SIEL Exchange - MTR static transfer switch technical data sheet

Original title SIEL Exchange–MTR static transfer switch datasheet

SIEL

SIEL's MTR (16-32 A single-phase) and Exchange (63-1600 A three-phase) static transfer switches: break-before-make transfer, efficiency above 99%, 125% overload for 10 minutes.

On this page

Overview

The document is a bilingual (Italian and English) technical data sheet introducing SIEL's static transfer switch (STS) family. An STS moves the load from one power source to another without an interruption of supply. The single-phase MTR comes in 16 A and 32 A, while the three-phase Exchange is offered from 63 A up to 1600 A in 3-pole or 4-pole versions.

On the input side the nominal voltage is 230 V (+7%/-20%) or 400 V (+20%/-35%), and the nominal frequency is 50/60 Hz +/-5%. The phase arrangement is single phase plus neutral or three phase plus neutral. Output efficiency is above 99%, the transfer mode is break before make, and the neutral is sized at 1.5 In. The running mode is selectable: fixed priority or no priority.

Overload capability is 125% for 10 minutes, 150% for 1 minute and 200% for 10 seconds. Electromagnetic compatibility is Class A under IEC EN 62040-2 and the operating temperature is 0-40 °C. The listed standards are CE, IEC EN 62310 and IEC EN 62040-2.

The MTR offers hot-swappable power electronics, an integrated standard manual bypass, 19-inch rack mounting and RS232 with free contacts. The Exchange integrates input, output and manual bypass breakers, with a chassis version on request. Communication options are an LED synoptic, RS232, RS485, Modbus, TeleGlobal Service and optional SNMP.

Key points

  1. MTR: single phase, 16 and 32 A; Exchange: three phase, 63 A to 1600 A, 3 or 4 poles.
  2. Nominal input 230 V (+7%/-20%) or 400 V (+20%/-35%), 50/60 Hz +/-5%.
  3. Efficiency above 99%; transfer mode is break before make.
  4. Overload: 10 min 125%, 1 min 150%, 10 s 200%.
  5. Neutral sized at 1.5 In; operating temperature 0-40 °C.
  6. Standards: CE, IEC EN 62310, IEC EN 62040-2 (Class A EMC).
  7. Running mode: fixed priority or no priority, selectable.
  8. MTR: hot-swappable electronics, 19-inch rack, integrated manual bypass.

Using it in design

  • In an A/B dual-feed design, select the STS current against the load current and the 125% / 10 min overload limit; use the MTR for rack loads below 63 A and the Exchange for larger distribution.
  • For transfer-sensitive loads, compare the break-before-make behaviour with the load voltage tolerance and obtain the transfer time from the manufacturer.
  • Size the neutral conductor to the 1.5 In rating and check neutral current with non-linear loads.
  • Confirm in the layout that the integrated manual bypass and breakers are accessible on site for maintenance.
  • Add the Modbus/SNMP/RS485 interface to the BMS or DCIM integration plan.

Who should read it

Electrical engineers designing dual-feed power distribution and UPS integrators selecting STS equipment.

Document contents

  1. Input parameters
  2. Output parameters
  3. General features (MTR and Exchange)
  4. Mechanical characteristics
  5. Communication interfaces
  6. Standards

Publication details

Authors
SIEL
Publisher
SIEL
Year
Year not stated
Document language
Multilingual
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

SIEL SIEL Exchange–MTR static transfer switch datasheet. SIEL. https://www.shanahanpower.com/wp-content/uploads/2022/12/SIEL-Exchange-MTR-Datasheet.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.