S³ Smart Backup modular lithium-ion UPS systems

AEC

AEC's S³ Smart Backup is a modular lithium-ion battery cabinet for its 60-1200 kW UPS range, using 40/50/100 Ah LFP cells; cabinets are 46-69 kWh, 60-200 kW, 600 x 860 x 2000 mm and parallel up to 8.

On this page

Overview

The AEC (Allis Electric) page introduces the S³ Smart Backup modular lithium-ion battery system, which combines over 30 years of power electronics experience with lithium-ion technology. It integrates with AEC's complete UPS range from 60 kW to 1200 kW. The page lists lithium's advantages over lead-acid: longer cycle life, lower self-discharge, higher working voltage and a wider temperature range.

Design features include electrical and physical double isolation (which reduces fault scope), two-level fire linkage, plug-and-play installation (maintenance time reduced to 5 minutes), intelligent current equalisation (new and old modules work together), voltage equalisation modules, adaptive SOC management and a three-layer BMS architecture (PBMU/SBMU/MBMU).

The data table gives three configurations: S3C040-6C-20-MX (40 Ah cells, 6C discharge), S3C050-4C-20-MX (50 Ah, 4C) and S3C100-1C-10-MX (100 Ah, 1C). Cabinets are 600 x 860 x 2000 mm and weigh 960, 1000 and 860 kg respectively. Output voltage is 240, ±240 or 480 V. The page is product literature.

Key points

  1. Cell: LFP, 3.2 V; 40 Ah (6C discharge, 1C charge), 50 Ah (4C, 1C), 100 Ah (1C, 0.5C); cycle life 5,000 at 50% DOD.
  2. Cell size 27.0 x 148.5 x 133.0 mm (40/50 Ah) and 50.5 x 160.3 x 120.0 mm (100 Ah); weight 1.01, 1.11 and 1.95 kg.
  3. Battery pack: 57.6 V; 2.3 kWh (40 Ah), 2.7 kWh (50 Ah), 5.7 kWh (100 Ah); DC/DC output 240 V x 2, 10 kW (40/50 Ah) and 5 kW (100 Ah).
  4. Cabinet: 46, 58 and 69 kWh maximum energy; system power 200 kW (40 and 50 Ah) and 60 kW (100 Ah); 20 or 12 modules.
  5. Cabinet size 600 x 860 x 2000 mm; weight 960, 1000 and 860 kg; up to 8 cabinets in parallel.
  6. Current imbalance ≤ 5%, SOC accuracy ≥ 95%, communication RS485, CAN, TCP/IP and dry contact.
  7. Operation 0-40 °C (+15 to +30 °C recommended); altitude 0-4000 m, derating above 2000 m.
  8. Self-discharge ≤ 3% per month (0-30 °C).

Using it in design

  • Compare the required backup time and power with cabinet kW (200 or 60 kW) and kWh (46-69) to set cabinet count and the 8-cabinet parallel limit.
  • Put cabinet weight (860-1000 kg) and the 600 x 860 mm footprint into floor loading and layout plans; reserve space for the optional distribution and fire cabinets.
  • Match the cabinet output voltage (240, ±240, 480 V) to the UPS DC bus voltage.
  • Set up maintenance for mixing new and old modules through current equalisation, and write plug-and-play module replacement into the maintenance procedure.
  • Check room ambient temperature against the recommended +15 to +30 °C range and the derating condition above 2000 m.

Who should read it

Electrical engineers designing lithium-ion backup with AEC UPS and writing battery system specifications.

Document contents

  1. The AEC advantage
  2. Benefits of lithium-ion
  3. S³ Smart Backup design features
  4. Cell data
  5. Battery pack
  6. Battery cabinet

Publication details

Authors
AEC
Publisher
AEC
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

AEC S³ Smart Backup modular lithium-ion UPS systems. AEC. https://ups.aecups.com/en/prodotti/lithium-systems/modular-lithium-ion/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.