Eternity QUASAR Top Terminal VRLA Battery: ET/NP QUASAR STANDBY BLOC V1 1025, p.2

Eternity Technologies

Eternity Technologies QUASAR is a carbon-nanotube VRLA top-terminal bloc family to IEC 60896-21/22 with 11 models: 6 V at 176-282 Ah and 12 V at 53-181 Ah (C8 to 1.75 V/cell).

On this page

Overview

Eternity Technologies' QUASAR brochure presents 6 and 12 V top-terminal gel-electrolyte VRLA monoblocs for UPS, telecom, data-centre, emergency and utility applications. The manufacturer states that the plates use a lead-calcium-tin alloy, the electrolyte is silica-based gel, and a patented carbon nanotube (CNT) solution is used; CNT is said to improve charge acceptance, cycle life and partial state of charge (PSOC) operation.

The table gives 11 models: four 6 V (EQ-6V195, 6V200, 6V260, 6V310) and seven 12 V (EQ-12V60, 12V75, 12V80, 12V90, 12V100, 12V150, 12V200). Each row lists C8 (1.75 V/cell) and C10 (1.80 V/cell) capacity at 20 C, length, width, height, weight, layout (A-E), short-circuit current, internal resistance and terminal type (M6, M8, M10). For example the EQ-6V310 has a C8 capacity of 282 Ah, weight of 53 kg, short-circuit current of 3354.3 A and internal resistance of 1.85 mOhm.

The brochure states a design life of over 12 years on the EUROBAT 2015 classification (very long life), design to IEC 60896-21/22, ISO 9001 and ISO 50001 certified production, and unrestricted transport by most rail, road, sea and air routes (IATA DGR A67). A V0 suffix on the part number selects UL-94 V0 flame-retardant plastic.

Capacities are given under two test conditions (C8 and C10), so models must be compared within the same column. Weight tolerance is +/-5%, and the 12V150 and 12V200 have reverse polarity. Cabinet energy and the load-time relationship are not in the document and are calculated separately.

Key points

  1. 11 models: four 6 V (EQ-6V195, 6V200, 6V260, 6V310) and seven 12 V (EQ-12V60, 12V75, 12V80, 12V90, 12V100, 12V150, 12V200).
  2. C8 capacity (1.75 V/cell, 20 C) is 176-282 Ah for 6 V models and 53-181 Ah for 12 V models; C10 (1.80 V/cell) is 189-302 Ah and 58-194 Ah.
  3. EQ-6V195: 33 kg, 2.36 mOhm internal resistance, 2635 A short-circuit current; EQ-12V200: 62 kg, 2.95 mOhm, 4225 A.
  4. Lowest internal resistance is 1.85 mOhm (EQ-6V310); highest is 9.70 mOhm (EQ-12V60).
  5. Terminal types are M6 (6 Nm), M8 (8 Nm) and M10 (16 Nm) with the stated torques.
  6. Design life is over 12 years on EUROBAT 2015; design to IEC 60896-21/22.
  7. CNT technology is claimed to give high charge acceptance, long cycle life, PSOC operation and an improved thermal operating range.
  8. Transport is unrestricted under IATA DGR A67; a V0 suffix selects UL-94 V0 plastic; the 12V150 and 12V200 have reverse polarity.

Using it in design

  • When choosing capacity from the C8 (1.75 V/cell) or C10 (1.80 V/cell) column, use the same column for all candidates and request the discharge table for the target runtime from the manufacturer.
  • Feed the short-circuit current and internal resistance columns into DC protection, fuse and cable selectivity calculations.
  • In rack layout, check terminal type and torque as well as length, width and height, and verify the wiring diagram for the reverse-polarity models.
  • Add the bloc weight (a 19.5-62 kg band) to floor-loading and rack-capacity calculations.
  • If the fire code requires flame retardancy, specify the V0 plastic option.

Who should read it

Electrical designers and specification writers selecting batteries for UPS and DC power systems.

Document contents

  1. QUASAR top terminal VRLA battery
  2. Carbon nanotube technology
  3. Features and applications
  4. Battery specifications
  5. Terminals and layouts

Publication details

Authors
Eternity Technologies
Publisher
Eternity Technologies
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Eternity Technologies Eternity QUASAR Top Terminal VRLA Battery: ET/NP QUASAR STANDBY BLOC V1 1025, p.2. Eternity Technologies. https://eternitytechnologies.com/wp-content/uploads/2025/11/QUASAR-TOP-TERMINAL-RESERVE-POWER-BROCHURE-25.11.25.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.