Master Power Technologies PowerSure MRM150/25C Modular UPS Technical Specification
Original title Master Power Technologies MRM150/25C technical specification, pp.1–2
Master Power Technologies
PowerSure MRM150/25C is a rack-mounted double-conversion modular UPS scaling from 25 to 150 kVA/kW with hot-swappable 25 kW modules and 96% efficiency in AC mode.
On this page
Overview
The PowerSure MRM series is presented as a scalable, hot-swappable, online double-conversion rack-mounted modular UPS. Capacity runs from 25 to 150 kVA/kW and the design uses three-level IGBT with full DSP control. The manufacturer positions it as a fit for modern data centres. The sheet is two pages and gives values for the 150 kVA cabinet and the 25 kVA/25 kW power module.
Efficiency is 96% in AC mode, 98% in ECO mode and 95.5% in battery mode. Input is 3-phase plus neutral at 380/400/415 V, 40 to 70 Hz, power factor above 0.99 and THDi below 3%; the input voltage range at full load is 304 to 478 Vac. Output power factor is 1, with THDu below 1% on linear load and below 6% on non-linear load. Inverter overload is 110% for 1 hour, 125% for 10 minutes and 150% for 1 minute.
On the battery side the sheet states ±240 Vdc with 40 batteries (an even number from 32 to 44 is settable), charger power up to 20% of output active power and battery cold start as standard. The cabinet weighs 116 kg and a power module 18 kg. The document is a product sheet; it does not detail module fault behaviour or the redundancy architecture.
Key points
- System capacity 150 kVA, power module 25 kVA / 25 kW; scaling range 25 to 150 kVA/kW.
- Efficiency: 96.0% in AC mode, 98.0% in ECO mode, 95.5% in battery mode.
- Input 380/400/415 V, 40 to 70 Hz, power factor above 0.99, THDi below 3% (100% linear load).
- Bypass overload: 110% continuous, 125% for 5 minutes, 150% for 1 minute.
- Inverter overload: 110% for 1 hour, 125% for 10 minutes, 150% for 1 minute.
- Battery ±240 Vdc, 40 units (even number from 32 to 44), charger up to 20% of output power.
- Altitude below 1000 m; between 1000 and 2000 m, 1% power derating per 100 m.
- Weight: cabinet 116 kg, module 18 kg; cabinet 482 x 916 x 931 mm.
Using it in design
- With 25 kW module steps, calculate from the load how many modules an N+1 arrangement needs.
- Size the battery string for ±240 Vdc and 40 units; the settable range is 32 to 44.
- At sites above 1000 m, subtract 1% of power per 100 m from capacity.
- Output power factor is 1, so kVA equals kW; the input THDi below 3% eases generator compatibility.
- Options (PDU, parallel kit, SPD, LBS) must be written into the specification explicitly.
Who should read it
Electrical designers comparing modular UPS units for data centres and server rooms.
Document contents
- Product description
- System
- Input
- Bypass
- Output
- Battery
- Physical
Publication details
- Authors
- Master Power Technologies
- Publisher
- Master Power Technologies
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Master Power Technologies Master Power Technologies MRM150/25C technical specification, pp.1–2. Master Power Technologies. https://kva.co.za/wp-content/uploads/2025/10/MRM150-25C.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.