Technical guideFree to readYear not stated

EAST EA660 Series modular UPS technical specifications, 400-1200 kVA

Original title EAST EA660 Series 100 kVA modular UPS technical specifications

EAST

EAST EA660 400-1200 kVA modular UPS: 100 kVA/3U power modules, 97% maximum efficiency, 97% at 40% load and 96% at 20% load, up to 4 units in parallel, output PF 1.

On this page

Overview

EAST's EA660 series is a three-phase modular UPS built from hot-swappable 100 kVA/100 kW power modules. The version on this page covers six systems of 400, 500, 600, 800, 1000 and 1200 kVA, with 4, 5, 6, 8, 10 and 12 power modules respectively. Features include dual DSP digital control, 100 kVA power density in 3U, a 600 kVA system footprint of only 0.8 m2 and an integrated PDU system.

Efficiency stays high at low load: 97% at 40% rated load and 96% at 20% rated load; maximum system efficiency is 97%. Input is 3 ph + N + PE, 380/400/415 V, 138-485 Vac (324-485 Vac without derating, linear 35% derating at 139-324 Vac), frequency 40-70 Hz, input power factor 0.99 or higher and current distortion below 3%. Soft start improves generator matching up to 1:1.1; 50/60 Hz frequency conversion is supported.

Output is 380/400/415 Vac +/-1% at power factor 1, with voltage distortion of 1% on linear and 3% on non-linear load, 3:1 crest factor and 0 ms transfer. Inverter overload transfers to bypass after 60 min at 105-110%, 10 min at 110-125%, 1 min at 125-150% and 200 ms above 150%; the bypass tolerates 125% continuously and above 200% for 100 ms. Battery voltage is 480 Vdc (360-600 Vdc selectable) with 40 x 12 V batteries (30-50 selectable); battery sharing in parallel operation is supported.

Physical data: cabinets are 800 x 1000 x 2000 mm (412 kg) and 2000 x 1000 x 2000 mm (920 kg); a power module is 440 x 750 x 130 mm and 50 kg. Operating temperature is 0-55 C, altitude to 1000 m (1% derating per further 100 m), IP20. With one fan failed 50% load can be carried, with two failed 20%. Communication is RS485, dry contacts and SNMP; the display is a 7-inch touch LCD. Efficiency headings without a stated condition should not be turned into a load curve.

Key points

  1. Six systems: 400, 500, 600, 800, 1000, 1200 kVA (kVA = kW); 4-12 modules of 100 kVA.
  2. Efficiency: maximum 97%; 97% at 40% load, 96% at 20% load.
  3. Input: 380/400/415 V, 138-485 Vac, 40-70 Hz, PF 0.99 or higher, THDi below 3%.
  4. Output PF 1, THDv 1% (linear) and 3% (non-linear), transfer 0 ms.
  5. Inverter overload: 60 min at 105-110%, 10 min at 110-125%, 1 min at 125-150%, 200 ms above 150%.
  6. Battery 480 Vdc, 40 x 12 V (30-50 selectable); up to 4 units in parallel.
  7. Cabinet 800 x 1000 x 2000 mm 412 kg and 2000 x 1000 x 2000 mm 920 kg; module 50 kg.
  8. Operation 0-55 C; altitude to 1000 m; fan fault tolerance (1 fan 50%, 2 fans 20% load).

Using it in design

  • Plan capacity in 100 kVA module steps, with an extra module for redundancy (N+1).
  • Use part-load efficiency (96% at 20%, 97% at 40%) in the load profile and PUE calculation.
  • Carry cabinet weight (412-920 kg) and module weight (50 kg) into floor loading and the installation plan.
  • Match the battery string (30-50 x 12 V) and DC window (360-600 Vdc) to the chosen autonomy.
  • Add generator soft-start and the input window (138-485 V) to the source compatibility check.

Who should read it

Data-centre electrical designers selecting large modular UPSs.

Document contents

  1. Characteristics
  2. Technical specifications
  3. Documents

Publication details

Authors
EAST
Publisher
EAST
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

EAST EAST EA660 Series 100 kVA modular UPS technical specifications. EAST. https://en.eastups.com/ModularUPS/8252.jhtml

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.