ZincFive Nickel-Zinc Monobloc Battery, High Rate (80 Ah / 90 Ah)

Original title Nickel-zinc high-rate and ultra-high-rate monobloc batteries

ZincFive

ZincFive Z5 13-80 H and 13-90 U nickel-zinc monobloc batteries are 13 V, 8-cell, 1.0-1.2 kWh units with 8-12 kW continuous discharge, over 10C discharge, over 15-year design life and UL 9540A.

On this page

Overview

The datasheet describes ZincFive's High-Rate (Z5 13-80 H S F, 80 Ah) and Ultra High-Rate (Z5 13-90 U S F, 90 Ah) nickel-zinc monobloc batteries. The maker lists UL 9540A certification with no thermal runaway, a chemistry that fails conductive so weak or depleted cells keep discharging, more than 10C discharge with 2C recharge, and wide temperature tolerance. Applications are backup, grid operations support and EV charger power buffering.

Electrical data: nominal voltage 13 V, 8 cells, operating range 10-15.2 V. Capacity at 1C is at least 80 Ah (1.0 kWh) and 90 Ah (1.2 kWh). Maximum continuous discharge power (100% to 0% state of charge) is 8,000 W and 12,000 W above 15 °C; short-circuit current 5,400 A and 6,200 A; AC impedance (1 kHz) at most 2.5 and 2.3 mΩ. Charging is constant current to 15.1 V (80 Ah) or 15.04 V (90 Ah), then constant voltage until a 4.0 A cutoff; charge rate is 20-160 A / 20-180 A and discharge rate 40-800 A / 40-1300 A.

Environmental and mechanical: charge 0 to 50 °C, discharge -20 to 45 °C, storage -20 to +50 °C; design life over 15 years at 25 °C. Size is about 278x175x188 mm, weight 15.5 kg (80 Ah) and 16.8 kg (90 Ah); the case is rated V-0, terminals are M6x1 with 10 N-m ±1 torque. Approvals include UL 1989, CSA C22.2 No. 60950-1, ANSI/CAN/UL 1973, CE, RoHS and EU 2023/1542. The lead-acid equivalent at an 80 A (1C) discharge is typically 250 Ah (C10).

Key points

  1. Models Z5 13-80 H S F (High-Rate, 80 Ah, 1.0 kWh) and Z5 13-90 U S F (Ultra High-Rate, 90 Ah, 1.2 kWh).
  2. Nominal 13 V, 8 cells, operating range 10-15.2 V.
  3. Continuous discharge power 8,000 W and 12,000 W (above 15 °C); short-circuit current 5,400 A and 6,200 A.
  4. Impedance (1 kHz) at most 2.5 mΩ (80 Ah) and 2.3 mΩ (90 Ah).
  5. Discharge current 40-800 A and 40-1300 A; charge current 20-160 A and 20-180 A; charge 15.1 / 15.04 V with 4.0 A cutoff.
  6. Charge 0-50 °C, discharge -20 to 45 °C, storage -20 to 50 °C; design life over 15 years at 25 °C.
  7. Weight 15.5 kg and 16.8 kg; size 278x175x188 mm; terminal torque 10 N-m ±1.
  8. Lead-acid equivalent at 80 A discharge is typically 250 Ah (C10); certified UL 9540A, UL 1973, UL 1989.

Using it in design

  • Size the UPS battery cabinet for 8-12 kW per block and 5,400-6,200 A short-circuit current; select DC switch and fuse breaking capacity accordingly.
  • Use the 250 Ah (C10) lead-acid equivalent only for short high-rate discharge; recalculate capacity for long autonomy.
  • With charge at 0-50 °C and discharge at -20 to 45 °C, verify the battery room thermal design against these limits.
  • Write the terminal torque (10 N-m ±1) and annual retorque into the maintenance plan.
  • Attach the UL 9540A test result to the building and fire code review.

Who should read it

UPS designers and battery system integrators selecting short-duration high-power batteries.

Document contents

  1. Benefits of NiZn Technology
  2. Specifications: Electrical, Environmental, Mechanical, Certifications
  3. Product drawing

Publication details

Authors
ZincFive
Publisher
ZincFive
Year
Year not stated
Document number
MKT-LIT-0006 REV10.0
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

ZincFive Nickel-zinc high-rate and ultra-high-rate monobloc batteries. ZincFive. MKT-LIT-0006 REV10.0. https://zincfive.com/wp-content/uploads/2025/11/MKT-LIT-0006-Rev_9.0.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.