REVO three-phase UPS lithium battery solution

Vision

Vision's REVO series provides UPS backup from 19-inch LFP modules that connect in series as 51.2 V x n (5 ≤ n ≤ 14): discharge efficiency of 95% or more, 2,500 cycles at 1C and a 15-year design life.

On this page

Overview

Vision's REVO product page presents a lithium iron phosphate (LFP) battery system for three-phase UPS. The series offers a high discharge rate and discharge efficiency of 95% or more, full cell-state management and cabinet-level fire response within seconds. A four-level safety architecture is used. Cycle life is at least 2,500 at 1C and design life is 15 years; an optional cloud management platform supports operations.

Applications are data centres, financial institutions, rail transit and backup power in off-grid areas. Series module connection allows voltage configurations of 51.2 V x n (5 ≤ n ≤ 14) and parallel connection allows power expansion. The system supports two-wire and three-wire connections and is compatible with mainstream UPS designs. Controlled circulating current management allows new and old modules to run together. Prefabricated delivery speeds installation.

In the specification table, modules use a standard 19-inch cabinet with full front wiring and an integrated single-cell monitoring unit. Models are TPH10 (51.2 V 50 Ah, 1P16S, 442x600x127 mm, 2.05 kWh), TP10 (50 Ah, 442x690x106 mm, 2.56 kWh), TP20 (51.2 V 100 Ah, 2P16S, 442x800x150 mm, 5.12 kWh), TPL5 (100 Ah cell, 1P16S, 442x690x108 mm, 5.12 kWh) and TPL10 (51.2 V 200 Ah, 2P16S, 442x800x149 mm, 10.24 kWh).

The rack table lists 600 x 1000 x 2000 mm racks: TPH160 (409.6 V, 8 modules, 16.38 kWh), TPH200 (512 V, 10 modules, 20.48 kWh), TPH240 (614.4 V, 12 modules, 24.50 kWh), TP80 (409.6 V, 20.48 kWh), TP100 (512 V, 25.60 kWh), TP120 (614.4 V, 30.72 kWh), TP140 (716.8 V, 14 modules, 600x1000x2300 mm, 35.84 kWh), TP160 (409.6 V 100 Ah, 8 TP20 modules, 40.96 kWh) and TP200 (512 V 100 Ah). Racks arrive pre-installed for FCL transport with status indication.

Key points

  1. LFP chemistry; discharge efficiency 95% or more; 15-year design life; at least 2,500 cycles at 1C.
  2. Four-level safety architecture; cabinet-level fire response within seconds.
  3. Series connection 51.2 V x n (5 ≤ n ≤ 14); parallel connection for power expansion.
  4. Two-wire and three-wire UPS connection; controlled circulating current allows mixing new and old modules.
  5. Module sizes: 442 mm width; TPH10 442x600x127 mm 2.05 kWh, TP10 442x690x106 mm 2.56 kWh, TP20 442x800x150 mm 5.12 kWh, TPL10 442x800x149 mm 10.24 kWh.
  6. Racks 600 x 1000 x 2000 mm (2300 mm high for TP140); TP80 20.48 kWh up to TP140 35.84 kWh, TP160 40.96 kWh.
  7. Rack voltages: 409.6 V, 512 V, 614.4 V, 716.8 V (8, 10, 12, 14 modules).
  8. Applications: data centres, financial institutions, rail transit, off-grid backup.

Using it in design

  • Choose the module count from the UPS DC bus voltage (51.2 V x 8 = 409.6 V, x10 = 512 V, x12 = 614.4 V, x14 = 716.8 V) and confirm the UPS accepts that battery voltage window.
  • Compare the required backup energy (kWh) with rack kWh and discharge power; use the 600 x 1000 mm footprint and 2000/2300 mm height in the layout.
  • Use the two-wire or three-wire UPS connection type as an input to rack selection.
  • Record the ability to mix old and new modules in the lifecycle plan for future module replacement.
  • Compare the life claim (15-year design, 2,500 cycles at 1C) with lead-acid replacement intervals in total cost of ownership.

Who should read it

Electrical engineers designing lithium-based UPS backup and writing battery system specifications.

Document contents

  1. Overview
  2. Application scenarios
  3. Battery quick facts
  4. Key features
  5. Module table
  6. Rack table

Publication details

Authors
Vision
Publisher
Vision
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Vision REVO three-phase UPS lithium battery solution. Vision. https://www.vision-batt.com/en/product/show/post-74.html

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.