Hager Main Switchgear Catalogue: Automatic Transfer Switches (63-1600 A)
Original title Hager Main Switchgear catalogue, automatic transfer switches
Hager
The ATS section of Hager's Main Switchgear catalogue covers 4-pole modular and enclosed automatic transfer switches from 63 to 1600 A (HIC4xxA, HIB4xxM, HIC4xxG, HIC4xxE) with technical data for the 63-160 A modular range.
On this page
Overview
The document is Hager's (Australia) Main Switchgear catalogue; the relevant section is devoted to automatic transfer switches (ATS). The selection guide compares four types: HIC4xxA (modular, 63-160 A), HIB4xxM (without automatic transfer relay), HIC4xxG (with automatic transfer relay) and HIC4xxE (with energy management). All are 4-pole; emergency manual transfer, remote-controlled transfer (RTSE) and automatic transfer (ATSE) functions are spread across the types.
The guide compares applications (network-generator, network-network and generator-generator), on-load and off-load test functions for gensets, voltage and frequency control, phase rotation and phase unbalance control, load shedding, energy measurement (with CT option) and supervision (RS485, Ethernet, web server, data log, genset start scheduling). The ordering pages list the enclosed ATS ratings 125, 160, 200, 250, 400, 630, 800, 1000, 1250 and 1600 A, plus accessories such as terminal shrouds, busbars, voltage tapping and power supply kits and an Auto/Manual key.
The technical page covers the HIC406A-HIC416A modular ATS: Ith (40 °C) 63-160 A, insulation voltage 800 V, impulse withstand 6 kV, utilisation category AC-33 B at 415 VAC, fuse-protected short-circuit withstand 50 kA (40 kA for 160 A), Icw 7 kA for 0.3 s and 4 kA for 60 ms, 10,000 operations, control supply 176-288 VAC, an "electrical blackout" duration of 150 ms and weight of 3.5 kg. Ith falls with temperature; for example, the 160 A model carries 100 A at 70 °C.
Key points
- Types: HIC4xxA (modular 63-160 A), HIB4xxM, HIC4xxG and HIC4xxE; all 4-pole.
- Enclosed ATS ratings 125, 160, 200, 250, 400, 630, 800, 1000, 1250 and 1600 A.
- Control: HIC4xxG/E use 230 VAC dual supply; configuration by potentiometers/dip switches or screen and keyboard depending on type.
- HIC4xxE adds energy management, load shedding, power/energy measurement (with CT) and configurable inputs/outputs.
- Modular range: Ui 800 V, Uimp 6 kV, Ith (40 °C) 63-160 A; 40-100 A at 70 °C.
- AC-33 B at 415 VAC: 63, 80, 100, 125 and 125 A (63-160 A models); Icw 7 kA for 0.3 s.
- Electrical blackout I-II 150 ms; control supply 176-288 VAC, 6 VA; 10,000 operations; weight 3.5 kg.
- Standard: EN 60947-3; IEC 60947-6-1 values are also given.
Using it in design
- Select the type by source arrangement (network-generator, network-network); look for HIC4xxE-class functions if genset test and start scheduling are needed.
- Derate rated current for ambient temperature (for example the 160 A model gives 125 A at 60 °C) and account for in-panel temperature.
- Upstream protection must be either a fuse (kA value in the table) or a breaker that trips in under 0.3 s; compare Icw and short-circuit withstand with the prospective fault current at the installation point.
- Assess the roughly 150 ms electrical blackout against UPS and load-shedding stages and the critical load's tolerance.
Who should read it
Electrical designers of generator-utility changeover and main switchboards, and panel builders.
Document contents
- Selection guide (63 A to 1600 A)
- Modular Automatic Transfer Switches (63 A - 160 A)
- Automatic Transfer Switches (125 A - 1600 A)
- Accessories
- Technical characteristics
Publication details
- Authors
- Hager
- Publisher
- Hager
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Hager Hager Main Switchgear catalogue, automatic transfer switches. Hager. https://assets1.sc.hager.com/australia/files/03_Main_Switchgear.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.