Technical guideFree to readYear not stated

Rehlko PW8000DPA RI technical specification TS_740_05 26 May 2026, pp.3,7-9

Original title Rehlko PW8000DPA RI technical specification TS_740_05 26 May 2026, pp.3,7–9

Rehlko

Rehlko's PW8000DPA RI specification covers a VFI-SS-111 modular UPS built from 10 or 20 kW modules in 20-80 kW frames with DPA paralleling, giving efficiency, input, battery and weight data.

On this page

Overview

The document presents the Rehlko PW8000DPA (RI) as a third-generation, high power density, double-conversion, rack-installable modular UPS. It is classed VFI-SS-111 under IEC 62040-3. Seven frames exist: RI-10, RI-11 and RI-12 (one module, up to 20 kW), RI-20, RI-22 and RI-24 (two modules, 40 kW) and RI-40 (four modules, 80 kW). The letters in the frame name give the number of module and battery rows, and the frames hold internal battery shelves of 40 or 80 12 V 7/9 Ah blocks (160 in the RI-24).

Paralleling uses Decentralized Parallel Architecture (DPA): each module carries its own bypass, processor, control panel and battery configuration, which the document says gives N+x redundancy without a single point of failure. A multi-module frame can start with one module and grow later, and a module can be hot-swapped without moving the load to bypass (depending on redundancy and load). All modules in a parallel system must have equal rating. Modules weigh 18.6 kg (10 kVA) and 21.5 kg (20 kVA) and need two people to lift.

Electrical data: input power factor 0.99 at 100% load, THDi below 4.5% for the 10 kVA module and below 3% for the 20 kVA module. Referenced to 3x400/230 V, the input accepts -20%/+15% below 100% load, -26%/+15% below 80% load and -35%/+15% below 60% load. Static output voltage stability is ±1%, dynamic ±4% and THDv below 1.5% on linear load. Inverter overload is 125% for 10 min and 150% for 60 s. Static bypass transfer is under 1 ms inverter-to-bypass, under 5 ms bypass-to-inverter and under 6 ms to ECO mode.

Efficiency, heat and environment: AC/AC efficiency is 94.5% at 100% load, 95% at 75% and 50%, and 94% at 25% (tolerance ±0.5%); ECO mode reaches 98%. At 100% nonlinear load heat dissipation is 550 W (10 kVA) and 1100 W (20 kVA) per module, airflow 150 m3/h, no-load loss 120/150 W. Operation is 0-40 °C with no derating up to 1000 m; factors at 1500, 2000, 2500 and 3000 m are 0.95, 0.91, 0.86 and 0.82. The revision history shows the VRLA end-of-discharge voltage corrected to 1.65 V per cell.

Key points

  1. VFI-SS-111; modules of 10 kVA/10 kW and 20 kVA/20 kW, frames of 20, 40 and 80 kW (RI-10/11/12, RI-20/22/24, RI-40).
  2. Empty frame weights: RI-10 20 kg, RI-11 40 kg, RI-12 56 kg, RI-20 25 kg, RI-22 66 kg, RI-24 93 kg, RI-40 50 kg; RI-40 with modules and no batteries 124-136 kg.
  3. Module 448 x 132 x 540 mm (3 HU); 10 kVA module 18.6 kg, 20 kVA module 21.5 kg.
  4. Input: 380/400/415 V, 35-70 Hz, PF 0.99, THDi <4.5% (10 kVA) and <3% (20 kVA), Icc 25 kA.
  5. Maximum input current per module 30.4 A (20 kVA, charged battery) and 33.3 A (discharged battery).
  6. AC/AC efficiency 94.5% (100%), 95% (75% and 50%), 94% (25%); ECO mode 98%.
  7. Overload: inverter 125% for 10 min, 150% for 60 s; short-circuit capability bypass 10 x In for 20 ms.
  8. Battery: VRLA 30-50 12 V blocks or NiCd 300-500 cells, charge current 4 A (6 A on request), float 2.26 V/cell.
  9. Operation 0-40 °C, derating above 1000 m (0.95 at 1500 m, 0.82 at 3000 m), noise 55/49 dBA, 20 cm rear clearance.

Using it in design

  • Use frame capacity (20, 40, 80 kW) and the equal-module-rating rule in the growth plan; set N+1 module count from load and module rating.
  • Remember that block count limits output power (for a 20 kW module, 12 kW at 30 blocks up to 20 kW at 48-50 blocks); check autonomy and power targets together.
  • Calculate the cooling load from 550/1100 W heat loss and 150 m3/h airflow per module, and apply the altitude derating factor above 1000 m.
  • Size input protection and cables with the per-module maximum input current (33.3 A with discharged battery) and the 25 kA Icc rating.
  • If ECO mode is used, assess the 6 ms transfer time and 98% efficiency against load sensitivity; mark front access and the 20 cm rear clearance in the layout.

Who should read it

Electrical designers, capacity planners and field engineers writing modular UPS specifications for data rooms and critical facilities.

Document contents

  1. Document control and contacts
  2. System configuration
  3. Advanced design features (hot-swap, input rectifier, battery management, DPA)
  4. UPS construction and modules
  5. General specification: frame mechanical data
  6. Module input and output characteristics
  7. Heat dissipation and efficiency
  8. Environmental characteristics
  9. Battery characteristics
  10. Communication options and standards

Publication details

Authors
Rehlko
Publisher
Rehlko
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Rehlko Rehlko PW8000DPA RI technical specification TS_740_05 26 May 2026, pp.3,7–9. Rehlko. https://www.ups.rehlko.sg/wp-content/uploads/2026/06/Rehlko-PW8000DPA-RI-Tech-Spec.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.