Aunilec HELIOS-RM 10-50 kVA Three-Phase Modular UPS

Original title Aunilec HELIOS-RM 10–50 kVA brochure, table p.4 (image verified)

Aunilec

Aunilec HELIOS-RM is a 10-50 kVA (kW = kVA) 19-inch rack three-phase on-line double-conversion UPS: VFI-SS-111, efficiency above 95.5%, up to 4 units in parallel and zero transfer time.

On this page

Overview

The brochure presents the HELIOS-RM range in 10, 15, 20, 25, 30, 40 and 50 kVA/kW models. The series is VFI-SS-111 under IEC 62040-3, with output power factor 1 and a compact on-line double-conversion design that fits a 19-inch rack cabinet. The UPS, the connection unit and the batteries are each 3U high. The maker states efficiency above 95.5% and supports redundant parallel operation of up to 4 systems.

The technical table gives input 380/400/415 Vac (3Ph+N+PE), 138-485 Vac, 40-70 Hz, input power factor 0.99 and THDi below 3%. Output regulation is ±1%, THD 2% on linear and 4% on non-linear load. Battery voltage is ±180 to ±300 Vdc (30-50 blocks of 12 V selectable), maximum charge current 18-20 A, and transfer time is 0 ms on both battery and bypass. Overload is 110% for 60 min, 125% for 10 min and 150% for 1 min.

Physical and environmental data: 670 x 440 x 130 mm (3U) for 10-30 kVA and 800 x 440 x 175 mm (4U) for 40-50 kVA; operation 0-40 °C, humidity to 95% non-condensing, nominal power below 1500 m with derating above, noise below 55-58 dB. Standards are IEC/EN 62040-1 and -3. Cold start, backfeed protection, built-in EPO, RS232/USB/RS485, dry contacts, an optional SNMP card and a 7-inch remote display are provided.

Key points

  1. Models: 10, 15, 20, 25, 30, 40, 50 kVA/kW; VFI-SS-111; output PF 1.
  2. Efficiency above 95.5%; up to 4 units in parallel.
  3. Input 380/400/415 Vac, 138-485 Vac, 40-70 Hz; input PF 0.99; THDi <3%.
  4. Output regulation ±1%; THD 2% (linear), 4% (non-linear).
  5. Battery ±180 to ±300 Vdc (30-50 blocks); charge current up to 18-20 A; transfer 0 ms.
  6. Overload: 110% 60 min, 125% 10 min, 150% 1 min.
  7. 10-30 kVA: 670 x 440 x 130 mm (3U); 40-50 kVA: 800 x 440 x 175 mm (4U).
  8. 0-40 °C; derating above 1500 m; IEC/EN 62040-1, -3.

Using it in design

  • When planning the rack UPS in a 19-inch cabinet, count the 3U heights of the UPS, connection unit and battery module separately.
  • Limit paralleling for redundancy to 4 units.
  • Select battery block count (30-50) together with the power derating conditions.
  • Use input PF 0.99 and THDi <3% in generator sizing.
  • Integrate the backfeed protection contact and the EPO input with the fire alarm.

Who should read it

Designers selecting rack-mount three-phase UPS units for small data rooms and edge sites.

Document contents

  1. Description
  2. Detailed views and 19-inch installation
  3. Connection overview
  4. Parallel option
  5. Technical data

Publication details

Authors
Aunilec
Publisher
Aunilec
Year
Year not stated
Document language
French
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Aunilec Aunilec HELIOS-RM 10–50 kVA brochure, table p.4 (image verified). Aunilec. https://onduleurs-aunilec.com/gb/index.php?controller=attachment&id_attachment=233

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.