Technical guideFree to readYear not stated

Helios TC-2500 Industrial AC UPS: specifications table

Helios Power Solutions

The TC-2500 product page from Helios Power Solutions describes a 2500 VA / 2500 W rack-mount line-interactive outdoor UPS that runs from -37 °C to 74 °C without derating, with a 48 VDC battery string and a weight of 21 kg.

On this page

Overview

The page documents the 2.5 kVA model of the TC series, which Helios Power Solutions offers for high-temperature and outdoor applications. The manufacturer states that the unit goes beyond the 0-40 °C range of general-purpose UPSs and operates from -37 °C to 74 °C with no derating. It complies with the Transportation Electrical Equipment Specifications (TEES) and can be installed in outdoor cabinets. Target applications are outdoor base stations, environmental monitoring stations, traffic signal centres and monitoring systems on solar farms.

The topology is line-interactive with a built-in AVR. Input and output are selectable at 220, 230 or 240 Vac, with an input voltage tolerance of ±25% and a frequency of 50/60 Hz. The output is a pure sine wave with frequency stability of ±0.5 Hz. Transfer time is given as a maximum of 12 ms in normal mode and a maximum of 25 ms in generator mode. Connections are made through a terminal block, an Anderson PP45 quick connector and an IEC socket.

On the battery side the string voltage is 48 VDC, the battery type is lead-acid and the maximum charge current is 10 A; the page does not say whether the battery sits inside the unit or outside it. Management is through RS232, USB (type B) and an optional SNMP or Modbus TCP/IP card, plus six programmable dry contacts. The specification table gives the dimensions as 432 x 320 x 133 mm (W x D x H) and the weight as 21 kg. Operating humidity is 0-95% non-condensing and noise is below 60 dB. The product SKU is listed as TC-2500HT.

Key points

  1. Capacity 2500 VA / 2500 W; line-interactive topology with built-in AVR.
  2. Operating temperature -37 °C to 74 °C with no derating.
  3. Input and output 220/230/240 Vac; input tolerance ±25%; output frequency 50/60 Hz ± 0.5 Hz.
  4. Transfer time: 12 ms maximum in normal mode, 25 ms maximum in generator mode.
  5. Battery string voltage 48 VDC, lead-acid, maximum charge current 10 A.
  6. Dimensions (W x D x H) 432 x 320 x 133 mm; weight 21 kg; rack mount.
  7. Communication: RS232, USB, optional SNMP or Modbus TCP/IP; six programmable dry contacts.
  8. Compliant with TEES (Transportation Electrical Equipment Specifications); operating humidity 0-95%, noise below 60 dB.

Using it in design

  • Choose a UPS of this class for places outside the 0-40 °C range, such as unconditioned outdoor cabinets, perimeter security and site monitoring points; it is not needed for loads inside the data hall.
  • Compare the line-interactive transfer time of 12 ms (25 ms in generator mode) with the hold-up time of the supplied device's power supply.
  • Size battery capacity and recharge time from the 48 VDC string and the 10 A charge-current limit, and confirm that the batteries suit the same temperature range.
  • A height of 133 mm takes 3U in a 19-inch rack; allow for the 320 mm depth and 21 kg weight in the cabinet layout.
  • For remote sites, add the SNMP or Modbus TCP/IP card and the dry contacts to the specification.

Who should read it

Electrical and infrastructure designers selecting UPSs for outdoor cabinets, perimeter security systems and remote-site equipment.

Document contents

  1. Product Range
  2. Description
  3. Main Features
  4. Applications
  5. Additional information
  6. Specifications table: Input, Output, Protection, Management & Communication, Battery, Indicators, Environment, Physical

Publication details

Authors
Helios Power Solutions
Publisher
Helios Power Solutions
Year
Year not stated
Document language
Unverified
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Helios Power Solutions Helios TC-2500 Industrial AC UPS: specifications table. Helios Power Solutions. https://heliosps.com/product/tc-2500-industrial-ac-ups-2500va-2500w/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.