Hankwang and BTB Electric Automatic Transfer Switches Technical Catalogue (N, TN, ATB)

Original title BTB and Hankwang Automatic Transfer Switches technical catalogue

BTB Electric

Joint Hankwang and BTB Electric automatic transfer switch catalogue: N, TN and ATB types, 63-630 A switches at 600 V AC / 125 V DC, IEC 60947-6-1 compliance, Hanpro1000 and ATbS C55 controllers.

On this page

Overview

The catalogue presents automatic transfer switches (ATS) as a joint product of two electrical equipment makers. The introduction explains the operating logic: on utility failure the ATS signals the generator to start, and once the generator reaches the correct frequency and voltage the load transfers to it; when utility returns the load goes back and the generator stops. Applied standards are IEC 60947-6-1, IEC 60947-2-1, BS 4652 part 1, VDE 0660, ANSI and KSC 8325. Operating ambient is -20 to +60 °C and altitude below 2000 m.

The N type is an electromagnetically operated two-position (double-throw) switch with fast transfer within 15 ms: HK-63/125N and HK-200/250N, AC 600 V and DC 125 V, Ui 690 V, Uimp 8 kV, Icw 5 kA, 5000 electrical and 10 000 mechanical operations. The TN type is three-position: 100/125 A and 200/250 A (Icw 5-7 kA), 400/500 A and 630 A (Icw 10-12 kA), opening ≤30 ms and closing ≤60 ms. They are recommended for medium-power loads in factories, hospitals and homes.

The ATB (Automatic Transfer Breaker) combines two AC-33B switches in one device and is an electromechanical, ACB-compatible design that can transfer power without interrupting the load; it targets critical loads in airports, hospitals and high-tech plants. Options include synchronising between gensets or genset and mains, closed-transition bypass and protection relays (OCR, GR). The catalogue covers models ATB-06EX to ATB-63EX and the Hanpro1000 and ATbS C55 controllers.

Key points

  1. Standards: IEC 60947-6-1, IEC 60947-2-1, BS 4652-1, VDE 0660, ANSI, KSC 8325.
  2. Ambient -20 to +60 °C; storage -25 to +65 °C; altitude <2000 m.
  3. N type: 63/125 A and 200/250 A, AC 600 V/DC 125 V, transfer within 15 ms, Icw 5 kA.
  4. TN type: 100/125, 200/250, 400/500, 630 A; Icw 5, 7, 10, 12 kA; opening ≤30 ms, closing ≤60 ms.
  5. N type life: 5000 electrical, 10 000 mechanical; 150 operations per hour.
  6. ATB type: two AC-33B in one device; no-break power transfer; genset synchronising.
  7. Controllers: Hanpro1000 and ATbS C55.
  8. Microprocessor controller with LCD measurement and monitoring; ATS and bypass switches are withdrawable.

Using it in design

  • In generator-backed data-centre distribution, select the ATS to IEC 60947-6-1 and compare Icw with the calculated short-circuit current.
  • In systems with UPS, evaluate generator transfer using the ATS transfer time (15 ms for the N type) together with the UPS ride-through calculation.
  • For critical loads, consider the ATB type, which offers no-break bypass and a withdrawable ATS.
  • List the controller (Hanpro1000 or ATbS C55) as a separate item in the specification.
  • Compare the altitude and ambient limits (2000 m, -20 to +60 °C) with site conditions.

Who should read it

Electrical designers and panel builders selecting transfer switches between generator and mains.

Document contents

  1. General
  2. Automatic Transfer Switches N type
  3. Automatic Transfer Switches TN type
  4. Automatic Transfer Breaker ATB type
  5. Controller Hanpro1000
  6. Controller ATbS C55

Publication details

Authors
BTB Electric
Publisher
BTB Electric
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

BTB Electric BTB and Hankwang Automatic Transfer Switches technical catalogue. BTB Electric. https://btb-electric.com/wp-content/uploads/2024/03/Technical-catalogue-Automatic-Transfer-Switches.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.