Technical guideFree to readYear not stated

EAST Sodium-ion All-in-one Power System technical specifications

EAST

EAST all-in-one sodium-ion UPS: 6, 10, 20, 30 and 40 kVA rack UPS, S3 sodium-ion battery and distribution unit in one cabinet; 6-10 kVA single-phase, 10-40 kVA three-phase.

On this page

Overview

EAST's all-in-one sodium-ion battery UPS solution combines a rack-mount UPS, an S3 sodium-ion battery and a distribution unit in one structure. No separate battery cabinet or distribution box is needed, which cuts the footprint. A touch screen monitors the UPS and S3 battery together; the battery module is hot-swappable and provides long backup. Ratings run from 6K to 40K.

The table lists 6 kVA and 10 kVA in 1:1 phase and 10, 20, 30 and 40 kVA in 3:3 phase. Input voltage is 110-288 V on single-phase models and 190-478 V on three-phase models, frequency 40-70 Hz, input power factor 0.99 or higher and THDi below 3% (linear load). Output power factor is 0.99; output voltage is 208/220/230/240 V +/-1% single-phase and 380/400/415 V +/-1% three-phase. Maximum AC/AC efficiency is 95.5% single-phase and 96% three-phase.

THDv is below 1% on linear load and below 4% (single-phase) or 3% (three-phase) on non-linear load; transfer time is 0 ms. Overload is 10 min at 115-130%, 30 s at 130-150% and 500 ms above 150% single-phase; 10 min at 115-125%, 1 min at 125-150% and 200 ms above 150% three-phase. Communication is RS232, EPO and USB (slot), with SNMP and RS485/dry contact optional.

Physical data: UPS sizes are 440 x 580 x 88 mm (2U) and 440 x 660 x 130 mm (3U); UPS weights are 12, 14, 20 and 34 kg; the cabinet is 600 x 900 x (1200/1500/1700) mm and 120 kg (without UPS and batteries). Noise is below 55 dB, operating temperature -5 to 40 C, relative humidity 0-95%. The page gives no battery capacity, autonomy time or efficiency curve; efficiency headings without a stated condition should not be turned into a load curve.

Key points

  1. Ratings: 6, 10, 10, 20, 30, 40 kVA (6K and 10K 1:1; 10K to 40K 3:3).
  2. Input: single-phase 110-288 V, three-phase 190-478 V; 40-70 Hz; PF 0.99 or higher; THDi below 3%.
  3. Output PF 0.99; 208/220/230/240 V (single-phase) and 380/400/415 V (three-phase), +/-1%.
  4. Maximum AC/AC efficiency: 95.5% single-phase; 96% three-phase.
  5. Transfer time 0 ms.
  6. Overload (single-phase): 10 min at 115-130%; three-phase: 10 min at 115-125%.
  7. UPS sizes 2U (440 x 580 x 88 mm) and 3U (440 x 660 x 130 mm); cabinet 600 x 900 x 1200/1500/1700 mm.
  8. Noise below 55 dB; operation -5 to 40 C.

Using it in design

  • Treat the structure without a separate battery cabinet and distribution as a footprint advantage in small rooms and server rooms.
  • Match phase configuration (1:1 or 3:3) and output voltage to the load voltage.
  • Confirm autonomy time from the battery module capacity with the manufacturer; the page does not give it.
  • Add the temperature and life characteristics of sodium-ion batteries to the technology comparison with lead-acid and Li-ion.
  • Carry communication options (SNMP, RS485) into the BMS/DCIM plan.

Who should read it

Server-room and data-centre designers evaluating compact UPSs and new battery technology.

Document contents

  1. All-in-one solution features
  2. Technical specifications table
  3. Documents

Publication details

Authors
EAST
Publisher
EAST
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

EAST EAST Sodium-ion All-in-one Power System technical specifications. EAST. https://en.eastups.com/LiFePO4SodiumionUPS/8474.jhtml

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.