ZincFive NiZn Retrofit Kit: Replacing VRLA Batteries with Nickel-Zinc
Original title Nickel-zinc retrofit kit for existing UPS battery cabinets
ZincFive
The ZincFive NiZn Retrofit Kit replaces VRLA batteries in existing UPS cabinets with 13 V, 80-90 Ah nickel-zinc monoblocs: 36-39 block strings for 1-2.5 MW UPS and a 15-year life.
On this page
Overview
The document presents a nickel-zinc (NiZn) retrofit kit designed as a direct replacement for VRLA batteries in UPS systems with external battery cabinets. The kit delivers ZincFive monobloc batteries and a BMS in standard tray formats and aims to avoid the regulatory and fire-safety challenges of lithium-based retrofits. The typical UPS range is 1-2.5 MW, and engineering validation may be required.
Architecture: each monobloc is 13 V nominal, 8 cells, 80-90 Ah (1.0-1.2 kWh). A string holds 36-39 blocks, giving a nominal system voltage of 468-507 V DC, maximum charge voltage of 537-600 V DC and low-voltage cutoff of 360-390 V DC. Per block, continuous discharge power is 8,000-12,000 W, maximum discharge current 800-1200 A and short-circuit current 5,400-7,222 A. Recharge time is 2-5 hours.
Environmental and mechanical data: discharge from -20 to 50 °C, charge from 15 to 40 °C, recommended operation 20-35 °C. A block measures 278x174.6x188 mm and weighs 16-18 kg. Shelf trays fit cabinets 40 in wide and 29.5-30.5 in deep (up to 38 in). The BMS monitors voltage, current and temperature with Ethernet, Modbus TCP/RTU and USB. The battery is certified to UL 9540A, UL 1973, UL 1989 and IBC 2021 / ICC AC156; the BMS to UL 61010-1.
Key points
- Chemistry: nickel-zinc (NiZn), wet alkali electrolyte; replaces VRLA strings.
- Monobloc 13 V, 8 cells, 80-90 Ah, 1.0-1.2 kWh; 36-39 blocks per string.
- Nominal system voltage 468-507 V DC; maximum charge 537-600 V DC; low-voltage cutoff 360-390 V DC.
- Per block maximum discharge power 8,000-12,000 W, current 800-1200 A; short circuit 5,400-7,222 A.
- Recharge time 2-5 hours; typical charge current about 90 A.
- Discharge temperature -20 to 50 °C, charge 15 to 40 °C; recommended 20-35 °C.
- 15-year life, 3x the power density of VRLA, no thermal runaway risk.
- Certifications: UL 9540A, UL 1973, UL 1989, IBC 2021 / ICC AC156; UL 61010-1 for the BMS.
Using it in design
- Compare the inner width and depth of the existing VRLA cabinet (40 in wide, 29.5-30.5 in deep) with the tray dimensions.
- Verify the UPS DC bus window against the 360-600 V DC range of a 36-39 block string.
- If the charge temperature range (15-40 °C) sits at the edge of the battery room thermal design, review cooling.
- Connect the BMS Modbus TCP/RTU output to the existing monitoring system.
- Discuss fire-suppression requirements with the authority having jurisdiction using the UL 9540A result.
Who should read it
Data centre operators refreshing existing UPS battery cabinets and battery service providers.
Document contents
- Benefits
- High Power Density, Where You Need It
- Specifications: System Overview, System Architecture, Battery Performance, Charging, Environmental, Mechanical, System Monitoring, Certifications
Publication details
- Authors
- ZincFive
- Publisher
- ZincFive
- Year
- Year not stated
- Document number
- MKT-LIT-0081 Rev.1.0
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
ZincFive Nickel-zinc retrofit kit for existing UPS battery cabinets. ZincFive. MKT-LIT-0081 Rev.1.0. https://zincfive.com/wp-content/uploads/2026/04/NiZn-Retrofit-Kit-MKT-LIT-0081-Rev.-1.0.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.