Technical guideFree to read2016

Raritan intelligent rack transfer switch datasheet (2016)

Raritan (Legrand)

Raritan's (Legrand) 2016 PX3TS datasheet presents a hybrid rack transfer switch that combines relays with SCRs: it moves a load between two sources in 4 to 8 ms and lists 13 models from 1U 16 A to 2U 32 A.

On this page

Overview

The document is the three-page datasheet for the PX3TS family, a rack-mounted transfer switch that connects single-corded IT devices to two separate feeds. Raritan positions the product as a hybrid design that puts electromechanical relays and silicon-controlled rectifiers (SCRs) in the same circuit. The stated aim is a unit that is faster and more dependable than relay-only automatic transfer switches (ATS), and cheaper and cooler-running than all-semiconductor static transfer switches (STS). The unit has no fans.

The datasheet compares the three technologies by transfer time. Relay-based ATS units are quoted at 8 to 16 ms depending on vendor, SCR-based STS units at normally 4 to 6 ms, and the Raritan hybrid at 4 to 8 ms. For relay-based units, contact welding caused by arcing is named as a leading failure cause; because such units do not report a welded contact, the fault only shows when an outage occurs and no switchover follows. For STS units the sheet cites a cost more than five and a half times that of electromechanical switches, higher energy draw and a need for forced cooling.

Protection and monitoring form the second main theme. The relays are oversized at a 70 A rating, the fast-blow fuses are field replaceable, and the unit detects an output short circuit and blocks the transfer so the fault does not cascade onto the second feed. Transfers between out-of-phase sources are supported. Metering accuracy is given as billing grade at ±1%, and the 5000 series adds outlet-level metering and switching. The Xerus firmware provides SNMP, Modbus, JSON-RPC, email, syslog and GSM text alerts, and records the AC waveform of the last transfer.

The final part is the model table: chassis height, input voltage, plug type, outlet type and quantity, current, circuit-breaker quantity and Ethernet are listed for 13 models. The 1U models carry 16 A (20 A on the Clipsal-plug models) with 7 or 8 C13 outlets and 1 C19; the 2U models offer 16 C13 and 4 C19 outlets at 24 A or 32 A. The operating environment is certified to 60 °C under UL and 50 °C under CE at 85% relative humidity. The document is a product sheet; it gives no test conditions for the transfer times and no numeric efficiency values.

Key points

  1. The hybrid relay-plus-SCR design transfers a load in 4 to 8 ms; the sheet gives 8 to 16 ms for relay ATS units and normally 4 to 6 ms for SCR STS units.
  2. STS units are described as more than five and a half times the cost of electromechanical switches, drawing more energy and needing forced cooling.
  3. The relays are rated 70 A, and the anti-arcing circuit is designed to prevent contact welding.
  4. An output short circuit blocks the transfer and raises an alarm, so the fault is not carried onto the second feed.
  5. Power metering accuracy is ±1%; the PX3TS-5000 series has outlet-level metering and switching.
  6. 1U models: 16 A or 20 A, 7 or 8 C13 plus 1 C19 (8 NEMA 5-20R on the 120 V model), no circuit breakers.
  7. 2U models: PX3TS-1464R at 24 A with two 20 A 2-pole breakers; the PX3TS-1469 series at 32 A with two 16 A 1-pole breakers; all with 16 C13 and 4 C19.
  8. Operating temperature certification is 60 °C (UL) and 50 °C (CE) at 85% relative humidity; the unit is fanless.
  9. Security and protocols: AES128, SSH, SNMPv3, TLS, FIPS 140-2; management over SNMP, Modbus, JSON-RPC, IPv4 and IPv6.

Using it in design

  • In racks holding single-corded devices, land the A and B feeds on a rack transfer switch and check the device load against the 16 A limit for 1U or the 24 A or 32 A limit for 2U.
  • Compare the 4 to 8 ms transfer time with the power-supply hold-up time of the connected devices; the 8 to 16 ms of a relay ATS leaves less margin in the same check.
  • Select the model by matching the plug type (IEC C20, IEC 60309 16 A or 32 A, NEMA L6-20P, L6-30P, Clipsal) to the upstream socket and breaker ratings.
  • Reflect the blocked transfer on an output short circuit in the A/B failure scenarios: the load is lost, and the other feed stays protected.
  • Allow for the 1U or 2U height and the full-depth chassis in the rack layout, and check hot-aisle ambient temperature against the 50 °C (CE) limit.

Who should read it

Electrical engineers designing rack power distribution, and operations teams connecting single-corded network and storage devices to redundant feeds.

Document contents

  1. A cost-effective reliable load transfer switch
  2. Most reliable power for single-corded devices
  3. Embedded with Xerus technology platform, for configurable monitoring, control, and alerting
  4. Performance features
  5. Most transfer switches on the market fall short of expectations: electromechanical relay switches (ATS), silicon-controlled rectifier switches (STS)
  6. Here's how Raritan's is different: hybrid design
  7. Smart controller enables remote monitoring and management
  8. PDView: integrated tablet display via USB port
  9. Web-based remote power monitoring
  10. Model table

Publication details

Authors
Raritan (Legrand)
Publisher
Raritan (Legrand)
Year
2016
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Raritan (Legrand) (2016). Raritan intelligent rack transfer switch datasheet (2016). Raritan (Legrand). https://www.raritan.com/assets/re/resources/data_sheets/RE-ds-RTS.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.