Artronic ART STS Static Transfer Switch, 16-500 A
Original title ARTronic ART STS 1-2-3-4 Pole 16-500A brochure, p.3
ARTronic
Artronic ART STS static transfer switch range: 1 to 4 poles, 16-500 A, transfer under 4 ms between synchronous sources, over 98-99% efficiency at full load and EN 62310 compliance.
On this page
Overview
The brochure presents the ART STS range in two tables: 1 and 2 pole models (16, 25, 32, 50, 63, 100, 150, 200 A; 220/230/240 Vac) and 3 and 4 pole models (50, 100, 150, 200, 250, 300, 400, 500 A; 380/400/415 Vac 3F+N+PE). The product switches without interruption between two independent power sources, with synchronous and asynchronous transfer, source priority selection, automatic or manual transfer and remote control. Priority sectors are finance, medical, industry, data centres and energy.
Technical data: input voltage range 180-264 Vac (phase-neutral), frequency 45-65 Hz (transfer outside the range, adjustable), input voltage THD below 10%, efficiency above 99% at full load for 3-4 poles and above 98% for 1-2 poles. Transfer type is break-before-make; time is under 4 ms for synchronous and about 10 ms for asynchronous sources, with zero-current transition when out of sync. Overload on 3-4 pole models is 100-110% continuous, 100-125% for 10 min, 125-150% for 1 min, 150-200% for 10 s and above 200% for 250 ms.
Protections are overload, short circuit, over-temperature, backfeed, SCR fault and out-of-sync protection. RS232 is standard and RS485/TCP-IP/SNMP optional; there are four programmable alarm relays and a cabinet temperature sensor. Operating temperature is 0-50 °C, protection class IP20 (up to IP66 optional on 3-4 pole), noise below 52-60 dBA. Weight is 139-340 kg for 3-pole and 160-375 kg for 4-pole models.
Key points
- 1-2 pole: 16-200 A, 220/230/240 Vac; 3-4 pole: 50-500 A, 380/400/415 Vac.
- Transfer time <4 ms for synchronous sources, about 10 ms for asynchronous sources.
- Efficiency at full load >99% for 3-4 poles, >98% for 1-2 poles.
- Input range 180-264 Vac (L-N), 45-65 Hz; input THD <10%.
- Overload (3-4 pole): 100-110% continuous, 100-125% 10 min, 125-150% 1 min, 150-200% 10 s, >200% 250 ms.
- Protections: overload, short circuit, over-temperature, backfeed, SCR fault, out-of-sync.
- Communication: RS232 standard; RS485, TCP-IP, SNMP optional; 4 programmable alarm relays.
- 0-50 °C; IP20 (up to IP66 optional); EN 62310-1, -2, -3.
- Weight: 139-340 kg for 3-pole, 160-375 kg for 4-pole.
Using it in design
- For single-corded critical loads, place the STS between two independent UPS lines.
- With non-synchronous sources the transfer takes about 10 ms; compare it with the load's ride-through.
- Select switch current from load current and the overload curve, up to 500 A.
- Wire the backfeed and SCR-fault alarm outputs into the monitoring system.
- Carry cabinet weight and size (from 680x540x1500 mm for 3-pole) into the electrical room layout.
Who should read it
Data-centre electrical designers selecting transfer switches for A/B power distribution and single-corded loads.
Document contents
- Specifications and priority application areas
- ART STS 3-pole and 4-pole technical specifications
- ART STS 1-pole and 2-pole technical specifications
Publication details
- Authors
- ARTronic
- Publisher
- ARTronic
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
ARTronic ARTronic ART STS 1-2-3-4 Pole 16-500A brochure, p.3. ARTronic. https://www.artronic.com.tr/Upload/ProductBrochure/4e4f67b8116645a18daa6c7dd3f2e886-ART-STS_ENG.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
