East Penn Deka HRC700C technical flyer: p.1
East Penn Manufacturing
East Penn Deka HRC700C high-rate 12 V UPS battery: 670, 476 and 370 W per cell at 5, 10 and 15 minutes to 1.67 V/cell at 25 C; 28 kg, 10-year float design life.
On this page
Overview
East Penn Manufacturing's Deka HRC700C technical flyer (E.P.M. Form No. 2890) presents a 12 V monobloc battery for high-rate UPS applications. The battery uses Armor Alloy power-protected lead technology, Compu-Press grid construction, micro-porous glass mat separators and a flame-arresting safety vent. The rating is 670 watts per cell at the 5-minute rate to 1.67 V per cell.
The discharge table lists watts per cell at 25 C for end voltages of 1.60, 1.63, 1.65, 1.67, 1.70 and 1.75 V per cell, from 1 to 60 minutes. At 1.67 V per cell the values are 1006 W at 1 min, 670 at 5 min, 476 at 10 min, 370 at 15 min and 123 at 60 min. At 1.75 V per cell the 5-minute value is 596 W and at 1.60 V per cell 715 W, so a lower end voltage gives more power.
Float voltage is 13.50 V per battery +/-0.5% at 25 C (range 13.42-13.57 V), and design life is 10 years in float service at 25 C. Dimensions are 12.01 x 6.56 x 8.23 in (305.2 x 166.7 x 209.0 mm) and weight 62 lb (28 kg). The terminal is a top-access 1/4-20 threaded insert; case and cover are UL94 V0 flame-retardant polypropylene.
The flyer also states guaranteed 100% initial string capacity when tested to IEEE 1188, UL 1973 certification for energy storage and an optional factory acceptance test. The factory test is a constant-power discharge at the 10-minute rate to 1.67 V per cell; the string must deliver 100% or more and individual batteries 95% or more of capacity.
Key points
- Rating: 670 W per cell at 5 min to 1.67 V/cell (25 C).
- At 1.67 V/cell: 1 min 1006, 10 min 476, 15 min 370, 60 min 123 W/cell.
- Nominal voltage 12 V; Armor Alloy positive and negative plates.
- Float voltage 13.50 V +/-0.5% (25 C); range 13.42-13.57 V.
- Design life 10 years (float, 25 C).
- Dimensions 305.2 x 166.7 x 209.0 mm; weight 28 kg (62 lb).
- Guaranteed 100% initial string capacity per IEEE 1188; UL 1973 certified.
- Case and cover UL94 V0, per UL1778 requirements; epoxy-sealed posts.
Using it in design
- Select the UPS battery string from the watts-per-cell table: set target autonomy (for example 10 or 15 min), end voltage and load power (including efficiency) together.
- Set cell count and DC bus voltage consistent with the float voltage (13.50 V per battery) and use 25 C as the temperature-compensation reference.
- Carry weight and dimensions into battery rack and floor-loading calculations.
- Reflect the 10-year design life (25 C) and shorter life at higher temperature in the replacement plan.
- Add the optional factory test and an IEEE 1188 field test to the acceptance specification.
Who should read it
Electrical designers sizing UPS battery strings and engineers writing specifications.
Document contents
- Features and benefits
- Specifications
- Discharge ratings (W/cell)
- Dimension drawing
- Optional factory acceptance testing
Publication details
- Authors
- East Penn Manufacturing
- Publisher
- East Penn Manufacturing
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
East Penn Manufacturing East Penn Deka HRC700C technical flyer: p.1. East Penn Manufacturing. https://www.eastpennmanufacturing.com/wp-content/uploads/2890-HRC700C-UnigyHighRateHRC.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
