TECNED STS (SF/D) static transfer switches
TECNED
TECNED's single-phase STS (SF/D) series offers break-before-make static transfer switches from 25 to 500 A, with 1- or 2-pole construction, an LCD digital controller and a 150% overload rating for 1 minute.
On this page
Overview
TECNED is a Dutch critical-power manufacturer. The product page introduces the STS (SF/D) family: static transfer switches with single-phase input and output and current ratings from 25 A to 500 A, designed to move a load safely between two independent sources. The page is a manufacturer product description rather than a guide or standard, and it does not list individual catalogue model numbers.
The series can be ordered as 1-pole or 2-pole static switching. Standard functions are source selection, automatic transfer control, source locking, input voltage monitoring and alarm supervision for out-of-tolerance conditions. Transfer can be automatic, manual or remote. The ST(D) model adds a digital controller with an LCD for real-time monitoring, parameter setting, diagnostics and event and alarm logging.
The specification table gives input voltages of 110/120/200/220/230/240/277 V (2 wire plus earth), a voltage tolerance of 180/264 Vac (phase to neutral), 50 or 60 Hz and an adjustable frequency window of 2-10%. Overload capacity is 150% for 1 minute and 200% for 10 seconds, and the load power factor may range from 0.6 lagging to 0.9 leading. Operating ambient is -10 to +40 °C and the altitude limit is 1000 m.
Compliance is stated as IEC/EN 62040-1 for safety, 55011 for EMC, IEC 60146 and the CE mark. The enclosure is an Aluzinc frame with RAL 7035 powder coat. For a data-centre designer this product reads as a smaller single-phase option, suited to critical single-phase loads such as control and monitoring boards, rather than a substitute for large three-phase STS units.
Key points
- Current range 25 A to 500 A, single-phase input and output.
- 1-pole or 2-pole static switch option.
- Break-before-make transfer; automatic, manual or remote transfer modes.
- Input voltages 110/120/200/220/230/240/277 V, tolerance 180/264 Vac, 50/60 Hz, adjustable 2-10% frequency window.
- Overload: 150% for 1 minute and 200% for 10 seconds; power factor 0.6 lagging to 0.9 leading.
- Operating temperature -10 to +40 °C, storage -20 to +70 °C, altitude 1000 m.
- Standards: IEC/EN 62040-1 (safety), 55011 (EMC), IEC 60146, CE.
Using it in design
- Where connecting both sources at once is unacceptable, compare the break-before-make behaviour and interruption time with the load's tolerance.
- Select the single-phase critical load current against the 25-500 A range and the 150% / 1 minute overload rating; load power factor must stay between 0.6 lagging and 0.9 leading.
- Record the source frequency window (2-10%) as a monitoring setting, matched to generator and mains frequency deviation.
- Ask the manufacturer for derating above 1000 m altitude and above 40 °C ambient.
Who should read it
Electrical designers and UPS integrators choosing a source-transfer solution for single-phase critical loads.
Document contents
- Static Transfer Switches STS (SF/D)
- Key features
- ST (D) specifications: input, output and general
Publication details
- Authors
- TECNED
- Publisher
- TECNED
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
TECNED TECNED STS (SF/D) static transfer switches. TECNED. https://tecned.com/sts/
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.