INVT RM600/60D 60-600 kVA Modular Online UPS
Original title INVT RM600/60D 60-600 kVA modular online UPS
INVT
INVT's RM600/60D page defines a 600 kVA modular online UPS built from ten hot-swappable 60 kVA, 2U modules, with overall efficiency up to 97%.
On this page
Overview
The document is the product page for the RM600/60D system of INVT's RM series 60-600 kVA modular online UPS family. The system is rated 600 kVA and holds 10 power modules, each 60 kVA/kW and 2U high. A knob on the front panel allows a module to be hot-swapped without interrupting the load, which supports redundancy and online maintenance.
The input is dual and defined as 380/400/415 VAC (line-line), three-phase plus neutral plus earth. The input voltage range at full load is 323-478 Vac; at the lower limit, load decreases linearly from 100% to 40% according to the minimum phase voltage. Input frequency is 40-70 Hz, input power factor is above 0.99 and THDi is below 3%. The bypass range is settable, with a default of -20%/+15%.
Output power factor is 1, voltage regulation is ±1%, and THDu is below 1% on linear load and below 5% on non-linear load. Inverter overload is 1 hour at 110%, 10 minutes at 110-125% and 1 minute at 125-150%. Efficiency is above 97% in AC mode and above 96% in battery mode. A bidirectional DC-DC converter provides charging power up to 30% of output active power, and lithium batteries are supported.
Environmentally, operating temperature is 0-40 °C and altitude below 1,000 m; between 1,000 and 2,000 m a 1% power derating per 100 m applies. Noise is 75 dB at 100% load and 70 dB at 45% load. The cabinet is 800×1100×2000 mm and 443 kg; a power module is 550×750×85 mm and 35.7 kg. Standards are IEC/EN 62040-1, -2, -3.
Key points
- System rating 600 kVA; 10 modules, each 60 kVA/kW and 2U; hot-swappable.
- Dual input as standard; 380/400/415 VAC, 3-phase + neutral + earth; input range 323-478 Vac at full load.
- Input power factor above 0.99, THDi below 3%; input frequency 40-70 Hz.
- Output power factor 1; regulation ±1%; THDu below 1% (linear) and below 5% (non-linear).
- Efficiency above 97% in AC mode and above 96% in battery mode.
- Charging power up to 30% of output active power; lithium batteries supported; battery voltage ±180-288 VDC.
- Inverter overload: 1 hour at 110%, 10 min at 110-125%, 1 min at 125-150%.
- Altitude below 1,000 m; 1% power derating per 100 m between 1,000 and 2,000 m.
- Cabinet 800×1100×2000 mm, 443 kg; power module 550×750×85 mm, 35.7 kg.
Using it in design
- Decide how many modules to fit in the 10-slot, 600 kVA cabinet against an N+1 or N+X redundancy target.
- Carry the cabinet weight (443 kg) and 35.7 kg per module into floor loading and the module-replacement procedure.
- On sites above 1,000 m, include the 1% per 100 m power derating in the capacity calculation.
- Select the battery block count against the voltage limits; 30-32 blocks derate to 70%, 34-36 to 80% and 38 to 90%.
- Assess the high charging power (30%) together with battery capacity and charge-current limits.
Who should read it
Electrical engineers specifying modular UPS up to 600 kVA for large data centres.
Document contents
- Features
- Specifications (system, input, bypass, output, battery, system, environment, physical)
- Certification
- Download
Publication details
- Authors
- INVT
- Publisher
- INVT
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
INVT INVT RM600/60D 60-600 kVA modular online UPS. INVT. https://www.invt-power.com/product/RM-Series-60-600kVA-Modular-Online-UPS-(380V400V415V)-104.html
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.