Aunilec HELIOS-TH 10-100 kVA Three-Phase Modular UPS
Original title Aunilec HELIOS-TH brochure, technical table p.4 (image verified)
Aunilec
Aunilec HELIOS-TH is a 10-100 kVA three-level double-conversion modular UPS with 10 or 20 kVA modules, N+1 redundancy, VFI-SS-111 and 95.5% efficiency in normal mode and 99% in ECO mode.
On this page
Overview
The brochure presents the HELIOS-TH as a modular double-conversion UPS with three-phase input and output and three-level converter technology. Four cabinet configurations are given: 10-30 kVA (10 kVA modules, 3 slots), 10-50 kVA (10 kVA, 5 slots), 20-60 kVA (20 kVA, 3 slots) and 20-100 kVA (20 kVA, 5 slots). For N+1 redundancy one extra module is needed above the desired output power. Cabinets measure 1200 x 600 x 850 mm and 1400 x 600 x 850 mm.
Features: input power factor 1, VFI-SS-111 class, ECO mode switching, hot-swappable power modules, front-replaceable fans and filters, a redundant parallel control unit and N+X parallel operation of up to 4 systems. The Power Walk In function starts the rectifier gradually and avoids inrush peaks on the supply; Inter Power Walk In starts several UPS units in sequence. An intelligent standby mode deactivates modules at low load to raise efficiency.
Technical data: input 380/400/415 Vac, 138-485 Vac, 40-70 Hz, THDi below 3% (100% non-linear load), output regulation ±1%, efficiency 95.5% in normal mode and 99% in ECO mode. Battery ±180 to ±300 Vdc (30-50 blocks), charge current 18 A per module, recharge from 5 hours. Overload goes to bypass after 60 min at 105-110%, 10 min at 110-125% and 1 min at 125-150%; above 150% it shuts down at once. Operation is 0-40 °C (recommended +15 to +25 °C), noise below 58-61 dB, warranty 5 or 10 years depending on battery type.
Key points
- Power ranges: 10-30, 10-50, 20-60 and 20-100 kVA/kW; 10 or 20 kVA modules.
- VFI-SS-111; output PF 1; 95.5% efficiency in normal mode, 99% in ECO mode.
- N+1 needs one extra module above the output power; up to 4 systems N+X in parallel.
- Input 380/400/415 Vac, 138-485 Vac, 40-70 Hz; THDi <3%.
- Battery ±180 to ±300 Vdc (30-50 blocks), 18 A charging per module.
- Overload: 105-110% 60 min, 110-125% 10 min, 125-150% 1 min then bypass; >150% shutdown.
- Cabinet 1200 x 600 x 850 mm or 1400 x 600 x 850 mm; about 150 and 180 kg without batteries.
- Module weight about 21 kg; 0-40 °C, IP20, EN 62040-1, -2, -3.
Using it in design
- Choose the module count so one spare module remains for N+1, and record the 100 kVA cabinet ceiling in the growth plan.
- Set Power Walk In together with generator load acceptance on generator-fed systems.
- Calculate battery block count and charge current (18 A per module) against autonomy and recharge targets.
- When selecting on ECO efficiency, account for the changed protection class in that mode.
- Use the 150-180 kg cabinet weight and the 1200/1400 mm height for floor loading and layout.
Who should read it
Electrical designers selecting scalable three-phase UPS units for data-centre and industrial sites.
Document contents
- Modular UPS and efficiency
- Service concept
- Redundant power modules and Power Walk In
- Connections
- Redundant and scalable cabinets
- Features and technical data
Publication details
- Authors
- Aunilec
- Publisher
- Aunilec
- Year
- Year not stated
- Document language
- French
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Aunilec Aunilec HELIOS-TH brochure, technical table p.4 (image verified). Aunilec. https://onduleurs-aunilec.com/gb/index.php?controller=attachment&id_attachment=200
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.