Technical guideFree to readYear not stated

6-GFM-80C VRLA battery datasheet (Coslight)

Original title 6-GFM-80C VRLA battery datasheet

Coslight

Coslight datasheet for the 12 V, 80 Ah (10-hour) 6-GFM-80C VRLA block: 377 x 174 x 227 mm, about 30 kg, 6.3 milliohm internal resistance and discharge tables.

On this page

Overview

The document is a one-page datasheet for the Coslight Group 6-GFM-80C VRLA block; the manufacturer sheet is hosted on a distributor's site. Nominal voltage is 12 V and 10-hour capacity is 80 Ah. Length is 377 mm, width 174 mm, case height 217 mm, 227 mm over terminals, and weight is about 30 kg.

Capacity is 87 Ah at 20 hours, 80 Ah at 10 hours, 69 Ah at 5 hours and 46 Ah at 1 hour. Internal resistance of a fully charged block is 6.3 milliohm. The temperature effect matches the 100 Ah sister model: 109% at 40 °C, 88% at 0 °C, 76% at -15 °C. Capacity after three months of storage is given as 92%.

Charging is 14.10 V with at most 12 A for cycle use and 13.50 V with at most 12 A for float use; compensation is -0.018 V/°C. The constant-current and constant-power tables cover end voltages of 1.60 to 1.85 V per cell from 5 minutes to 8 hours. The document gives block-level parameters only; it does not describe a complete cabinet or the current product lifecycle.

Key points

  1. Nominal 12 V, 80 Ah (10-hour rate); 87 Ah at 20 h, 69 Ah at 5 h, 46 Ah at 1 h.
  2. Dimensions 377 x 174 x 217 mm (227 mm over terminals), weight about 30 kg.
  3. Internal resistance 6.3 milliohm when fully charged.
  4. Capacity 109% at 40 °C, 88% at 0 °C, 76% at -15 °C; 92% after 3 months of storage.
  5. Float 13.50 V, cycle charge 14.10 V, current limit 12 A.
  6. Constant current at 1.75 V/cell: 5 min 176 A, 15 min 120 A, 1 h 46.4 A.
  7. Constant power at 1.75 V/cell: 5 min 384 W/cell, 1 h 92 W/cell, 8 h 19 W/cell.

Using it in design

  • For string autonomy, read the constant-power row matching the UPS cut-off voltage.
  • Enter the charger float setting as 13.50 V per block for this model; do not reuse the 13.62 V figure of the 100 Ah model.
  • In cold battery rooms derate capacity using the temperature table.
  • Use the 377 x 174 mm footprint and 30 kg block weight in rack layout.

Who should read it

Designers sizing UPS battery strings and engineers writing purchase specifications.

Document contents

  1. Specifications
  2. Characteristics
  3. Discharging characteristics curves
  4. Charging characteristics curves
  5. Constant current discharge table
  6. Constant power discharge table

Publication details

Authors
Coslight
Publisher
Coslight
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Coslight 6-GFM-80C VRLA battery datasheet. Coslight. https://www.ups-mag.ru/upload/files/akb/coslight/6_gfm_80c.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.