6-GFM-100X/B VRLA battery datasheet (Coslight)
Original title 6-GFM-100X/B VRLA battery datasheet
Coslight
Coslight datasheet for the 12 V, 100 Ah (10-hour) 6-GFM-100X/B VRLA block: 393 x 108 x 287 mm, about 33 kg, with constant-current and constant-power discharge tables from 5 minutes to 8 hours.
On this page
Overview
The document is a one-page datasheet for the Coslight Group 6-GFM-100X/B valve-regulated lead-acid (VRLA) block; the original manufacturer sheet is hosted on a distributor's site. Nominal voltage is 12 V and the 10-hour rated capacity is 100 Ah at 25 °C. The block has a narrow case: length 393 mm, width 108 mm, case height 285 mm, 287 mm over terminals, and a weight of about 33 kg.
The sheet gives capacity against discharge time: 108 Ah at 20 hours, 100 Ah at 10 hours, 88 Ah at 5 hours and 62 Ah at 1 hour. Internal resistance of a fully charged block is 4.7 milliohm. Capacity depends on temperature: 109% at 40 °C, 100% at 25 °C, 88% at 0 °C and 76% at -15 °C. After three months of storage 92% of capacity remains.
Charging parameters are 14.40 V with at most 14 A for cycle use and 13.62 V with at most 14 A for float use, with a temperature compensation of -0.018 V/°C. Most of the page is the constant-current and constant-power tables: for end voltages of 1.60 to 1.85 V per cell it lists values from 5, 10, 15, 20, 30, 40 and 50 minutes and 1 to 6 hours. At 1.75 V per cell the 15-minute current is 162 A. The sheet contains no cabinet layout, life or warranty data; it provides block-level data only.
Key points
- Nominal 12 V, 100 Ah (10-hour rate, 25 °C); 108 Ah at 20 h, 88 Ah at 5 h, 62 Ah at 1 h.
- Dimensions 393 x 108 x 285 mm (287 mm over terminals), weight about 33 kg.
- Internal resistance 4.7 milliohm when fully charged.
- Capacity: 109% at 40 °C, 88% at 0 °C, 76% at -15 °C; 92% after 3 months of storage.
- Float 13.62 V, cycle charge 14.40 V, current limit 14 A; compensation -0.018 V/°C.
- Constant current at 1.75 V/cell end voltage: 5 min 267 A, 15 min 162 A, 1 h 62.1 A.
- Constant power at 1.75 V/cell: 5 min 513 W/cell, 15 min 282 W/cell, 1 h 121 W/cell.
Using it in design
- Size UPS autonomy from the manufacturer's constant-power table, reading at the UPS cut-off voltage (for example 1.75 V per cell).
- If the battery room runs below 25 °C, derate capacity with the table's temperature factor; use 88% at 0 °C.
- Set the charger float voltage to 13.62 V per block and the compensation to -0.018 V/°C.
- In rack and cabinet layout, carry the 393 x 108 mm footprint and 33 kg block weight into the floor-loading calculation.
Who should read it
Electrical designers sizing UPS battery strings and engineers preparing battery room layouts.
Document contents
- Specifications
- Characteristics
- Discharging characteristics curves
- Charging characteristics curves
- Constant current discharge table
- Constant power discharge table
Publication details
- Authors
- Coslight
- Publisher
- Coslight
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Coslight 6-GFM-100X/B VRLA battery datasheet. Coslight. https://www.ups-mag.ru/upload/files/akb/coslight/6_gfm_100xb.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.