Technical guideFree to readYear not stated

CHINT NXZ automatic transfer switching equipment catalogue

CHINT

CHINT NXZ series PC-class automatic transfer switches: 11 current steps from 80 to 630 A, 400/415 V, 3P/4P, 100 kA conditional short-circuit rating, 125/250/630 A frames.

On this page

Overview

CHINT's NXZ catalogue presents automatic transfer switching equipment for three-phase four-wire 50 Hz duplicate supply grids at 400/415 V and below, up to 630 A. The equipment automatically moves one or several load circuits from one source to the other. Stated uses are industrial and commercial sites, high-rise buildings and residences. Product standards are IEC 60947-1 and IEC 60947-6-1; certifications are CB, CE and KEMA.

The product code combines frame current (125, 250, 630 A), pole count (3 or 4), controller type (A standard, B intelligent) and rated current, for example NXZ-125/4A 125A. Rated currents are 80, 100, 125, 160, 200, 250, 315, 320, 400, 500 and 630 A. The 125 A frame covers 80-125 A, the 250 A frame 160-250 A and the 630 A frame 315-630 A.

Technical data: rated operational voltage 400/415 V, insulation voltage AC 800 V, impulse withstand 8 kV, utilization category AC-33B, conditional short-circuit current 100 kA. Making capacity is 20, 30 and 50 kA and short-time withstand (0.2 s) 10, 10 and 25 kA. Contact transfer time is 0.6, 1 and 1.5 s; operating transfer time is 1.2, 2.1 and 3.3 s. Mechanical endurance is 8500, 7000 and 3000 operations, electrical endurance 1500, 1000 and 1000. Dimensions are 245 x 130 x 126, 295 x 175 x 175 and 430 x 272 x 230 mm.

The controller monitors phase loss, under- and over-voltage; transfer and return delays are adjustable 0-300 s; it supports grid-grid and grid-generator use, generator control and fire-control linkage. Operating conditions: -5 to +40 C (custom -25 to +70 C), altitude to 2000 m, pollution degree 3, installation category IV for the main circuit.

Key points

  1. Rated currents: 80, 100, 125, 160, 200, 250, 315, 320, 400, 500, 630 A; frames 125, 250, 630 A.
  2. Rated operational voltage 400/415 V 50 Hz; insulation AC 800 V; impulse 8 kV.
  3. Conditional short-circuit current 100 kA; making capacity 20/30/50 kA.
  4. Short-time withstand Icw (0.2 s): 10, 10 and 25 kA.
  5. Operating transfer time: 1.2 s (125 A), 2.1 s (250 A), 3.3 s (630 A).
  6. Mechanical endurance 8500, 7000, 3000; electrical 1500, 1000, 1000 operations.
  7. Controller: A standard and B intelligent; transfer and return delay 0-300 s.
  8. Conditions -5 to +40 C, to 2000 m; IEC 60947-6-1, CB, CE, KEMA.

Using it in design

  • Compare the transfer time (1.2-3.3 s) with the load type and with UPS or generator ride-through tolerance.
  • Coordinate the short-circuit rating (100 kA conditional, Icw) with the prospective fault current at the switch and the protective device.
  • Pick controller A or B against required monitoring, generator control and fire-linkage functions.
  • Use the catalogue derating tables above 2000 m altitude and above +40 C.
  • Separate complete equipment from control-only or component products in records; NXZ is complete transfer equipment.

Who should read it

Electrical designers and panel builders selecting dual-supply distribution and ATS equipment.

Document contents

  1. General description and scope
  2. Applicable standards
  3. Normal working conditions
  4. Model definition
  5. Structural features
  6. Technical data (PC class)
  7. Controller parameters
  8. Controller display and settings

Publication details

Authors
CHINT
Publisher
CHINT
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

CHINT CHINT NXZ automatic transfer switching equipment catalogue. CHINT. https://www.chintglobal.com/content/dam/chint/global/product-center/low-voltage/iec/secondary-power-distribution/atse/nxz/catalog/NXZ-ATSE-Catalog.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.