EAST Sodium-ion All-in-one Power System technical specifications
EAST
EAST all-in-one sodium-ion UPS: 6, 10, 20, 30 and 40 kVA rack UPS, S3 sodium-ion battery and distribution unit in one cabinet; 6-10 kVA single-phase, 10-40 kVA three-phase.
On this page
Overview
EAST's all-in-one sodium-ion battery UPS solution combines a rack-mount UPS, an S3 sodium-ion battery and a distribution unit in one structure. No separate battery cabinet or distribution box is needed, which cuts the footprint. A touch screen monitors the UPS and S3 battery together; the battery module is hot-swappable and provides long backup. Ratings run from 6K to 40K.
The table lists 6 kVA and 10 kVA in 1:1 phase and 10, 20, 30 and 40 kVA in 3:3 phase. Input voltage is 110-288 V on single-phase models and 190-478 V on three-phase models, frequency 40-70 Hz, input power factor 0.99 or higher and THDi below 3% (linear load). Output power factor is 0.99; output voltage is 208/220/230/240 V +/-1% single-phase and 380/400/415 V +/-1% three-phase. Maximum AC/AC efficiency is 95.5% single-phase and 96% three-phase.
THDv is below 1% on linear load and below 4% (single-phase) or 3% (three-phase) on non-linear load; transfer time is 0 ms. Overload is 10 min at 115-130%, 30 s at 130-150% and 500 ms above 150% single-phase; 10 min at 115-125%, 1 min at 125-150% and 200 ms above 150% three-phase. Communication is RS232, EPO and USB (slot), with SNMP and RS485/dry contact optional.
Physical data: UPS sizes are 440 x 580 x 88 mm (2U) and 440 x 660 x 130 mm (3U); UPS weights are 12, 14, 20 and 34 kg; the cabinet is 600 x 900 x (1200/1500/1700) mm and 120 kg (without UPS and batteries). Noise is below 55 dB, operating temperature -5 to 40 C, relative humidity 0-95%. The page gives no battery capacity, autonomy time or efficiency curve; efficiency headings without a stated condition should not be turned into a load curve.
Key points
- Ratings: 6, 10, 10, 20, 30, 40 kVA (6K and 10K 1:1; 10K to 40K 3:3).
- Input: single-phase 110-288 V, three-phase 190-478 V; 40-70 Hz; PF 0.99 or higher; THDi below 3%.
- Output PF 0.99; 208/220/230/240 V (single-phase) and 380/400/415 V (three-phase), +/-1%.
- Maximum AC/AC efficiency: 95.5% single-phase; 96% three-phase.
- Transfer time 0 ms.
- Overload (single-phase): 10 min at 115-130%; three-phase: 10 min at 115-125%.
- UPS sizes 2U (440 x 580 x 88 mm) and 3U (440 x 660 x 130 mm); cabinet 600 x 900 x 1200/1500/1700 mm.
- Noise below 55 dB; operation -5 to 40 C.
Using it in design
- Treat the structure without a separate battery cabinet and distribution as a footprint advantage in small rooms and server rooms.
- Match phase configuration (1:1 or 3:3) and output voltage to the load voltage.
- Confirm autonomy time from the battery module capacity with the manufacturer; the page does not give it.
- Add the temperature and life characteristics of sodium-ion batteries to the technology comparison with lead-acid and Li-ion.
- Carry communication options (SNMP, RS485) into the BMS/DCIM plan.
Who should read it
Server-room and data-centre designers evaluating compact UPSs and new battery technology.
Document contents
- All-in-one solution features
- Technical specifications table
- Documents
Publication details
- Authors
- EAST
- Publisher
- EAST
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
EAST EAST Sodium-ion All-in-one Power System technical specifications. EAST. https://en.eastups.com/LiFePO4SodiumionUPS/8474.jhtml
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.