LTI Power Systems Static Transfer Switch 20A to 125A Datasheet
Original title LTI Static Transfer Switch20A-125A datasheet, p.2
LTI Power Systems
LTI Power Systems' 20 to 125 A static transfer switch moves a load between two AC sources in half a cycle; continuous ratings run 20 to 125 A and the design follows UL1008S.
On this page
Overview
The LTI static transfer switch gives a critical load virtually uninterruptible power by automatically or manually selecting between two AC input sources. If the preferred source leaves preset limits, the unit transfers instantly to the second source; when the preferred source returns within limits, it retransfers the load automatically. Typical sources are a UPS, inverter, motor generator, dual substation and AC regulator.
Switching is a half-cycle transfer using solid-state devices, with no contactors or relays. Break-before-make logic removes the risk of out-of-phase transfer between sources. The unit offers single or double pole design, 50/60 Hz, 110 to 240 V options, adjustable delayed transfer up to 10 seconds and Form C alarm contacts. The design targets the UL1008S standard.
Seven models exist: LTSS20, 30, 40, 50, 60, 100 and 125, with continuous current from 20 to 125 A. Overload capability is 125% for 2 hours, 150% for 15 minutes and 1000% for 2 cycles. Load power factor ranges from 0.5 to 1.0, leading or lagging, and crest factor up to 4:1. The enclosure is 7 x 19 x 13 inches and 10.43 kg. The document is a two-page manufacturer sheet and does not cover large three-phase STS units.
Key points
- Half-cycle (ultra-fast) transfer; solid-state switching with no contactors or relays.
- Seven models: LTSS20, 30, 40, 50, 60, 100, 125; continuous current 20 to 125 A.
- Input voltages 110, 120, 208, 220, 230, 240 V; 50/60 Hz.
- Overload: 125% for 2 hours, 150% for 15 minutes, 1000% for 2 cycles.
- Load power factor 0.5 to 1.0, crest factor up to 4:1; input voltage distortion up to 10% THD.
- Break-before-make switching prevents out-of-phase transfer between sources.
- Adjustable delayed transfer up to 10 seconds; Form C alarm contacts.
- Operation 0 to 50 °C, up to 1200 m without derating, noise below 55 dB(A); NEMA 1 enclosure.
Using it in design
- Use a rack-mount STS to feed single-input equipment from two UPS lines; check whether the two sources are synchronised.
- Select the switch rating against continuous load current and the 125% / 150% overload durations.
- Set priority with the preferred-source selector and tune the retransfer delay to generator return.
- Wire the Form C alarm contacts to the BMS or monitoring system.
Who should read it
Electrical designers who need source redundancy for single-corded equipment.
Document contents
- Features
- Options
- Electrical specifications
- Environmental
- Enclosure
Publication details
- Authors
- LTI Power Systems
- Publisher
- LTI Power Systems
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
LTI Power Systems LTI Static Transfer Switch20A-125A datasheet, p.2. LTI Power Systems. https://ltipowersystems.com/files/Datasheet_Static_Transfer_Switch3.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.