Technical guideFree to readYear not stated

Hitachi Hi-Rel HM33 Series IT & Infra UPS brochure (Ver. 3)

Original title Hitachi Hi-Rel HM33 IT UPS brochure Ver.3, p.4

Hitachi Hi-Rel

The HM33 brochure from Hitachi Hi-Rel Power Electronics describes eleven three-phase modular double-conversion UPS models from 60 kVA to 500 kVA: unity output power factor, AC-mode efficiency above 95-96%, input current distortion below 3% and parallel operation of up to 30 modules.

On this page

Overview

The six-page brochure describes the HM33 series modular UPS family from India-based Hitachi Hi-Rel Power Electronics. The manufacturer states that the series offers up to 900 kVA in a footprint of under 2 m², is built from hot-swappable 30 kVA and 50 kVA power modules and can be paralleled up to 30 modules. Target uses are internet service providers, data centres, computer rooms and corporate offices. The design is fully DSP-controlled and IGBT-based, and a smart sleep function raises efficiency by putting some modules to sleep at low load.

The technical table lists eleven models: HM33-60-3X, 80-3X, 90-3X, 100-5X, 120-3X, 150-5X, 200-5X, 250-5X, 300-5X, 400-5X and 500-5X. The input is three phases plus neutral and ground at 380/400/415 VAC, 50/60 Hz. At full load the input voltage range is 304-478 VAC; between 228 and 304 VAC the load is reduced linearly according to the lowest phase voltage. Input power factor is above 0.99 and input current THDi is below 3% at full linear load.

The output power factor is unity, so kVA and kW ratings are equal. Voltage precision is ±1%, THDu is below 1.5% on linear load and below 6% on full non-linear load to IEC/EN 62040-3. The inverter carries up to 110% for 60 minutes, 110-125% for 10 minutes, 125-150% for 1 minute and above 150% for 200 ms. The battery system is ±240 VDC, settable from 34 to 44 blocks in even numbers, and 12 V, 2 V or lithium-ion batteries can be used. Charger power is at most 20% of output power.

Efficiency in AC mode is given as above 95% for the 60, 90 and 120 kVA models and above 96% for the 80 and 100 kVA models and the 150-500 kVA models; the figures are lower bounds. Cabinets range from 600 x 980 x 950 mm and 170 kg for 60 kVA to 1300 x 1100 x 2000 mm and 810-900 kg for 400 and 500 kVA; the weights are for the cabinet. Operating temperature is 0-40 °C and ingress protection is IP20. Above 1000 m and up to 2000 m, the load is derated by 1% per 100 m.

Key points

  1. Eleven models: 60, 80, 90, 100, 120, 150, 200, 250, 300, 400 and 500 kVA; model codes carry a 3X or 5X suffix, and power modules are 30 kVA and 50 kVA.
  2. Input 380/400/415 VAC three-phase; 304-478 VAC at full load; input power factor above 0.99; THDi below 3%.
  3. Output power factor 1; voltage precision ±1%; THDu below 1.5% on linear load and below 6% on non-linear load.
  4. Inverter overload: up to 110% for 60 minutes, 110-125% for 10 minutes, 125-150% for 1 minute, above 150% for 200 ms.
  5. Efficiency (AC mode and battery mode): above 95% for 60, 90 and 120 kVA; above 96% for 80, 100 and 150-500 kVA.
  6. Battery: ±240 VDC, 34-44 blocks (even numbers), 12 V, 2 V or Li-ion; charger power at most 20% of output power.
  7. Cabinet dimensions (W x D x H): 60 kVA 600 x 980 x 950 mm; 80, 90, 120 kVA 600 x 980 x 1400 mm; 100 kVA 600 x 980 x 1150 mm; 150 and 200 kVA 650 x 960 x 1400 mm; 250 and 300 kVA 650 x 960 x 2000 mm; 400 and 500 kVA 1300 x 1100 x 2000 mm.
  8. Cabinet weights: 170, 210, 231, 210, 266, 305, 350, 445, 490, 810 and 900 kg.
  9. Noise at 1 metre is 65 dB at 100% load and 62 dB at 45% load; operation 0-40 °C, IP20.
  10. Bypass voltage range selectable, default -20% to +15%; synchronised range ±0.5 to ±5 Hz, default ±3 Hz.

Using it in design

  • With unity output power factor, select the model directly against the IT load in kW, and plan the module count in 30 or 50 kVA steps for N+X redundancy.
  • Use the 95% and 96% lower bounds for heat load and PUE calculations, and request a curve from the manufacturer for part-load efficiency.
  • Design the battery string for ±240 VDC and 34-44 blocks, and include the 20% charger-power limit in the recharge-time calculation.
  • Models up to 120 kVA need front access only, larger ones need front and rear access; set service clearances accordingly.
  • On sites above 1000 m, add the 1% per 100 m derating to the capacity calculation.
  • Input THDi below 3% eases generator sizing; use it together with the 0.99 input power factor when selecting the generator.

Who should read it

Electrical designers and capacity planners selecting modular UPSs for medium and large data centres.

Document contents

  1. About HM33 Series IT & Infra UPS
  2. Total Solution for
  3. Features
  4. Optional Features
  5. Configuration
  6. Technology
  7. Certification
  8. Technical Specifications

Publication details

Authors
Hitachi Hi-Rel
Publisher
Hitachi Hi-Rel
Year
Year not stated
Document language
Unverified
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Hitachi Hi-Rel Hitachi Hi-Rel HM33 IT UPS brochure Ver.3, p.4. Hitachi Hi-Rel. https://www.hitachi-hirel.com/pdf/catalogues/uninterruptible-power-supply-ups/HM33-Series-IT-UPS-46353-Ver.3.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.