BTB Electric BA Series Automatic Transfer Switches Technical Catalogue

Original title BTB Electric BA Series Automatic Transfer Switches catalogue, printed pp.10-11

BTB Electric

BTB Electric BA series ATS catalogue: NN, NY, TN, TY, PC and HY types, 63-2000 A, IEC/EN 60947-6-1 compliance, AC 500 V and DC 125 V, and 140-165 ms change-over on the 63-630 A NN type.

On this page

Overview

The catalogue presents BTB Electric's BA series automatic transfer switches (ATS) in two-position (NN, NY, HY) and three-position (TN, TY, PC) families. NN is a two-position ON-ON switch without controller and needs an external automatic controller; NY has a built-in controller; TN is three-position without controller, TY three-position with controller and PC a three-position switch of power-continuity design; HY is a two-position automatic switch for residential use. The ordering code has fields for BA, rated current (063, 100, 250, 400, 630, 800, 10H=1000, 12H=1250, 16H=1600, 20H=2000 A), type, number of poles (2, 3, 4) and control voltage (DC 110 V, AC 110 V, AC 220 V).

General conditions: IEC/EN 60947-6-1 and IEC 60664-1; ambient temperature -5 to +55 °C, relative humidity up to 95%, altitude up to 2000 m, pollution degree 3, installation category IV, utilization category AC-33iB (AC-33B for PC types). Mounting verticality must stay within 15°. For the NN type the rated operational voltage is AC 500 V and DC 125 V, Ui 690 V, Uimp 8 kV, Icw 10 kA for 63/100 A and 250 A models and 12 kA for 400/630 A; life is 35 000 electrical and 180 000 mechanical operations.

Transfer times for the NN type are change-over 140-165 ms, opening 55-65 ms and contact transfer 85-125 ms. In the large classes (800-2000 A) Uimp is 12 kV and Icw 25-35 kA. All types can be combined with a smart controller (ATbS C55, C56, C50) for over- and undervoltage and over- and underfrequency protection; the transfer delay prevents the remaining source from feeding back into the main source.

Key points

  1. Families: NN, NY (two-position), TN, TY, PC (three-position), HY (residential).
  2. Ratings: 63, 100, 250, 400, 630, 800, 1000, 1250, 1600, 2000 A; 2, 3 or 4 poles.
  3. Standards: IEC/EN 60947-6-1 and IEC 60664-1; utilization category AC-33iB.
  4. Ambient -5 to +55 °C; humidity ≤95%; altitude ≤2000 m; pollution degree 3; installation category IV.
  5. NN type: AC 500 V/DC 125 V; Ui 690 V; Uimp 8 kV; Icw 10 kA (63/100, 250 A) and 12 kA (400/630 A).
  6. NN type: change-over ≤140-165 ms, opening ≤55-65 ms, contact transfer ≤85-125 ms.
  7. NN life: 35 000 electrical, 180 000 mechanical operations; 60 operations per hour.
  8. 800-2000 A: Uimp 12 kV; Icw 25-35 kA.
  9. Controllers: ATbS C55, C56, C50; control voltage DC 110 V, AC 110 V, AC 220 V.

Using it in design

  • Choose NY or TY when a built-in controller is needed and NN or TN when an external smart controller is wanted.
  • Compare the transfer time (140-165 ms for NN) with UPS bypass and load ride-through; use a static transfer switch where millisecond transfer is required.
  • Compare Icw with the calculated short-circuit current (10, 12, 25, 35 kA).
  • Match control voltage (DC 110, AC 110 or AC 220 V) to the panel supply design.
  • Verify altitude 2000 m, ambient -5 to +55 °C and pollution degree 3 against electrical room conditions.

Who should read it

Electrical designers selecting mechanical transfer switches between generator and mains.

Document contents

  1. ATS NN type (two-position without controller)
  2. ATS NY type (two-position with controller)
  3. ATS TN type (three-position without controller)
  4. ATS TY type (three-position with controller)
  5. ATS PC type (three-position with PC design)
  6. ATS HY type (two-position for residential use)

Publication details

Authors
BTB Electric
Publisher
BTB Electric
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

BTB Electric BTB Electric BA Series Automatic Transfer Switches catalogue, printed pp.10-11. BTB Electric. https://btb-electric.com/wp-content/uploads/Technical-catalogue-Automatic-Transfer-Switches-BA-series.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.