Aunilec HELIOS-RM 10-50 kVA Three-Phase Modular UPS
Original title Aunilec HELIOS-RM 10–50 kVA brochure, table p.4 (image verified)
Aunilec
Aunilec HELIOS-RM is a 10-50 kVA (kW = kVA) 19-inch rack three-phase on-line double-conversion UPS: VFI-SS-111, efficiency above 95.5%, up to 4 units in parallel and zero transfer time.
On this page
Overview
The brochure presents the HELIOS-RM range in 10, 15, 20, 25, 30, 40 and 50 kVA/kW models. The series is VFI-SS-111 under IEC 62040-3, with output power factor 1 and a compact on-line double-conversion design that fits a 19-inch rack cabinet. The UPS, the connection unit and the batteries are each 3U high. The maker states efficiency above 95.5% and supports redundant parallel operation of up to 4 systems.
The technical table gives input 380/400/415 Vac (3Ph+N+PE), 138-485 Vac, 40-70 Hz, input power factor 0.99 and THDi below 3%. Output regulation is ±1%, THD 2% on linear and 4% on non-linear load. Battery voltage is ±180 to ±300 Vdc (30-50 blocks of 12 V selectable), maximum charge current 18-20 A, and transfer time is 0 ms on both battery and bypass. Overload is 110% for 60 min, 125% for 10 min and 150% for 1 min.
Physical and environmental data: 670 x 440 x 130 mm (3U) for 10-30 kVA and 800 x 440 x 175 mm (4U) for 40-50 kVA; operation 0-40 °C, humidity to 95% non-condensing, nominal power below 1500 m with derating above, noise below 55-58 dB. Standards are IEC/EN 62040-1 and -3. Cold start, backfeed protection, built-in EPO, RS232/USB/RS485, dry contacts, an optional SNMP card and a 7-inch remote display are provided.
Key points
- Models: 10, 15, 20, 25, 30, 40, 50 kVA/kW; VFI-SS-111; output PF 1.
- Efficiency above 95.5%; up to 4 units in parallel.
- Input 380/400/415 Vac, 138-485 Vac, 40-70 Hz; input PF 0.99; THDi <3%.
- Output regulation ±1%; THD 2% (linear), 4% (non-linear).
- Battery ±180 to ±300 Vdc (30-50 blocks); charge current up to 18-20 A; transfer 0 ms.
- Overload: 110% 60 min, 125% 10 min, 150% 1 min.
- 10-30 kVA: 670 x 440 x 130 mm (3U); 40-50 kVA: 800 x 440 x 175 mm (4U).
- 0-40 °C; derating above 1500 m; IEC/EN 62040-1, -3.
Using it in design
- When planning the rack UPS in a 19-inch cabinet, count the 3U heights of the UPS, connection unit and battery module separately.
- Limit paralleling for redundancy to 4 units.
- Select battery block count (30-50) together with the power derating conditions.
- Use input PF 0.99 and THDi <3% in generator sizing.
- Integrate the backfeed protection contact and the EPO input with the fire alarm.
Who should read it
Designers selecting rack-mount three-phase UPS units for small data rooms and edge sites.
Document contents
- Description
- Detailed views and 19-inch installation
- Connection overview
- Parallel option
- Technical data
Publication details
- Authors
- Aunilec
- Publisher
- Aunilec
- Year
- Year not stated
- Document language
- French
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Aunilec Aunilec HELIOS-RM 10–50 kVA brochure, table p.4 (image verified). Aunilec. https://onduleurs-aunilec.com/gb/index.php?controller=attachment&id_attachment=233
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.