Mod5T User Manual 04 17 AA 59 201 06 (Infosec UPS System)
Original title Mod5T user manual 04 17 AA 59 201 06
Infosec UPS System
Infosec Mod5T is a three-phase modular UPS built from 30 kVA/kW modules scaling from 30 to 300 kVA, with efficiency up to 94.5% and a 10-module cabinet reaching 300 kVA (210 kVA at 7+1).
On this page
Overview
The manual covers the Infosec UPS System Mod5T three-phase modular UPS family with 30 kVA modules, from 30 to 300 kVA. There are six cabinets: Mod5T 90/30 and 120/30 (internal battery modules), and 120/30 S, 180/30 S, 210/30 S and 300/30 S (external battery). Cabinet height is 30U or 42U and the maximum number of power modules is 3, 4, 4, 6, 8 and 10. Standard cabinets have battery module compartments (12 or 20 modules); extended (S) cabinets connect the battery externally. Each cabinet holds one switch unit and one STS module.
Operating modes are standby, line, battery, bypass, ECO, shutdown and maintenance bypass. In line mode the rectifier draws DC power from the utility, the charger charges the battery and the inverter supplies pure AC output. In ECO mode the load is powered by bypass while bypass voltage and frequency are within the acceptable range; if bypass is out of range the load moves to the inverter, and to shorten transfer the rectifier and inverter keep running. The manual also describes control-panel screens, the alarm list, history record, dry contact and SNMP interfaces, troubleshooting and module replacement.
Specifications: input 3 x 380/400/415 VAC (3-phase plus neutral), 305 to 478 VAC at 100% load and 208 to 304 VAC below 70% load; frequency 50/60 Hz (40 to 70 Hz); input power factor above 0.99 at 100% load; THDi below 3%. Output regulation is ±1% (balanced load), THDv ≤2% on linear and ≤4% on non-linear load. Overload is 1 hour at 110%, 10 minutes at 120% and 1 minute at 150%. Efficiency reaches 94.5%. Battery is ±240 V (40 x 12 V), float 2.25 V per element, boost 2.35 V per element and up to 8 A charging per power module. Power factor is 1, derated to 0.8 at 31 to 35 °C and 0.7 at 36 to 40 °C when temperature exceeds 30 °C.
Key points
- 30 kVA / 30 kW power module; cabinets 90/30, 120/30 (internal battery), 120/30 S, 180/30 S, 210/30 S, 300/30 S (external battery).
- Maximum power modules 3, 4, 4, 6, 8 (7+1 for 210 kVA) and 10; cabinet 30U or 42U.
- Input 3 x 380/400/415 VAC; 305 to 478 VAC at 100% load; power factor >0.99; THDi <3%.
- Output regulation ±1% (balanced), ±2% (unbalanced); THDv ≤2% (linear), ≤4% (non-linear).
- Overload: 110% for 1 hour, 120% for 10 minutes, 150% for 1 minute, 200 ms above 150%.
- Efficiency up to 94.5%; output power factor 1; 0.8 at 31 to 35 °C and 0.7 at 36 to 40 °C above 30 °C.
- Battery ±240 V (40 x 12 V); float 2.25 V per element; boost 2.35 V per element; 8 A per module; temperature compensation.
- Parallel rack system: power module firmware 10.69 and LCD firmware 09.50 or higher; input and output cable lengths must be equal.
Using it in design
- For N+1 redundancy, compute the module count from the load; for example the 210 kVA cabinet is configured 7+1.
- If room temperature may exceed 30 °C, include the output power-factor derating (31 to 35 °C: 0.8; 36 to 40 °C: 0.7) in the capacity calculation.
- For the external-battery cabinet (S series), plan battery space and cable size for ±240 V DC (40 x 12 V).
- In parallel rack installations, verify that input and output cables are the same length for every rack and that firmware versions meet the requirement.
- Show on the single-line diagram the four-pole disconnecting device and backfeed warning labels the manual calls for.
Who should read it
Electrical engineers and site teams installing and operating 30 to 300 kVA modular UPS systems in data centres and industrial plants.
Document contents
- Safety
- Installation
- Operation mode and UPS operation
- Control panel and display description
- Interface and communication
- Troubleshooting
- Service
- Specifications
- UPS installation for parallel rack system
Publication details
- Authors
- Infosec UPS System
- Publisher
- Infosec UPS System
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Infosec UPS System Mod5T user manual 04 17 AA 59 201 06. Infosec UPS System. https://www.infosec-ups.com/en/mwdownloads/download/link/id/137/
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.