LTI Power Systems Static Transfer Switch 20A to 125A Datasheet

Original title LTI Static Transfer Switch20A-125A datasheet, p.2

LTI Power Systems

LTI Power Systems' 20 to 125 A static transfer switch moves a load between two AC sources in half a cycle; continuous ratings run 20 to 125 A and the design follows UL1008S.

On this page

Overview

The LTI static transfer switch gives a critical load virtually uninterruptible power by automatically or manually selecting between two AC input sources. If the preferred source leaves preset limits, the unit transfers instantly to the second source; when the preferred source returns within limits, it retransfers the load automatically. Typical sources are a UPS, inverter, motor generator, dual substation and AC regulator.

Switching is a half-cycle transfer using solid-state devices, with no contactors or relays. Break-before-make logic removes the risk of out-of-phase transfer between sources. The unit offers single or double pole design, 50/60 Hz, 110 to 240 V options, adjustable delayed transfer up to 10 seconds and Form C alarm contacts. The design targets the UL1008S standard.

Seven models exist: LTSS20, 30, 40, 50, 60, 100 and 125, with continuous current from 20 to 125 A. Overload capability is 125% for 2 hours, 150% for 15 minutes and 1000% for 2 cycles. Load power factor ranges from 0.5 to 1.0, leading or lagging, and crest factor up to 4:1. The enclosure is 7 x 19 x 13 inches and 10.43 kg. The document is a two-page manufacturer sheet and does not cover large three-phase STS units.

Key points

  1. Half-cycle (ultra-fast) transfer; solid-state switching with no contactors or relays.
  2. Seven models: LTSS20, 30, 40, 50, 60, 100, 125; continuous current 20 to 125 A.
  3. Input voltages 110, 120, 208, 220, 230, 240 V; 50/60 Hz.
  4. Overload: 125% for 2 hours, 150% for 15 minutes, 1000% for 2 cycles.
  5. Load power factor 0.5 to 1.0, crest factor up to 4:1; input voltage distortion up to 10% THD.
  6. Break-before-make switching prevents out-of-phase transfer between sources.
  7. Adjustable delayed transfer up to 10 seconds; Form C alarm contacts.
  8. Operation 0 to 50 °C, up to 1200 m without derating, noise below 55 dB(A); NEMA 1 enclosure.

Using it in design

  • Use a rack-mount STS to feed single-input equipment from two UPS lines; check whether the two sources are synchronised.
  • Select the switch rating against continuous load current and the 125% / 150% overload durations.
  • Set priority with the preferred-source selector and tune the retransfer delay to generator return.
  • Wire the Form C alarm contacts to the BMS or monitoring system.

Who should read it

Electrical designers who need source redundancy for single-corded equipment.

Document contents

  1. Features
  2. Options
  3. Electrical specifications
  4. Environmental
  5. Enclosure

Publication details

Authors
LTI Power Systems
Publisher
LTI Power Systems
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

LTI Power Systems LTI Static Transfer Switch20A-125A datasheet, p.2. LTI Power Systems. https://ltipowersystems.com/files/Datasheet_Static_Transfer_Switch3.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.