East Penn Deka HRC950C technical flyer: p.1

East Penn Manufacturing

East Penn Deka HRC950C high-rate 12 V UPS battery: 930, 712 and 578 W per cell at 5, 10 and 15 minutes to 1.67 V/cell at 25 C; 42 kg, 10-year float design life.

On this page

Overview

East Penn Manufacturing's Deka HRC950C technical flyer (E.P.M. Form No. 2830) presents a 12 V monobloc battery for high-rate UPS applications. The battery uses Armor Alloy power-protected lead technology, Compu-Press grid construction, micro-porous glass mat separators and a flame-arresting safety vent. The rating is 930 watts per cell at the 5-minute rate to 1.67 V per cell.

The discharge table lists watts per cell at 25 C for end voltages of 1.60, 1.63, 1.65, 1.67, 1.70 and 1.75 V per cell, from 1 to 60 minutes. At 1.67 V per cell the values are 1244 W at 1 min, 930 at 5 min, 712 at 10 min, 578 at 15 min and 216 at 60 min. At 1.75 V per cell the 5-minute value is 814 W and at 1.60 V per cell 1008 W, so a lower end voltage gives more power.

Float voltage is 13.50 V per battery +/-0.5% at 25 C (range 13.42-13.57 V), and design life is 10 years in float service at 25 C. Dimensions are 13.46 x 6.84 x 11.21 in (341.9 x 173.7 x 284.7 mm) and weight 93 lb (42 kg). The terminal is a top-access 1/4-20 threaded insert; case and cover are UL94 V0 flame-retardant polypropylene.

The flyer also states guaranteed 100% initial string capacity when tested to IEEE 1188, UL 1973 certification for energy storage and an optional factory acceptance test. The factory test is a constant-power discharge at the 10-minute rate to 1.67 V per cell; the string must deliver 100% or more and individual batteries 95% or more of capacity.

Key points

  1. Rating: 930 W per cell at 5 min to 1.67 V/cell (25 C).
  2. At 1.67 V/cell: 1 min 1244, 10 min 712, 15 min 578, 60 min 216 W/cell.
  3. Nominal voltage 12 V; Armor Alloy positive and negative plates.
  4. Float voltage 13.50 V +/-0.5% (25 C); range 13.42-13.57 V.
  5. Design life 10 years (float, 25 C).
  6. Dimensions 341.9 x 173.7 x 284.7 mm; weight 42 kg (93 lb).
  7. Guaranteed 100% initial string capacity per IEEE 1188; UL 1973 certified.
  8. Case and cover UL94 V0, per UL1778 requirements; epoxy-sealed posts.

Using it in design

  • Select the UPS battery string from the watts-per-cell table: set target autonomy (for example 10 or 15 min), end voltage and load power (including efficiency) together.
  • Set cell count and DC bus voltage consistent with the float voltage (13.50 V per battery) and use 25 C as the temperature-compensation reference.
  • Carry weight and dimensions into battery rack and floor-loading calculations.
  • Reflect the 10-year design life (25 C) and shorter life at higher temperature in the replacement plan.
  • Add the optional factory test and an IEEE 1188 field test to the acceptance specification.

Who should read it

Electrical designers sizing UPS battery strings and engineers writing specifications.

Document contents

  1. Features and benefits
  2. Specifications
  3. Discharge ratings (W/cell)
  4. Dimension drawing
  5. Optional factory acceptance testing

Publication details

Authors
East Penn Manufacturing
Publisher
East Penn Manufacturing
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

East Penn Manufacturing East Penn Deka HRC950C technical flyer: p.1. East Penn Manufacturing. https://www.eastpennmanufacturing.com/wp-content/uploads/Deka-HRC950C-2830.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.