Rehlko PW9250DPA configured cabinet physical specification

Rehlko

Rehlko's technical specification for the PW9250DPA cabinet built from modular 50 kW UPS modules, giving capacity tables, physical dimensions, mass, input-output and efficiency data.

On this page

Overview

The PW9250DPA is a three-phase UPS family with a decentralised parallel architecture (DPA) in which a standard cabinet takes up to six 50 kW UPS modules. Modules sit on shelf runners on the cabinet side walls and plug into power sockets at the back. With six modules the cabinet is a 300 kW (N+0) or 250 kW (N+1) system. Redundancy depends on load: a three-module (150 kW) cabinet works as a capacity system for loads of 100-150 kW and as N+1 for loads below 100 kW.

Up to five cabinets can be paralleled for a total capacity of up to 1500 kW; by design a parallel system can hold at most 30 modules. Modules are hot-swappable, so capacity can be increased in a partly populated cabinet without interrupting the load. Adding a new cabinet, however, requires the load to be shut down or moved to an external maintenance bypass, so the specification recommends allowing enough cabinets in the initial design. Example: for an N+1 system whose load grows from 300 kW to 800 kW, at least seven modules are needed (300 kW N+1) rising to seventeen as the load approaches 800 kW; installing a three-cabinet system from the start lets the modules be distributed between cabinets.

The physical data are gathered in one table: cabinet dimensions height x width x depth are 1978 x 795 x 943 mm, and mass by module count is 345 kg for 1 module, 409 kg for 2, 474 kg for 3, 538 kg for 4, 603 kg for 5 and 667 kg for 6. Acoustic noise at 1 m from the front is below 65 dBA at 50% load and 70 dBA at 100% load; protection is IP20 (IP21 optional), service access from the front, cable entry top or bottom (factory option). Batteries are in a separate cabinet or on a battery rack.

Electrical values: input 380/400/415 V phase-to-phase, 50 or 60 Hz, THDI below 3% at 100% linear load, power factor 0.99; output voltage variation ±1%, output overload 150% for 1 minute, 125% for 10 minutes and 110% continuous. Double-conversion efficiency is 96.9% at full load and 97.4% at 50% load. The document gives the physical data of the 300 kW cabinet as an official table.

Key points

  1. The six-module cabinet is 300 kW (N+0) or 250 kW (N+1); module size 50 kW.
  2. Six-module 300 kW cabinet: 1978 x 795 x 943 mm, 667 kg.
  3. Mass by module count is 345, 409, 474, 538, 603 and 667 kg.
  4. Up to 5 cabinets in parallel, total 1500 kW; at most 30 modules in a parallel system.
  5. Modules are hot-swappable; adding a new cabinet requires load shutdown or an external maintenance bypass.
  6. Acoustic noise at 1 m is below 65 dBA at 50% load and 70 dBA at full load.
  7. Double-conversion efficiency is 96.9% at full load and 97.4% at 50% load.
  8. THDI below 3% at 100% linear load; input power factor 0.99; full power from 0.9 leading to 0.7 lagging load power factor.
  9. Output overload: 150% / 1 min, 125% / 10 min, 110% continuous (40 °C).

Using it in design

  • For floor loading and layout take the cabinet size and mass by module count: 667 kg with six modules, excluding batteries.
  • In a growth scenario install enough cabinets from the start; an extra cabinet needs a load outage or maintenance bypass.
  • Verify the N+1 need by load: the same cabinet can be a capacity or a redundant system depending on load.
  • For acoustic limits compare the 70 dBA (full load, 1 m) value with the hall noise requirement.
  • Draw the recommended front service clearance and the cable entry direction (a factory option) into the floor plan.
  • Plan the battery cabinet or rack next to the UPS cabinet; the separate DC breaker per module can be used in battery string design.

Who should read it

Electrical designers selecting medium-power UPSs, engineers writing specifications and teams planning layouts.

Document contents

  1. System description
  2. Single cabinet system (50-300 kW)
  3. Parallel cabinet system (250-1500 kW)
  4. System expansion
  5. Key features summary
  6. Cabinet construction
  7. General specification: cabinet, input, output, static bypass, efficiency

Publication details

Authors
Rehlko
Publisher
Rehlko
Year
2026
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Rehlko (2026). Rehlko PW9250DPA configured cabinet physical specification. Rehlko. https://www.ups.rehlko.sg/wp-content/uploads/2026/06/Rehlko-PW9250DPA-Tech-Spec.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.