INVT RM600/60D 60-600 kVA Modular Online UPS

Original title INVT RM600/60D 60-600 kVA modular online UPS

INVT

INVT's RM600/60D page defines a 600 kVA modular online UPS built from ten hot-swappable 60 kVA, 2U modules, with overall efficiency up to 97%.

On this page

Overview

The document is the product page for the RM600/60D system of INVT's RM series 60-600 kVA modular online UPS family. The system is rated 600 kVA and holds 10 power modules, each 60 kVA/kW and 2U high. A knob on the front panel allows a module to be hot-swapped without interrupting the load, which supports redundancy and online maintenance.

The input is dual and defined as 380/400/415 VAC (line-line), three-phase plus neutral plus earth. The input voltage range at full load is 323-478 Vac; at the lower limit, load decreases linearly from 100% to 40% according to the minimum phase voltage. Input frequency is 40-70 Hz, input power factor is above 0.99 and THDi is below 3%. The bypass range is settable, with a default of -20%/+15%.

Output power factor is 1, voltage regulation is ±1%, and THDu is below 1% on linear load and below 5% on non-linear load. Inverter overload is 1 hour at 110%, 10 minutes at 110-125% and 1 minute at 125-150%. Efficiency is above 97% in AC mode and above 96% in battery mode. A bidirectional DC-DC converter provides charging power up to 30% of output active power, and lithium batteries are supported.

Environmentally, operating temperature is 0-40 °C and altitude below 1,000 m; between 1,000 and 2,000 m a 1% power derating per 100 m applies. Noise is 75 dB at 100% load and 70 dB at 45% load. The cabinet is 800×1100×2000 mm and 443 kg; a power module is 550×750×85 mm and 35.7 kg. Standards are IEC/EN 62040-1, -2, -3.

Key points

  1. System rating 600 kVA; 10 modules, each 60 kVA/kW and 2U; hot-swappable.
  2. Dual input as standard; 380/400/415 VAC, 3-phase + neutral + earth; input range 323-478 Vac at full load.
  3. Input power factor above 0.99, THDi below 3%; input frequency 40-70 Hz.
  4. Output power factor 1; regulation ±1%; THDu below 1% (linear) and below 5% (non-linear).
  5. Efficiency above 97% in AC mode and above 96% in battery mode.
  6. Charging power up to 30% of output active power; lithium batteries supported; battery voltage ±180-288 VDC.
  7. Inverter overload: 1 hour at 110%, 10 min at 110-125%, 1 min at 125-150%.
  8. Altitude below 1,000 m; 1% power derating per 100 m between 1,000 and 2,000 m.
  9. Cabinet 800×1100×2000 mm, 443 kg; power module 550×750×85 mm, 35.7 kg.

Using it in design

  • Decide how many modules to fit in the 10-slot, 600 kVA cabinet against an N+1 or N+X redundancy target.
  • Carry the cabinet weight (443 kg) and 35.7 kg per module into floor loading and the module-replacement procedure.
  • On sites above 1,000 m, include the 1% per 100 m power derating in the capacity calculation.
  • Select the battery block count against the voltage limits; 30-32 blocks derate to 70%, 34-36 to 80% and 38 to 90%.
  • Assess the high charging power (30%) together with battery capacity and charge-current limits.

Who should read it

Electrical engineers specifying modular UPS up to 600 kVA for large data centres.

Document contents

  1. Features
  2. Specifications (system, input, bypass, output, battery, system, environment, physical)
  3. Certification
  4. Download

Publication details

Authors
INVT
Publisher
INVT
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

INVT INVT RM600/60D 60-600 kVA modular online UPS. INVT. https://www.invt-power.com/product/RM-Series-60-600kVA-Modular-Online-UPS-(380V400V415V)-104.html

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.