Helios Heteos 3000 UPS Data Sheet (pp.2-3)
Original title Helios Heteos 3000 UPS data sheet, pp.2-3
Helios Power Solutions
The Helios Heteos 3000 is a 3000 VA / 2700 W single-phase double-conversion on-line UPS with 91% AC-mode and 90% battery-mode efficiency, input power factor of 0.99 or better and a weight of 27.4 kg.
On this page
Overview
The document is the data sheet for the Heteos 3000 model of Helios Power Solutions' Heteos 100 series. The unit is a 1-phase-in / 1-phase-out, 3000 VA / 2700 W, DSP-controlled true on-line double-conversion UPS. Server rooms, telecom, offices, healthcare and commercial buildings are named as applications; the maker stresses low total cost of ownership, compact size and easy installation.
On the input side, voltage is offered as 100-127 VAC or 200-240 VAC; the input range is 110-300 VAC (or 55-150 VAC) at 50% load and 160-300 VAC (or 80-150 VAC) at 100% load, frequency range is 40-70 Hz and power factor is 0.99 or better. Output regulation is ±1%, THD is 2% on linear and 4% or less on non-linear load, AC-to-battery transfer time is zero and inverter-to-bypass is typically 4 ms. Operating modes are on-line, battery, ECO (energy saving through bypass, with the battery still charged) and bypass.
The battery section lists six 12 V 9 Ah batteries (CSB internal batteries), 82.1 VDC charge voltage, 1.5 A maximum charge current and 90% recharge in 4 hours; battery charging is disabled automatically when running on a generator. Size is 318 x 190 x 421 mm (D x W x H) and weight is 27.4 kg; operating temperature is 0-40 °C, humidity 0-95% RH, altitude 1500 m at full load and noise 50 dB or less. Standards are IEC 62040-1/2/3, IEC 60364 and ISO 9001.
Key points
- Capacity 3000 VA / 2700 W; 1-phase in, 1-phase out; input PF 0.99 or better.
- Efficiency: 91% in AC mode, 90% in battery mode.
- Input range: 110-300 VAC at 50% load, 160-300 VAC at 100% load (200-240 V version); frequency 40-70 Hz.
- Output regulation ±1%; THD 2% on linear and 4% or less on non-linear load.
- Transfer: AC to battery zero, inverter to bypass typically 4 ms.
- Battery: 12 V 9 Ah x 6, 82.1 VDC, 1.5 A, 90% in 4 h; charging disabled automatically on generator.
- Size 318 x 190 x 421 mm, weight 27.4 kg; 0-40 °C, 1500 m at full load, noise 50 dB or less.
- Interfaces: RS232; optional RPA, SNMP and Modbus RTU.
Using it in design
- For a small server room, check the 2700 W load limit and the minutes-level autonomy of the internal battery (6 x 12 V 9 Ah), and whether an external battery is needed.
- Consider the wide input range (160-300 VAC at 100% load) for weak-grid and generator supply.
- If ECO mode is used, compare the bypass transfer time (typically 4 ms) and the lack of conditioning in that mode with load sensitivity.
- Verify derating separately for installations above 1500 m.
Who should read it
Electrical designers selecting UPS units for small server rooms, offices and telecom points.
Publication details
- Authors
- Helios Power Solutions
- Publisher
- Helios Power Solutions
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Helios Power Solutions Helios Heteos 3000 UPS data sheet, pp.2-3. Helios Power Solutions. https://heliosps.com/wp-content/uploads/2024/06/Heteos3000-UPS-Data-Sheet.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.