Master Power Technologies MT Range Three Phase 10-40 kVA UPS Catalogue
Original title Master Power Technologies MT range three phase10–40kVA, pp.1–10
Master Power Technologies
PowerSure MT33X is a tower-type three-phase online UPS range from 10 to 40 kVA, with normal-operation efficiency of 95% to above 96% and input THDi below 3% to 4%.
On this page
Overview
The PowerSure MT33X series is a tower-design three-phase UPS family that fits office, industrial and data-centre settings. The manufacturer says its efficiency lowers operating cost and that external battery configuration lets runtime be extended. The catalogue runs to 10 pages with one data page per model: MT33010XL, MT33015XL, MT33020XL, MT33030XL and MT33040XL.
The input mains is three-phase plus neutral plus ground, 380/400/415 VAC, 50/60 Hz with a 40 to 70 Hz window; the full-load input range is 304 to 478 Vac and input power factor is above 0.99. THDi is below 4% in the 10 kVA class and below 3% at 20 kVA. The 10 kVA model has output power factor 1 and 10 kW, the 20 kVA model 0.9 and 18 kW, the 30 kVA model 27 kW and the 40 kVA model 36 kW. Bypass overload is 125% continuous, 125 to 130% for 10 minutes and 130 to 150% for 1 minute.
Normal-operation efficiency is at most 95% on the 10, 15 and 30 kVA pages, above 95% at 20 kVA and above 96% at 40 kVA. Inverter overload is 60 minutes below 110%, 10 minutes at 110 to 125% and 1 minute at 125 to 150%. Battery voltage is ±240 VDC and charger power is at most 20% of system power. Cabinet weight ranges from 31 to 61 kg, with a 600 x 980 x 950 mm, 170 kg cabinet also listed for the 10 and 15 kVA models. The 15 kVA page repeats the 10 kVA values.
Key points
- Five data pages: MT33010XL, 015XL, 020XL, 030XL, 040XL; tower design with external battery support.
- Output: 10 kVA / 10 kW; 20 kVA / 18 kW; 30 kVA / 27 kW; 40 kVA / 36 kW.
- Input 380/400/415 VAC, 304 to 478 Vac at full load; power factor >0.99; THDi <4% (10 kVA), <3% (20 kVA).
- Efficiency in normal operation: at most 95% (10, 15, 30 kVA), >95% (20 kVA), >96% (40 kVA).
- Bypass overload: 125% continuous, 10 min at 125 to 130%, 1 min at 130 to 150%.
- Inverter overload: 60 min below 110%, 10 min at 110 to 125%, 1 min at 125 to 150%.
- Battery ±240 VDC; charger up to 20% of system power; RS232 and RS485 standard; SNMP, dry contact, parallel kit and battery cold start optional.
- Noise 58 dB (10 kVA) to 65 dB (20 kVA and above) at 1 m; operation 0 to 40 °C.
Using it in design
- Output power factor is 1 or 0.9 depending on the model; size by kW: the 20 kVA model carries 18 kW and the 40 kVA model 36 kW.
- Input power factor of 0.99 and THDi of 3 to 4% ease generator and transformer sizing.
- Size the battery string for ±240 VDC and keep the 20% charger limit in mind for long autonomy.
- Specify the parallel kit and SNMP card separately where redundancy and monitoring are required.
- Include the 65 dB noise level for 20 kVA and above in acoustic design.
Who should read it
Electrical designers comparing three-phase tower UPS units from 10 to 40 kVA.
Document contents
- Product description
- Efficiency and system
- Environment
- Mechanical
- Main input
- Bypass input
- Output
- Battery and charger
Publication details
- Authors
- Master Power Technologies
- Publisher
- Master Power Technologies
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Master Power Technologies Master Power Technologies MT range three phase10–40kVA, pp.1–10. Master Power Technologies. https://kva.co.za/wp-content/uploads/2025/10/MT-Range-Three-Phase-10-40-kVA.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.