KSTAR HPM3300E Series UPS Solution (30 to 1200 kVA) Catalogue

Original title KSTAR HPM series 2026 catalogue, 100 kW modular specification p.16

KSTAR

The KSTAR catalogue for the HPM3300E family of three-phase transformerless online UPS from 10 kVA to 1200 kVA, covering modular, subrack-modular and T series, with features and technical tables for each power range.

On this page

Overview

The catalogue first introduces the manufacturer: founded in 1993 and listed on the Shenzhen Stock Exchange in 2010, with more than 4300 employees, a presence in more than 180 countries and regions and an annual production capacity of 3 million kVAh. Market achievements are cited to Omdia and ICT Research. The HPM3300E family is then divided into seven sub-series: 30 to 75 kVA modular, 10 to 30 and 40 to 60 kVA subrack modular, 10 to 30 and 40 to 60 kVA modular, 100 kVA modular and the 200 to 1200 kVA HPM3300E-T.

All series are transformerless three-level online double-conversion, with output power factor 1.0 and output voltage 380/400/415 V (3Ph+N+PE). Input power factor is stated as 0.99 or higher and THDi below 3% (full linear load). Online efficiency reaches up to 95.8% in the small series, 96% in the mid series and 97% at 400 to 1200 kVA; ECO and HECO modes are given up to 99%. Features include hot-swappable power, bypass and monitoring modules, parallel expansion (up to 6 units for 30 to 75 kVA), a built-in battery option, LBS (synchronous operation of two independent UPS), Power Walk In (reduces generator start-up current) and a 7-inch touch screen.

The technical table for the 400 to 1200 kVA series gives 100 kVA modules (4 to 12 modules), parallel of 6 units (up to 1000 kVA) and 4 units (1200 kVA), input range of 138 to 324 V (at 40% load) and 323 to 485 V (at 100% load), output THDv of 1% (linear) and 3% (non-linear), battery voltage 360 to 600 Vdc, VRLA or Li-ion, charging current up to 100 A, cabinet weights of 305 to 920 kg and noise below 73 to 75 dB. The catalogue states that values are typical and for reference, not a basis for engineering design. It also warns that the 30 to 75 kVA series is incompatible with energy-feedback loads such as CT machines, semiconductor cutting machines and elevators.

Key points

  1. Seven sub-series: 30 to 75 kVA, 10 to 30 kVA and 40 to 60 kVA subrack, 10 to 30 kVA and 40 to 60 kVA modular, 100 kVA modular, and 200 to 1200 kVA T series.
  2. Transformerless three-level online double conversion; output power factor 1.0; input power factor 0.99 or higher; THDi below 3%.
  3. Online efficiency 95.8% (30 to 75 kVA), 96% (40 to 200 kVA), 97% (400 to 1200 kVA); up to 99% in ECO and HECO.
  4. In the 30 to 75 kVA series, modules are 10/15/20/25/30 kVA, up to 6 units in parallel, voltage range 138 to 305 V (40% load) and 305 to 485 V (100% load).
  5. In the 30 to 75 kVA series, up to 24 hot-swappable battery modules, each with ten 12 V 9 Ah; battery voltage ±240 V, charging current up to 18 A.
  6. At 400 to 1200 kVA: 100 kVA modules, 4 to 12 modules; up to 6 units in parallel (4 at 1200 kVA); battery voltage 360 to 600 Vdc; charging current up to 100 A.
  7. The 400 to 1200 kVA cabinet weighs 305 to 920 kg (52.5 kg per module); noise below 73 to 75 dB.
  8. Overload (inverter mode): 105-110% for 60 min, 110-125% for 10 min, 125-150% for 1 min.
  9. Energy-feedback loads (CT machines, semiconductor cutting machines, elevators) are not compatible with the 30 to 75 kVA series.

Using it in design

  • Select the series by power range: 30 to 75 kVA modular for small rooms, the 400 to 1200 kVA T series for large halls; set the N+1 module count for redundancy.
  • Treat the catalogue values as typical and for reference; ask the manufacturer for an approved data sheet for the project.
  • When choosing between built-in battery (30 to 75 kVA) and a separate battery cabinet, compare autonomy and the charging-current limit (18 A and 100 A).
  • If a generator is used, add the Power Walk In function and generator input support to the specification.
  • Where energy-feedback loads (elevators, CT) are present, choose a compatible series or a separate supply instead of this UPS.

Who should read it

Electrical designers and procurement teams selecting modular UPS for mid-sized and large data centres and industry.

Document contents

  1. KSTAR overview and market achievements
  2. HPM3300E modular series (30 to 75 kVA)
  3. HPM3300E subrack modular series (10 to 30 kVA and 40 to 60 kVA)
  4. HPM3300E modular series (10 to 30 kVA, 40 to 60 kVA and 100 kVA)
  5. HPM3300E-T series (200 to 1200 kVA)

Publication details

Authors
KSTAR
Publisher
KSTAR
Year
2026
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

KSTAR (2026). KSTAR HPM series 2026 catalogue, 100 kW modular specification p.16. KSTAR. https://dl.rockcontrol.ir/documents/kstar-ups-hpm3300E-series-30-1200-kVA.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.