Technical guideFree to readYear not stated

KSTAR HPM3300E Modular Series 10-150 kVA Manufacturer Datasheet

Original title KSTAR HPM3300E Modular Series 10–150 kVA manufacturer datasheet, p. 2 (Intellcom hosted)

KSTAR

KSTAR's HPM3300E datasheet gives 10-150 kVA three-level modular UPS cabinets built from 10-30 kVA power modules, with 95.8% efficiency, THDi below 3% and a 138-485 V input window.

On this page

Overview

The document is the two-page datasheet of the HPM3300E modular series from the Chinese manufacturer KSTAR. The series is a transformerless, 3-level, three-phase in and three-phase out online UPS in the 10-150 kVA range. Power modules are 10, 15, 20, 25 and 30 kVA; the power, bypass, monitoring and ECU control modules are hot-swappable. A cabinet takes one or several modules, and some configurations are 2+1 redundant.

The cabinet-to-module mapping is read from the table: for example, with 10 kVA modules, 30 kVA (3 modules) and 50 kVA (5 modules); with 20 kVA modules, 60 kVA (3 modules) and 100 kVA (5 modules); with 30 kVA modules, 60 kVA (2+1 redundant) and 150 kVA (5 modules). Parallel operation supports up to 8 units, and batteries can be shared among parallel units. The datasheet states explicitly that the series is not compatible with energy-feedback loads (medical CT machines, semiconductor cutting machines, elevators).

Input is 380/400/415 Vac; the input range is 305-485 Vac at 100% load and 138-305 Vac at 40% load. Input power factor is 0.99 or above, and THDi is 3% or below at 100% linear load. Efficiency reaches 95.8% in AC mode and up to 99% in ECO and HECO mode; efficiency is a typical value under standard test conditions. Output power factor is 1, regulation ±1%, and THDv does not exceed 1% on linear load or 3% on non-linear load.

The battery is VRLA, with block count selectable from 30 to 50 (default 36). Output power factor is 1 on 36-50 blocks, 0.9 on 32-34 blocks and 0.8 on 30 blocks; maximum charging current is 18 A. The cabinet is 600×850×1200 mm, the power module 440×620×86 mm (2U) and 19-21 kg; cabinet weight is 130-170 kg. Operation is 0-40 °C and altitude up to 1,000 m; standards are IEC/EN 62040-1, 62477-1, 62040-2 and IEC 62040-3:2021. The document states that the values are not a basis for engineering design.

Key points

  1. Power range 10-150 kVA; modules 10, 15, 20, 25, 30 kVA; 3-level, transformerless, hot-swappable.
  2. Cabinet configurations: 30k/50k (10 kVA modules), 45k/75k (15), 60k/100k and 50k/125k (20, 25), 60k/150k (30 kVA).
  3. Up to 8 units in parallel; 2+1 module redundancy on some cabinets.
  4. Input: 380/400/415 Vac; 100% load at 305-485 Vac, 40% load at 138-305 Vac.
  5. Input power factor ≥0.99; THDi ≤3% (100% linear load).
  6. Efficiency: AC mode up to 95.8%; ECO and HECO mode up to 99%.
  7. Output PF 1; regulation ±1%; THDv ≤1% (linear), ≤3% (non-linear).
  8. Inverter overload: ≤110% 60 min, ≤125% 10 min, ≤150% 1 min, >150% 1.2 s.
  9. Battery 30-50 blocks (36 default); PF 0.9 at 32-34 blocks, 0.8 at 30 blocks; maximum charge 18 A.

Using it in design

  • Set the cabinet-to-module mapping (for example 10 kVA × 5 modules = 50 kVA) together with the capacity growth plan and a 2+1 redundancy target.
  • Choose 36 or more battery blocks to keep output power factor at 1; fewer blocks reduce output power.
  • This series cannot serve energy-feedback loads (CT machines, elevators, motor drives); check the load list.
  • On sites above 1,000 m, carry the derating into the capacity calculation.
  • Because the datasheet says its values are not a design basis, confirm project data with the manufacturer.

Who should read it

Data-centre and industrial electrical designers selecting modular UPS in the 10-150 kVA range.

Document contents

  1. Features: modular design, parallel redundancy, flexible battery configuration, high reliability, strong load capability, intelligent management, green and power saving, LBS
  2. Technical specifications: capacity, input, output, efficiency, battery
  3. Management, system features, environmental
  4. Physical data and standards

Publication details

Authors
KSTAR
Publisher
KSTAR
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

KSTAR KSTAR HPM3300E Modular Series 10–150 kVA manufacturer datasheet, p. 2 (Intellcom hosted). KSTAR. https://www.intellcom.ge/files/pdf/1764661189190/HPM3320E_RM_Datasheet.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.