Technical guideFree to readYear not stated

MPOWERSYS Tower Online UPS SMART Series Technical Table

Original title MPOWERSYS tower online UPS SMART series technical table

MPOWERSYS

The MPOWERSYS SMART series is a 1 to 10 kVA single-phase online double-conversion tower UPS with input power factor of at least 0.99, efficiency of 92 to 94% and 0 ms transfer time.

On this page

Overview

The MPOWERSYS SMART series is a small-capacity family of tower-type online double-conversion UPS units. There are five models: SMART-1001 (1 kVA), 1002 (2 kVA), 1003 (3 kVA), 1005 (5 kVA) and 1010 (10 kVA). Input voltage is 160 to 295 V, frequency 50/60 Hz ±5%, input is single-phase two-wire and input power factor is at least 0.99. Output voltage is 220 or 230 V ±1% and output THD is below 3% on linear load.

The page lists a wide input voltage range, hot-swappable batteries, over-current, short-circuit and overload protection, an EMI/RFI filter, ECO and EPO functions, external battery and cabinet options, RS-232/422/USB ports (SNMP and RS485 optional) and a 0 ms transfer time. Efficiency is 92 to 94% and the power factor is 0.99. Listed applications are data centres, retail, hubs, network devices, routers, precision equipment and commercial facilities.

Output power is given as 1000 VA / 900 W, 2000 / 1800, 3000 / 2700, 5000 / 4800 and 10000 / 8000 W, with output power factor of 0.8 to 0.9. Battery voltage is 24/36, 48/72, 72/96 or 192 V and backup time is selectable, for example 10, 30 or 60 minutes. Noise is 50 to 60 dB, operating temperature -5 to 40 °C and humidity 0 to 95%. Weight ranges from 7 to 70 kg. The document is the product page's feature and dimension table.

Key points

  1. Five models: 1, 2, 3, 5, 10 kVA (SMART-1001 to SMART-1010).
  2. Input 160 to 295 V, 50/60 Hz ±5%, single-phase; input power factor ≥0.99.
  3. Output 220 or 230 V ±1%; THD <3% (linear load); transfer time 0 ms.
  4. Output power: 1000/900, 2000/1800, 3000/2700, 5000/4800, 10000/8000 VA/W.
  5. Efficiency 92 to 94%; ECO and EPO functions; hot-swappable battery.
  6. Battery voltage 24/36, 48/72, 72/96 or 192 V; backup time selectable at 10, 30, 60 minutes.
  7. Communication RS-232, 422, USB; SNMP, RS485 and dry contact optional.
  8. Operation -5 to 40 °C, humidity 0 to 95%; noise 50 to 60 dB.

Using it in design

  • On the 10 kVA model, note that active power is 8000 W; select by kW.
  • The input range down to 160 V reduces battery use at sites with weak mains.
  • Match battery voltage (24 to 192 V) to model capacity and state the backup time at order stage.
  • For network and office use, add the SNMP option to the specification along with the monitoring requirement.
  • Use ECO mode on non-critical loads to raise efficiency and keep it off for sensitive loads.

Who should read it

Engineers selecting tower UPS units for small server rooms and network equipment.

Document contents

  1. Product features
  2. Electrical characteristics
  3. Dimensions and weight

Publication details

Authors
MPOWERSYS
Publisher
MPOWERSYS
Year
Year not stated
Document language
Korean
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only. Original publisher HTTP URL retained as a bibliographic link. Its HTTPS counterpart could not be verified on 2026-11-16; no content was downloaded or redistributed.

Citation

MPOWERSYS MPOWERSYS tower online UPS SMART series technical table. MPOWERSYS. http://www.mpowersys.co.kr/bbs/page.php?hid=ups_tower

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.