Static Power iSTS Model A1: 1RU single-phase static transfer switch (16 A, 32 A)

Original title Static Power iSTS Model A1 datasheet, p.2

Static Power

The Static Power iSTS Model A1 is a 1RU, 16 A and 32 A single-phase (2-pole) true solid-state static transfer switch: typical 10 ms synchronous break time, MTBF over 1,000,000 hours.

On this page

Overview

Designed and manufactured in Australia, the iSTS Model A1 is presented as a true solid-state static transfer switch (STS), more rugged than relay-based or hybrid transfer switches. It transfers a critical load safely and seamlessly between two power supplies. It mounts in a 19-inch rack at 1RU and is single-phase, 2-pole.

Current ratings are 16 A and 32 A, voltage ratings are 115 V or 230 V +/-10%, and frequency is 50/60 Hz +/-10% with auto detection. Transfer is break-before-make zero-current transfer by thyristors/SCR. Synchronous break time is typically 10 ms; asynchronous break time can be 0, 10, 50 ms or proportional to voltage (0 to 180 degrees), and detection is digital (<1 ms).

Protection and ruggedness: built-in transient voltage protection, back-feed protection contactors, a 300% peak fault-current setting with load-fault transfer inhibit, 100 A BS88/FE100 fuses and device ratings of 80 ARMS and 1400 V. Overload at 40 °C is 40 A for 30 s, 63 A for 1 s and 115 A for 0.1 s. There is no practical power factor limit, crest factor is 3:1, and permitted source voltage distortion is at most 10% THDV.

Physical data: 44x483x285 mm for the 16 A and 44x483x307 mm for the 32 A, weight 5 kg, operating temperature 0-40 °C, IP31, passive cooling and humidity 5-95% non-condensing. Inputs are IEC C20 for 16 A and 6 mm² terminals for 32 A; outputs are 2 x IEC C19 + 8 x IEC C13 or 6 mm² terminals. There is no maintenance bypass; source isolator switches are optional, as is Ethernet (LAN/TCP, Modbus, SNMP). Standards include IEC 62310-1,2,3, IEC 60950, IEC 61000-6, CE, RCM and RoHS; warranty is 24 months.

Key points

  1. 1RU/19-inch, 1-phase 2-pole; 16 A and 32 A; 115 V or 230 V +/-10%; 50/60 Hz.
  2. Thyristor/SCR break-before-make; synchronous break typically 10 ms; detection <1 ms.
  3. Asynchronous break time 0, 10, 50 ms or voltage-proportional (0 to 180 degrees).
  4. MTBF over 1,000,000 hours; back-feed protection contactors; built-in transient voltage protection.
  5. Overload at 40 °C: 40 A/30 s, 63 A/1 s, 115 A/0.1 s; fault current 300% peak.
  6. No practical power factor limit; crest factor 3:1; source THDV at most 10%.
  7. Weight 5 kg; 0-40 °C; IP31; passive cooling; no maintenance bypass.
  8. UPS Eco-Mode and RCD site compatible; IEC 62310-1,2,3; 24-month warranty.

Using it in design

  • For in-rack single-phase dual-source (A/B) feeds, choose the 16 A (C20 input) or 32 A model against load current, and plan load distribution across the 16 A model's 2 x C19 + 8 x C13 outputs.
  • For asynchronous sources (for example UPS and mains), compare the asynchronous break time (0-50 ms or voltage-proportional) with the load's ride-through.
  • With no maintenance bypass, state in the design how the load stays powered during service (source isolator option, dual-PSU servers).
  • Write compatibility with UPS Eco-Mode and RCD-protected sites into the project specification.
  • Add the optional Ethernet module (Modbus/SNMP) to the DCIM plan.

Who should read it

Electrical engineers designing rack-level single-phase dual-feed critical loads and data-centre operators.

Document contents

  1. Key features
  2. Available options
  3. Technical specification
  4. Input and output options
  5. Dimensions, environment and protection
  6. Regulatory approvals and warranty

Publication details

Authors
Static Power
Publisher
Static Power
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Static Power Static Power iSTS Model A1 datasheet, p.2. Static Power. https://www.staticpower.com.au/wp-content/uploads/2018/12/iSTS-Model-A1.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.