BPC Energy Static Transfer Switches (50-800 A)
Original title BPC Energy Static Transfer Switches: Technical Specification
BPC Energy
BPC Energy static transfer switches: automatic or manual transfer between two AC sources, under 4 ms for synchronous sources, 50-800 A, bringing 2N architecture to single-fed loads.
On this page
Overview
The product page presents BPC Energy's automatic static transfer switches (STS). The device transfers automatically or manually between two AC power supplies; the page gives a transfer time of less than a quarter of a cycle. Installing an STS achieves 2N architecture and lets single-fed loads always be supplied by the best source. Switching is automatic when the incoming supply leaves a user-defined window, or manual when an operator forces it from the mimic panel or a remote connection.
Features: selectable preferred source and transfer method, break-before-make transfer, under 5 ms between synchronised sources (the technical row gives under 4 ms for synchronous and under 10 ms for non-synchronous sources), a switched-neutral option that keeps the sources isolated, and adjustable delay (non-synchronous). Ratings are 50, 100, 150, 200, 250, 300, 400, 600 and 800 A.
Overload capability is 0-100% continuous, 101-150% for 1 min, 151-200% for 10 s and over 200% for 250 ms. Protections are output overload and short circuit, over-temperature, backfeed and SCR fault; programmable relay outputs (dry contacts) are provided. The page notes better maintainability of switchboards in 2N distribution and protection against source interruptions or distribution-line failures.
Key points
- The STS transfers automatically or manually between two independent AC sources.
- Transfer time: <4 ms for synchronous and <10 ms for non-synchronous sources; under a quarter cycle per the page text.
- Ratings: 50, 100, 150, 200, 250, 300, 400, 600, 800 A.
- Overload: 100% continuous, 101-150% 1 min, 151-200% 10 s, >200% 250 ms.
- Protections: output overload and short circuit, over-temperature, backfeed, SCR fault.
- Switched-neutral option keeps the sources isolated.
- Programmable dry-contact relay outputs; mimic panel and remote control.
Using it in design
- Feed single-corded loads from two independent UPS lines through an STS in a 2N architecture.
- If sources are not synchronised, compare the up to 10 ms transfer with load tolerance.
- Where neutral isolation between sources is needed, write the switched-neutral option into the specification.
- Choose STS current from the load and the short-time overload curve up to 200%.
Who should read it
Data-centre electrical engineers designing 2N power distribution and critical-load transfer.
Document contents
- Static transfer switches
- Features
- Technical specification
- Accreditations and certifications
Publication details
- Authors
- BPC Energy
- Publisher
- BPC Energy
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
BPC Energy BPC Energy Static Transfer Switches: Technical Specification. BPC Energy. https://www.bpc-ups.com/products/switches-regulators/static-transfer-switches
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.