Technical guideFree to readYear not stated

Eternity Technologies OGi Bloc Battery: ET/NP OGi BLOC V4 0525, p.3

Eternity Technologies

Eternity Technologies OGi Bloc is a family of 12 discrete flooded deep-cycle lead-acid bloc batteries to DIN 40739, 25-300 Ah (C10 to 1.8 V/cell at 20 C).

On this page

Overview

Eternity Technologies' May 2025 brochure presents the OGi Bloc family for renewable energy, railway, UPS and telecom use. The units are vented (flooded) lead-acid blocs built with a low-antimony flat positive plate, acid density of 1.24 kg/l, an ABS lid and a SAN container. The design follows DIN 40739 and is stated to comply with IEC 60896-11 and EN 50272-2.

The table lists 12 models: six 12 V blocs (ET 12V 1 OGI 25 to 6 OGI 150, 25-150 Ah) and six 6 V blocs (7 OGI 175 to 12 OGI 300, 175-300 Ah). Each row gives C10 capacity to 1.8 V/cell at 20 C, length, width, H1 (over lid) and H2 (including ceramic plug) height, filled weight, internal resistance, short-circuit current and C5, C3 and C1 capacities (to 1.75 V/cell). All models have M10 threaded terminals with 23 Nm torque.

For life and maintenance the brochure quotes a design life of over 12 years (EUROBAT Long Life), topping-up intervals of up to 3 years in float, more than 1000 cycles at 80% depth of discharge, and self-discharge of roughly 3% per month at 20 C. These are manufacturer statements and do not give a runtime for a given load profile.

Dimensions carry a +/-5% weight tolerance, and 6 V blocs are made in type A and type B versions. Cabinet energy and the load-time relationship are not given in the brochure and must be calculated separately from the number of blocs and the discharge conditions. As a vented battery, hydrogen ventilation and watering access enter the layout decisions.

Key points

  1. 12 models: six 12 V (25, 50, 75, 100, 125, 150 Ah) and six 6 V (175, 200, 225, 250, 275, 300 Ah), C10 capacity at 1.8 V/cell and 20 C.
  2. Example: ET 12V 4 OGI 100 has a weight of 53.65 kg, internal resistance of 4.46 mOhm and short-circuit current of 2810 A.
  3. The largest model, ET 6V 12 OGI 300, is 300 Ah, 70.11 kg, 8440 A short-circuit current, with C1 capacity of 194.4 Ah (to 1.75 V/cell).
  4. Dimensions: 272 or 380 mm length, 205 mm width, H1 349 mm, H2 400 mm; H2 includes the ceramic plug.
  5. Design life is over 12 years per EUROBAT; more than 1000 cycles at 80% DoD; self-discharge roughly 3% per month (20 C).
  6. Topping-up interval is up to 3 years in float; low-antimony alloy and large electrolyte volume.
  7. Terminals are M10 threaded with 23 Nm torque; weight tolerance is +/-5%.
  8. Compliance: DIN 40739 design, IEC 60896-11 and EN 50272-2.

Using it in design

  • Select capacity from the C5, C3 or C1 column matching the target runtime with a 1.75 V/cell end voltage, not from the C10 figure.
  • Feed the short-circuit current (for example 720-8440 A) and internal resistance into DC protection and cable selectivity calculations.
  • Set rack height from H2 (400 mm, ceramic plug included) plus watering access space, and confirm the type A or B version of 6 V blocs against terminal layout.
  • Include hydrogen ventilation and EN 50272-2 requirements in the battery room design for a vented battery.
  • Add the weight (a 32-75 kg band) to floor-loading and rack-capacity calculations.

Who should read it

Electrical engineers designing battery rooms and DC systems, and teams writing UPS battery specifications.

Document contents

  1. OGi Bloc technology
  2. Features and applications
  3. OGi Bloc cell specification

Publication details

Authors
Eternity Technologies
Publisher
Eternity Technologies
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Eternity Technologies Eternity Technologies OGi Bloc Battery: ET/NP OGi BLOC V4 0525, p.3. Eternity Technologies. https://eternitytechnologies.com/wp-content/uploads/2021/05/NP-OGi-BLOC-BATTERY-FAMILY-BROCHURE-lo-res-06.05.25.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.