MPOWERSYS Three-Phase Input/Output UPS MPS 3000 Series Technical Table

Original title MPOWERSYS three-phase input/output UPS technical table

MPOWERSYS

MPOWERSYS MPS-3000 is a true online UPS from 20 to 200 kVA with three-phase input and output, isolation transformers on input and output, DSP control, efficiency above 90% and 0.99 input power factor.

On this page

Overview

The MPOWERSYS MPS-3000 series is a double-conversion true online UPS family with fully digital control by a 32-bit high-speed DSP and isolation transformers on both input and output. The manufacturer highlights high-quality output voltage, good response to changing loads, uninterrupted transfer and over-voltage protection and filtering. A colour touch screen offers Korean and English display and a mimic diagram for operation.

There are seven models: MPS-3200 (20 kVA), 3300 (30), 3500 (50), 3800 (80), 31000 (100), 31500 (150) and 32000 (200 kVA). Input power factor is 0.99 and the rectifier device is SCR; efficiency is above 90%. Input is three-phase 208/220/380/480 VAC ±15% (user selectable), frequency 50/60 Hz ±5%; output voltage uses the same options at ±2% and output frequency is 50/60 Hz ±0.5%.

Inverter overload capacity is 120% for 10 minutes. Operating temperature is 0 to 40 °C and protection class IP20. Noise is 60 to 75 dB depending on the model. The battery count is optional at 12 V units in 16, 20, 30 or 32 cells. Some table rows (THD, voltage stability) are left without values in the source. The document is the product page's feature and dimension table.

Key points

  1. Seven models: 20, 30, 50, 80, 100, 150, 200 kVA (MPS-3200 to MPS-32000).
  2. Double-conversion true online; isolation transformers on input and output; 32-bit DSP, colour touch screen.
  3. Input power factor 0.99; rectifier device SCR.
  4. Efficiency above 90%; protection class IP20.
  5. Input: 3-phase 208/220/380/480 VAC ±15% (selectable), 50/60 Hz ±5%.
  6. Output: same voltage options ±2%; 50/60 Hz ±0.5%.
  7. Inverter overload 120% for 10 minutes; operation 0 to 40 °C.
  8. Battery: 12 V units, 16, 20, 30 or 32 cells optional; noise 60 to 75 dB.

Using it in design

  • Input and output isolation transformers help where galvanic separation and neutral reference are needed; account for transformer losses within the above-90% efficiency.
  • Match the battery cell-count option (16 to 32) to the battery maker's float voltage and the DC bus range.
  • With noise up to 75 dB, plan to place the unit in a separate electrical room.
  • With 208/220/380/480 VAC selectable, fix the site voltage level at order stage.
  • Ask the manufacturer for the missing THD and voltage-stability values.

Who should read it

Electrical engineers seeking transformer-based industrial UPS units from 20 to 200 kVA.

Document contents

  1. Product description
  2. Electrical characteristics
  3. Dimension table

Publication details

Authors
MPOWERSYS
Publisher
MPOWERSYS
Year
Year not stated
Document language
Korean
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only. Original publisher HTTP URL retained as a bibliographic link. Its HTTPS counterpart could not be verified on 2026-11-16; no content was downloaded or redistributed.

Citation

MPOWERSYS MPOWERSYS three-phase input/output UPS technical table. MPOWERSYS. http://www.mpowersys.co.kr/bbs/page.php?hid=ups_mps03

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.