ZincFive NiZn Retrofit Kit: Replacing VRLA Batteries with Nickel-Zinc

Original title Nickel-zinc retrofit kit for existing UPS battery cabinets

ZincFive

The ZincFive NiZn Retrofit Kit replaces VRLA batteries in existing UPS cabinets with 13 V, 80-90 Ah nickel-zinc monoblocs: 36-39 block strings for 1-2.5 MW UPS and a 15-year life.

On this page

Overview

The document presents a nickel-zinc (NiZn) retrofit kit designed as a direct replacement for VRLA batteries in UPS systems with external battery cabinets. The kit delivers ZincFive monobloc batteries and a BMS in standard tray formats and aims to avoid the regulatory and fire-safety challenges of lithium-based retrofits. The typical UPS range is 1-2.5 MW, and engineering validation may be required.

Architecture: each monobloc is 13 V nominal, 8 cells, 80-90 Ah (1.0-1.2 kWh). A string holds 36-39 blocks, giving a nominal system voltage of 468-507 V DC, maximum charge voltage of 537-600 V DC and low-voltage cutoff of 360-390 V DC. Per block, continuous discharge power is 8,000-12,000 W, maximum discharge current 800-1200 A and short-circuit current 5,400-7,222 A. Recharge time is 2-5 hours.

Environmental and mechanical data: discharge from -20 to 50 °C, charge from 15 to 40 °C, recommended operation 20-35 °C. A block measures 278x174.6x188 mm and weighs 16-18 kg. Shelf trays fit cabinets 40 in wide and 29.5-30.5 in deep (up to 38 in). The BMS monitors voltage, current and temperature with Ethernet, Modbus TCP/RTU and USB. The battery is certified to UL 9540A, UL 1973, UL 1989 and IBC 2021 / ICC AC156; the BMS to UL 61010-1.

Key points

  1. Chemistry: nickel-zinc (NiZn), wet alkali electrolyte; replaces VRLA strings.
  2. Monobloc 13 V, 8 cells, 80-90 Ah, 1.0-1.2 kWh; 36-39 blocks per string.
  3. Nominal system voltage 468-507 V DC; maximum charge 537-600 V DC; low-voltage cutoff 360-390 V DC.
  4. Per block maximum discharge power 8,000-12,000 W, current 800-1200 A; short circuit 5,400-7,222 A.
  5. Recharge time 2-5 hours; typical charge current about 90 A.
  6. Discharge temperature -20 to 50 °C, charge 15 to 40 °C; recommended 20-35 °C.
  7. 15-year life, 3x the power density of VRLA, no thermal runaway risk.
  8. Certifications: UL 9540A, UL 1973, UL 1989, IBC 2021 / ICC AC156; UL 61010-1 for the BMS.

Using it in design

  • Compare the inner width and depth of the existing VRLA cabinet (40 in wide, 29.5-30.5 in deep) with the tray dimensions.
  • Verify the UPS DC bus window against the 360-600 V DC range of a 36-39 block string.
  • If the charge temperature range (15-40 °C) sits at the edge of the battery room thermal design, review cooling.
  • Connect the BMS Modbus TCP/RTU output to the existing monitoring system.
  • Discuss fire-suppression requirements with the authority having jurisdiction using the UL 9540A result.

Who should read it

Data centre operators refreshing existing UPS battery cabinets and battery service providers.

Document contents

  1. Benefits
  2. High Power Density, Where You Need It
  3. Specifications: System Overview, System Architecture, Battery Performance, Charging, Environmental, Mechanical, System Monitoring, Certifications

Publication details

Authors
ZincFive
Publisher
ZincFive
Year
Year not stated
Document number
MKT-LIT-0081 Rev.1.0
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

ZincFive Nickel-zinc retrofit kit for existing UPS battery cabinets. ZincFive. MKT-LIT-0081 Rev.1.0. https://zincfive.com/wp-content/uploads/2026/04/NiZn-Retrofit-Kit-MKT-LIT-0081-Rev.-1.0.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.