Raritan intelligent rack transfer switch datasheet (2016)
Raritan (Legrand)
Raritan's (Legrand) 2016 PX3TS datasheet presents a hybrid rack transfer switch that combines relays with SCRs: it moves a load between two sources in 4 to 8 ms and lists 13 models from 1U 16 A to 2U 32 A.
On this page
Overview
The document is the three-page datasheet for the PX3TS family, a rack-mounted transfer switch that connects single-corded IT devices to two separate feeds. Raritan positions the product as a hybrid design that puts electromechanical relays and silicon-controlled rectifiers (SCRs) in the same circuit. The stated aim is a unit that is faster and more dependable than relay-only automatic transfer switches (ATS), and cheaper and cooler-running than all-semiconductor static transfer switches (STS). The unit has no fans.
The datasheet compares the three technologies by transfer time. Relay-based ATS units are quoted at 8 to 16 ms depending on vendor, SCR-based STS units at normally 4 to 6 ms, and the Raritan hybrid at 4 to 8 ms. For relay-based units, contact welding caused by arcing is named as a leading failure cause; because such units do not report a welded contact, the fault only shows when an outage occurs and no switchover follows. For STS units the sheet cites a cost more than five and a half times that of electromechanical switches, higher energy draw and a need for forced cooling.
Protection and monitoring form the second main theme. The relays are oversized at a 70 A rating, the fast-blow fuses are field replaceable, and the unit detects an output short circuit and blocks the transfer so the fault does not cascade onto the second feed. Transfers between out-of-phase sources are supported. Metering accuracy is given as billing grade at ±1%, and the 5000 series adds outlet-level metering and switching. The Xerus firmware provides SNMP, Modbus, JSON-RPC, email, syslog and GSM text alerts, and records the AC waveform of the last transfer.
The final part is the model table: chassis height, input voltage, plug type, outlet type and quantity, current, circuit-breaker quantity and Ethernet are listed for 13 models. The 1U models carry 16 A (20 A on the Clipsal-plug models) with 7 or 8 C13 outlets and 1 C19; the 2U models offer 16 C13 and 4 C19 outlets at 24 A or 32 A. The operating environment is certified to 60 °C under UL and 50 °C under CE at 85% relative humidity. The document is a product sheet; it gives no test conditions for the transfer times and no numeric efficiency values.
Key points
- The hybrid relay-plus-SCR design transfers a load in 4 to 8 ms; the sheet gives 8 to 16 ms for relay ATS units and normally 4 to 6 ms for SCR STS units.
- STS units are described as more than five and a half times the cost of electromechanical switches, drawing more energy and needing forced cooling.
- The relays are rated 70 A, and the anti-arcing circuit is designed to prevent contact welding.
- An output short circuit blocks the transfer and raises an alarm, so the fault is not carried onto the second feed.
- Power metering accuracy is ±1%; the PX3TS-5000 series has outlet-level metering and switching.
- 1U models: 16 A or 20 A, 7 or 8 C13 plus 1 C19 (8 NEMA 5-20R on the 120 V model), no circuit breakers.
- 2U models: PX3TS-1464R at 24 A with two 20 A 2-pole breakers; the PX3TS-1469 series at 32 A with two 16 A 1-pole breakers; all with 16 C13 and 4 C19.
- Operating temperature certification is 60 °C (UL) and 50 °C (CE) at 85% relative humidity; the unit is fanless.
- Security and protocols: AES128, SSH, SNMPv3, TLS, FIPS 140-2; management over SNMP, Modbus, JSON-RPC, IPv4 and IPv6.
Using it in design
- In racks holding single-corded devices, land the A and B feeds on a rack transfer switch and check the device load against the 16 A limit for 1U or the 24 A or 32 A limit for 2U.
- Compare the 4 to 8 ms transfer time with the power-supply hold-up time of the connected devices; the 8 to 16 ms of a relay ATS leaves less margin in the same check.
- Select the model by matching the plug type (IEC C20, IEC 60309 16 A or 32 A, NEMA L6-20P, L6-30P, Clipsal) to the upstream socket and breaker ratings.
- Reflect the blocked transfer on an output short circuit in the A/B failure scenarios: the load is lost, and the other feed stays protected.
- Allow for the 1U or 2U height and the full-depth chassis in the rack layout, and check hot-aisle ambient temperature against the 50 °C (CE) limit.
Who should read it
Electrical engineers designing rack power distribution, and operations teams connecting single-corded network and storage devices to redundant feeds.
Document contents
- A cost-effective reliable load transfer switch
- Most reliable power for single-corded devices
- Embedded with Xerus technology platform, for configurable monitoring, control, and alerting
- Performance features
- Most transfer switches on the market fall short of expectations: electromechanical relay switches (ATS), silicon-controlled rectifier switches (STS)
- Here's how Raritan's is different: hybrid design
- Smart controller enables remote monitoring and management
- PDView: integrated tablet display via USB port
- Web-based remote power monitoring
- Model table
Publication details
- Authors
- Raritan (Legrand)
- Publisher
- Raritan (Legrand)
- Year
- 2016
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Raritan (Legrand) (2016). Raritan intelligent rack transfer switch datasheet (2016). Raritan (Legrand). https://www.raritan.com/assets/re/resources/data_sheets/RE-ds-RTS.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.