Toshiba G2020 Series SiC UPS, 500/750 kVA brochure
Original title Toshiba G2020 Series SiC 500/750 kVA brochure
Toshiba
Toshiba G2020 is a silicon-carbide (SiC) double-conversion UPS in 500 kVA/kW and 750 kVA/kW, with typical AC-AC efficiency of 98.2%, parallel operation up to 8 units and no derating up to 40 °C and 1981 m.
On this page
Overview
The Toshiba International Power Electronics brochure presents the G2020 series as one of the world's first UPSs to use SiC technology. There are two models: T200H0500KWWW (500 kVA/500 kW) and T200H0750KWWW (750 kVA/750 kW). The design is true online double conversion, offers a separate second input for bypass and uses all-digital signal-processor control. Target sites are data centres, edge and colocation facilities, banking and healthcare.
An efficiency curve is shown against load percentage for the 500 kVA/kW model. Typical AC-AC efficiency is 98.2%; curve points run from about 90.9% at 5% load, above 98.2% at mid loads, to about 97.8% at 100% load.
Technical data: 480 V +15%/-20%, 60 Hz ±10%, three-phase three-wire input, with reflected current THDi of typically 3% at full load (no input filter required). Static bypass input is 480 V ±10%. Output is 480 V with ±1% regulation, unity nominal power factor and a 0.7 lagging to 0.8 leading range, voltage THD at most 2% on linear load and 5% on non-linear load. Overload is 125% for 1 minute, 150% for 10 seconds and 500% for 1 cycle on bypass.
Energy storage may be lead-acid or lithium-ion: nominal 480 Vdc, minimum 400 Vdc, 240 cells for VRLA. RemotEye 4 monitoring supports HTTP(S), SNMP, Modbus RTU and TCP, and BACnet MSTP and IP. Operation is 0-40 °C (recommended 20-30 °C), 5-95% humidity and 0-1981 m altitude with no capacity derating up to 40 °C. Dimensions are 59.1 x 33.5 x 80.6 in for 500 kVA and 84.7 x 33.5 x 80.6 in for 750 kVA.
Key points
- Models: 500 kVA/500 kW and 750 kVA/750 kW; SiC technology, online double conversion.
- Typical AC-AC efficiency 98.2%; parallel up to 8 units.
- Input 480 V +15%/-20%, 60 Hz ±10%; input THDi typically 3% at full load.
- Output 480 V, ±1% regulation, nominal power factor 1.0; range 0.7 lagging to 0.8 leading.
- Voltage THD at most 2% (linear) and 5% (non-linear load).
- Overload: 125% for 1 minute, 150% for 10 seconds; bypass 500% for 1 cycle.
- Transient response: ±2% on load step, ±1% on loss/return of AC, ±5% on bypass transfer; recovery under 20 ms.
- Energy storage: lead-acid or lithium-ion, 480 Vdc, 240 cells for VRLA.
- No capacity derating up to 40 °C and 1981 m; size 59.1 x 33.5 x 80.6 in (500 kVA).
Using it in design
- At hyperscale and colocation sites, weigh the typical 98.2% efficiency against the drop at low load (for example 90.9% at 5%) and compute annual loss from the operating profile.
- With unity power factor take kW equal to kVA, and keep loads in the 0.7 lagging to 0.8 leading range within the kW rating.
- Since no input filter is needed at 480 V, use the 3% THDi in the harmonic study.
- Plan the number of parallel units (up to 8) around an N+1 or 2N architecture and reserve 1016 mm front and 610 mm top clearance in the layout.
- Decide battery type (lead-acid or lithium-ion) and autonomy per project; the brochure leaves ride-through application specific.
Who should read it
Data-centre electrical designers writing large UPS specifications.
Document contents
- SiC technology and features
- Efficiency curve and power flow diagram
- Specifications: AC input, static bypass, energy storage
- AC output, overload, environment
- Industries served and applications
Publication details
- Authors
- Toshiba
- Publisher
- Toshiba
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Toshiba Toshiba G2020 Series SiC 500/750 kVA brochure. Toshiba. https://toshiba.com/tic/wp-content/uploads/G2020_Series_ESSENCE_101619_nocrop.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.