TECNED STS (SF/D) static transfer switches

TECNED

TECNED's single-phase STS (SF/D) series offers break-before-make static transfer switches from 25 to 500 A, with 1- or 2-pole construction, an LCD digital controller and a 150% overload rating for 1 minute.

On this page

Overview

TECNED is a Dutch critical-power manufacturer. The product page introduces the STS (SF/D) family: static transfer switches with single-phase input and output and current ratings from 25 A to 500 A, designed to move a load safely between two independent sources. The page is a manufacturer product description rather than a guide or standard, and it does not list individual catalogue model numbers.

The series can be ordered as 1-pole or 2-pole static switching. Standard functions are source selection, automatic transfer control, source locking, input voltage monitoring and alarm supervision for out-of-tolerance conditions. Transfer can be automatic, manual or remote. The ST(D) model adds a digital controller with an LCD for real-time monitoring, parameter setting, diagnostics and event and alarm logging.

The specification table gives input voltages of 110/120/200/220/230/240/277 V (2 wire plus earth), a voltage tolerance of 180/264 Vac (phase to neutral), 50 or 60 Hz and an adjustable frequency window of 2-10%. Overload capacity is 150% for 1 minute and 200% for 10 seconds, and the load power factor may range from 0.6 lagging to 0.9 leading. Operating ambient is -10 to +40 °C and the altitude limit is 1000 m.

Compliance is stated as IEC/EN 62040-1 for safety, 55011 for EMC, IEC 60146 and the CE mark. The enclosure is an Aluzinc frame with RAL 7035 powder coat. For a data-centre designer this product reads as a smaller single-phase option, suited to critical single-phase loads such as control and monitoring boards, rather than a substitute for large three-phase STS units.

Key points

  1. Current range 25 A to 500 A, single-phase input and output.
  2. 1-pole or 2-pole static switch option.
  3. Break-before-make transfer; automatic, manual or remote transfer modes.
  4. Input voltages 110/120/200/220/230/240/277 V, tolerance 180/264 Vac, 50/60 Hz, adjustable 2-10% frequency window.
  5. Overload: 150% for 1 minute and 200% for 10 seconds; power factor 0.6 lagging to 0.9 leading.
  6. Operating temperature -10 to +40 °C, storage -20 to +70 °C, altitude 1000 m.
  7. Standards: IEC/EN 62040-1 (safety), 55011 (EMC), IEC 60146, CE.

Using it in design

  • Where connecting both sources at once is unacceptable, compare the break-before-make behaviour and interruption time with the load's tolerance.
  • Select the single-phase critical load current against the 25-500 A range and the 150% / 1 minute overload rating; load power factor must stay between 0.6 lagging and 0.9 leading.
  • Record the source frequency window (2-10%) as a monitoring setting, matched to generator and mains frequency deviation.
  • Ask the manufacturer for derating above 1000 m altitude and above 40 °C ambient.

Who should read it

Electrical designers and UPS integrators choosing a source-transfer solution for single-phase critical loads.

Document contents

  1. Static Transfer Switches STS (SF/D)
  2. Key features
  3. ST (D) specifications: input, output and general

Publication details

Authors
TECNED
Publisher
TECNED
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

TECNED TECNED STS (SF/D) static transfer switches. TECNED. https://tecned.com/sts/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.