CHINT NXZ automatic transfer switching equipment catalogue
CHINT
CHINT NXZ series PC-class automatic transfer switches: 11 current steps from 80 to 630 A, 400/415 V, 3P/4P, 100 kA conditional short-circuit rating, 125/250/630 A frames.
On this page
Overview
CHINT's NXZ catalogue presents automatic transfer switching equipment for three-phase four-wire 50 Hz duplicate supply grids at 400/415 V and below, up to 630 A. The equipment automatically moves one or several load circuits from one source to the other. Stated uses are industrial and commercial sites, high-rise buildings and residences. Product standards are IEC 60947-1 and IEC 60947-6-1; certifications are CB, CE and KEMA.
The product code combines frame current (125, 250, 630 A), pole count (3 or 4), controller type (A standard, B intelligent) and rated current, for example NXZ-125/4A 125A. Rated currents are 80, 100, 125, 160, 200, 250, 315, 320, 400, 500 and 630 A. The 125 A frame covers 80-125 A, the 250 A frame 160-250 A and the 630 A frame 315-630 A.
Technical data: rated operational voltage 400/415 V, insulation voltage AC 800 V, impulse withstand 8 kV, utilization category AC-33B, conditional short-circuit current 100 kA. Making capacity is 20, 30 and 50 kA and short-time withstand (0.2 s) 10, 10 and 25 kA. Contact transfer time is 0.6, 1 and 1.5 s; operating transfer time is 1.2, 2.1 and 3.3 s. Mechanical endurance is 8500, 7000 and 3000 operations, electrical endurance 1500, 1000 and 1000. Dimensions are 245 x 130 x 126, 295 x 175 x 175 and 430 x 272 x 230 mm.
The controller monitors phase loss, under- and over-voltage; transfer and return delays are adjustable 0-300 s; it supports grid-grid and grid-generator use, generator control and fire-control linkage. Operating conditions: -5 to +40 C (custom -25 to +70 C), altitude to 2000 m, pollution degree 3, installation category IV for the main circuit.
Key points
- Rated currents: 80, 100, 125, 160, 200, 250, 315, 320, 400, 500, 630 A; frames 125, 250, 630 A.
- Rated operational voltage 400/415 V 50 Hz; insulation AC 800 V; impulse 8 kV.
- Conditional short-circuit current 100 kA; making capacity 20/30/50 kA.
- Short-time withstand Icw (0.2 s): 10, 10 and 25 kA.
- Operating transfer time: 1.2 s (125 A), 2.1 s (250 A), 3.3 s (630 A).
- Mechanical endurance 8500, 7000, 3000; electrical 1500, 1000, 1000 operations.
- Controller: A standard and B intelligent; transfer and return delay 0-300 s.
- Conditions -5 to +40 C, to 2000 m; IEC 60947-6-1, CB, CE, KEMA.
Using it in design
- Compare the transfer time (1.2-3.3 s) with the load type and with UPS or generator ride-through tolerance.
- Coordinate the short-circuit rating (100 kA conditional, Icw) with the prospective fault current at the switch and the protective device.
- Pick controller A or B against required monitoring, generator control and fire-linkage functions.
- Use the catalogue derating tables above 2000 m altitude and above +40 C.
- Separate complete equipment from control-only or component products in records; NXZ is complete transfer equipment.
Who should read it
Electrical designers and panel builders selecting dual-supply distribution and ATS equipment.
Document contents
- General description and scope
- Applicable standards
- Normal working conditions
- Model definition
- Structural features
- Technical data (PC class)
- Controller parameters
- Controller display and settings
Publication details
- Authors
- CHINT
- Publisher
- CHINT
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
CHINT CHINT NXZ automatic transfer switching equipment catalogue. CHINT. https://www.chintglobal.com/content/dam/chint/global/product-center/low-voltage/iec/secondary-power-distribution/atse/nxz/catalog/NXZ-ATSE-Catalog.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.