Infosec Mod5T and Mod5T E: 20 to 600 kVA Modular UPS Brochure
Original title Infosec Mod5T and Mod5T E: 20 to 600 kVA
Infosec UPS System
Infosec UPS System's brochure describes the 20-600 kVA modular Mod5T and Mod5T E ranges with hot-swappable 20, 30 and 60 kVA modules, N+X redundancy and efficiency up to 96%.
On this page
Overview
The brochure introduces two modular UPS families designed for data centres and critical applications. Mod5T is the high-end solution; Mod5T E is an economical version optimised for performance against investment. Both use high-frequency online double-conversion technology and have zero transfer time. Power is divided into hot-swappable 20, 30 or 60 kVA modules. Mod5T E takes up to 3 modules (20 or 30 kVA) in a single 15U cabinet; adding a 14U battery cabinet below gives a compact 29U unit. Mod5T cabinets are 30U or 42U and are configured from 20 kVA to 600 kVA; paralleling is standard up to 600 kVA. Each module has its own controller and a charger of up to 20 A.
Redundancy is explained as N+X: N is the number of modules supplying the required power and X is the number of extra modules providing security if one fails. When a module drops out, its load is shared automatically among the remaining modules. The dual-input arrangement lets the bypass line be fed from a second source such as a generator; the brochure shows this for Mod5T up to 210 kVA.
In the specification table, input power factor is above 0.99 at 100% load and above 0.98 at 50% load, and THDi is below 3% at 100% load. The input frequency range is 40-70 Hz, and output THDv does not exceed 1% on linear load or 3% on non-linear load. Efficiency is 94.5-96% on the 120-600/60 S models and stays high at 50% load. Overload is 150% for 1 minute. A battery module consists of 4 trays of 10 batteries each, and the count per tray can be set between 8 and 10.
Key points
- Power range 20-600 kVA; modules of 20, 30 and 60 kVA, hot-swappable.
- Mod5T E: up to 3 modules in a 15U cabinet; 29U configuration with a 14U battery cabinet. Mod5T: 30U or 42U cabinets.
- N+X redundancy: remaining modules share the load of a failed module.
- Dual input: separate rectifier and bypass feed, so a second source (for example a generator) can be connected.
- Input power factor above 0.99 at 100% load and above 0.98 at 50%; THDi below 3% at 100% load.
- Efficiency 94.5-96% (Mod5T 120-600/60 S); high efficiency is claimed at 50% load.
- Output THDv at most 1% (linear) and 3% (non-linear); overload 150% for 1 min.
- Each module has a charger of up to 20 A; battery module has 4 trays with 8-10 batteries per tray.
- Operation 0-40 °C; altitude below 1,000 m for nominal power; noise up to 75 dB (Mod5T) and 70 dB (Mod5T E).
Using it in design
- For halls with expected load growth, fix the module size (20/30/60 kVA) and the N+X redundancy level on day one.
- Use the dual-input option in distribution architectures where the bypass line is fed from a separate source.
- With input THDi below 3%, account for the low harmonic burden when sizing the generator.
- Plan battery runtime using in-cabinet and external battery cabinet options together with the 29U or 42U layout.
- Check the stated noise level and altitude limit against the room layout.
Who should read it
Data-centre electrical designers selecting modular UPS, and engineers building redundant power architectures for finance, health and telecom infrastructure.
Document contents
- Mod5T and Mod5T E: 20 to 600 kVA
- High efficiency and performance
- Redundancy N+X
- Static bypass and manual bypass, dual input
- Flexible and scalable solution
- Mod5T E (15U/29U) and Mod5T (30U/42U) cabinet configurations
- Overview of Mod5T UPS: power module, battery module, breakers, LCD, STS/control module
- Configuration and management
- Specifications table
Publication details
- Authors
- Infosec UPS System
- Publisher
- Infosec UPS System
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Infosec UPS System Infosec Mod5T and Mod5T E: 20 to 600 kVA. Infosec UPS System. https://www.infosec-ups.com/en_pt/mwdownloads/download/link/id/29
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.