Hitachi Hi-Rel HS11 Single Phase IT UPS, 46354 Ver.3 (p.4)
Original title Hitachi Hi-Rel HS11 IT UPS, 46354 Ver.3, p.4
Hitachi Hi-Rel
The Hitachi Hi-Rel HS11 series is a range of 6 kVA / 4800 W and 10 kVA / 8000 W single-phase on-line UPS units with 0 ms transfer time, 88% AC-mode efficiency and a 176-280 VAC input range.
On this page
Overview
The document is the technical specifications page of Hitachi Hi-Rel Power Electronics' HS11 Series Single Phase IT & Infra UPS catalogue (46354 Ver.3). The series covers 6 kVA to 10 kVA (1:1). The table gives two capacities, 6000 VA / 4800 W and 10000 VA / 8000 W; the HS11, HS11S and HS11H model names are grouped in the same table.
On the input side, nominal voltage is 220/230/240 VAC, the input range at 100% load is 176-280 VAC, frequency range is 46-54 Hz (50 Hz system) or 56-64 Hz (60 Hz system), and input power factor is 0.99 or better at nominal voltage and 100% load. Output regulation is ±1%, overload is 10 min at 100-110%, 1 min at 110-130% and 1 s above 130%, crest factor is up to 3:1, THD is 3% on linear and 6% or less on non-linear load. Transfer time from AC to battery and from inverter to bypass is 0 ms, and overall AC-mode efficiency is 88%.
On the battery side the standard model has sixteen 12 V 7 Ah batteries, 90% recharge in 9 hours, 1 A maximum charge current and 218.4 VDC charge voltage. The long-run model uses 16-20 external batteries, charge current adjustable 1/2/4/6 A and charge voltage 218.4-272 VDC. Standard enclosure sizes are 369 x 190 x 688 mm (6 kVA, 72 kg) and 442 x 190 x 688 mm (10 kVA, 82 kg); long-run enclosures are 369 x 190 x 318 mm (21 kg) and 442 x 190 x 318 mm (23 kg). Footnotes require derating to 80% in frequency converter mode and 90% at 208 VAC output, plus 1% per 100 m above 1000 m.
Key points
- Capacity 6000 VA / 4800 W and 10000 VA / 8000 W; single phase with ground.
- Input 220/230/240 VAC, 176-280 VAC at 100% load; input PF 0.99 or better.
- Output regulation ±1%; THD 3% on linear and 6% or less on non-linear load; crest factor 3:1.
- Overload: 10 min at 100-110%, 1 min at 110-130%, 1 s above 130%.
- Transfer time 0 ms (AC to battery and inverter to bypass); AC-mode efficiency 88%.
- Standard battery 16 x 12 V 7 Ah, 218.4 VDC, 90% in 9 h; long-run model uses 16-20 external batteries with 1-6 A charging.
- Weights: standard enclosure 72 kg (6 kVA) and 82 kg (10 kVA); long-run enclosure 21 and 23 kg.
- Derate to 80% in frequency converter mode and 90% at 208 VAC output; 1% per 100 m above 1000 m.
Using it in design
- Base load calculations on the kW rating (4800 W or 8000 W); output power factor is 0.8 (kW/kVA).
- For long autonomy choose the long-run model and set external battery count (16-20) and charge current from the runtime.
- Use the 88% AC-mode efficiency in heat-load and cooling calculations.
- If 208 VAC output or frequency converter mode is used, multiply capacity by 0.9 and 0.8 respectively.
Who should read it
Electrical designers selecting single-phase UPS units for small server rooms and infrastructure applications.
Publication details
- Authors
- Hitachi Hi-Rel
- Publisher
- Hitachi Hi-Rel
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Hitachi Hi-Rel Hitachi Hi-Rel HS11 IT UPS, 46354 Ver.3, p.4. Hitachi Hi-Rel. https://www.hitachi-hirel.com/pdf/catalogues/uninterruptible-power-supply-ups/HS11-Series-IT-UPS-46354-Ver.3.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.