in AC mode (by model), 99% in ECO mode and 95-96% on battery. The display is a 7-inch (60-200 kVA) or 10.4-inch (240-500 kVA) touch screen; interfaces are RS232, RS485, programmable dry contacts and USB, with options of SNMP card, parallel kit, SPD, LBS and dust filter. Operation is 0-40 °C, IP20, altitude below 1000 m without derating (1% per 100 m between 1000 and 2000 m) and noise of 65 dB at 100% load. Weight runs from 170 kg to 900 kg and dimensions from 600 x 980 x 950 mm to 1300 x 1100 x 2000 mm.

Key points

  1. 12 models: 60, 80, 90, 100, 120, 150, 200, 250, 300, 400, 500 and 600 kVA; output PF 1.
  2. Efficiency: 95-96% in AC mode, 99% in ECO mode, 95-96% on battery.
  3. Input 380/400/415 V, 304-478 Vac at full load; input PF above 0.99; input THDi below 3%.
  4. Output THDu below 1% on linear and below 5% on non-linear load; crest factor 3:1.
  5. Inverter overload: 110% for 1 hour, 125% for 10 min, 150% for 1 min, above 150% for 200 ms.
  6. Bypass overload: 125% continuous, 130% for 10 min, 150% for 1 min, above 150% for 300 ms (one column); 110% continuous, 125% for 5 min (other column).
  7. Battery ±240 Vdc, 40 units (even number 32-44); charge power up to 20% of output power.
  8. Parallel up to 1500 kVA; weight 170-900 kg; 0-40 °C, IP20; 1% per 100 m between 1000 and 2000 m.

Using it in design

  • Select capacity directly in kW (output PF 1) and plan N+1 with parallel units (up to 1500 kVA) for redundancy.
  • Separate AC-mode and ECO-mode efficiencies (95-96% and 99%) in heat-loss and PUE calculations by operating profile.
  • If the battery count differs from 40 (32-44), check the effect on DC bus voltage and charge power (20% of output power).
  • Take weight and dimensions per model from the manufacturer; apply 1% per 100 m derating above 1000 m.

Who should read it

Electrical designers selecting UPS systems for mid-size and large data centres and IT facilities.

Document contents

  1. Product introduction
  2. Features
  3. Specifications table
  4. Downloads

Publication details

Authors
INVT
Publisher
INVT
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

INVT HT33 Series Tower Online UPS 60–600 kVA. INVT. https://www.invt.com/products/ht33-series-tower-online-ups-60-600kva

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.