6-GFM-100X/B VRLA battery datasheet (Coslight)

Original title 6-GFM-100X/B VRLA battery datasheet

Coslight

Coslight datasheet for the 12 V, 100 Ah (10-hour) 6-GFM-100X/B VRLA block: 393 x 108 x 287 mm, about 33 kg, with constant-current and constant-power discharge tables from 5 minutes to 8 hours.

On this page

Overview

The document is a one-page datasheet for the Coslight Group 6-GFM-100X/B valve-regulated lead-acid (VRLA) block; the original manufacturer sheet is hosted on a distributor's site. Nominal voltage is 12 V and the 10-hour rated capacity is 100 Ah at 25 °C. The block has a narrow case: length 393 mm, width 108 mm, case height 285 mm, 287 mm over terminals, and a weight of about 33 kg.

The sheet gives capacity against discharge time: 108 Ah at 20 hours, 100 Ah at 10 hours, 88 Ah at 5 hours and 62 Ah at 1 hour. Internal resistance of a fully charged block is 4.7 milliohm. Capacity depends on temperature: 109% at 40 °C, 100% at 25 °C, 88% at 0 °C and 76% at -15 °C. After three months of storage 92% of capacity remains.

Charging parameters are 14.40 V with at most 14 A for cycle use and 13.62 V with at most 14 A for float use, with a temperature compensation of -0.018 V/°C. Most of the page is the constant-current and constant-power tables: for end voltages of 1.60 to 1.85 V per cell it lists values from 5, 10, 15, 20, 30, 40 and 50 minutes and 1 to 6 hours. At 1.75 V per cell the 15-minute current is 162 A. The sheet contains no cabinet layout, life or warranty data; it provides block-level data only.

Key points

  1. Nominal 12 V, 100 Ah (10-hour rate, 25 °C); 108 Ah at 20 h, 88 Ah at 5 h, 62 Ah at 1 h.
  2. Dimensions 393 x 108 x 285 mm (287 mm over terminals), weight about 33 kg.
  3. Internal resistance 4.7 milliohm when fully charged.
  4. Capacity: 109% at 40 °C, 88% at 0 °C, 76% at -15 °C; 92% after 3 months of storage.
  5. Float 13.62 V, cycle charge 14.40 V, current limit 14 A; compensation -0.018 V/°C.
  6. Constant current at 1.75 V/cell end voltage: 5 min 267 A, 15 min 162 A, 1 h 62.1 A.
  7. Constant power at 1.75 V/cell: 5 min 513 W/cell, 15 min 282 W/cell, 1 h 121 W/cell.

Using it in design

  • Size UPS autonomy from the manufacturer's constant-power table, reading at the UPS cut-off voltage (for example 1.75 V per cell).
  • If the battery room runs below 25 °C, derate capacity with the table's temperature factor; use 88% at 0 °C.
  • Set the charger float voltage to 13.62 V per block and the compensation to -0.018 V/°C.
  • In rack and cabinet layout, carry the 393 x 108 mm footprint and 33 kg block weight into the floor-loading calculation.

Who should read it

Electrical designers sizing UPS battery strings and engineers preparing battery room layouts.

Document contents

  1. Specifications
  2. Characteristics
  3. Discharging characteristics curves
  4. Charging characteristics curves
  5. Constant current discharge table
  6. Constant power discharge table

Publication details

Authors
Coslight
Publisher
Coslight
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Coslight 6-GFM-100X/B VRLA battery datasheet. Coslight. https://www.ups-mag.ru/upload/files/akb/coslight/6_gfm_100xb.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.